12
G
AERASGARD
®
RPS - SD ⁄ RFTM - PS - xx
Rev. 2021 - V11
Schematic diagram
RFTM - PS - CO2 - W
Schematic diagram
RPS - SD
4
5
6
1 2 3
SET REL.
OFFSET
ZERO
CO2 CO2
r.H.
°C
12
11
13
1 2 3 4 5 6 7 8 9
ON
DIP
ON
ON
PS
CO2 Mode
NC
= Normally Closed
COM
= Common
NO
= Normally Open
Plug for
display
–UB GND
+UB 2
4V A
C/DC
Output CO
2
[ppm
]
NC
COM
NO
relay
switch
point
humidity [% r.H.]
fine dust [µg/m
3
]
Outputs
temperature [°C]
1 2 3
1 2 3
ON
DIP
PS
–UB GND
+UB 2
4V A
C/DC
Output PM [µ
g/m
³]
DIP switch
RFTM - PS
- xx
Fine dust (PM) Measuring range
DIP 1 DIP 2
0...50 µg/m
3
OFF
OFF
0...100 µg/m
3
(default)
O N
OFF
0...300 µg/m
3
OFF
O N
0...500 µg/m
3
O N
O N
Fine dust (PM) Particle size
DIP 3
PM 2.5 (default)
O N
PM 10
OFF
CO2
content
DIP 4
0...2000 ppm (default)
OFF
0...5000 ppm
O N
CO2
automatic zero point
DIP 6
deactivated
OFF
activated (default)
O N
Relay assignment
DIP 7 DIP 8
CO2 (default) 600...1900 ppm / 900...4700 ppm
OFF
OFF
Fine dust
10 %...95 % of measuring range
O N
OFF
Temperature +5...+48 °C
OFF
O N
Humidity
10...95 % r.H.
O N
O N
Output
DIP 9
Voltage 0 -10 V (default)
OFF
Current 4...20 mA
O N
Note:
DIP 5
is not assigned !
DIP switch
RPS - SD
Fine dust (PM) Measuring range
DIP 1 DIP 2
0...50 µg/m
3
OFF
OFF
0...100 µg/m
3
(default)
O N
OFF
0...300 µg/m
3
OFF
O N
0...500 µg/m
3
O N
O N
Fine dust (PM) Particle size
DIP 3
PM 2.5 (default)
O N
PM 10
OFF