19
F
AERASGARD
®
RPS - SD ⁄ RFTM - PS - xx
Rev. 2021 - V11
Schéma de raccordement
RFTM - PS - CO2 - W
Schéma de raccordement
RPS - SD
1 2 3
1 2 3
ON
DIP
PS
–UB GND
+UB 2
4V A
C/DC
Output PM [µ
g/m
³]
4
5
6
1 2 3
SET REL.
OFFSET
ZERO
CO2 CO2
r.H.
°C
12
11
13
1 2 3 4 5 6 7 8 9
ON
DIP
ON
ON
PS
CO2 Mode
NC
= Normally Closed
COM
= Common
NO
= Normally Open
Plug for
display
–UB GND
+UB 2
4V A
C/DC
Output CO
2
[ppm
]
NC
COM
NO
relay
switch
point
humidity [% r.H.]
fine dust [µg/m
3
]
Outputs
temperature [°C]
Interrupteur DIP
RFTM - PS
- xx
Particules fines (PM) Plage de mesure
DIP 1 DIP 2
0...50 µg/m
3
OFF
OFF
0...100 µg/m
3
(default)
O N
OFF
0...300 µg/m
3
OFF
O N
0...500 µg/m
3
O N
O N
Particules fines (PM) Taille de particules
DIP 3
PM 2,5 (default)
O N
PM 10
OFF
Teneur en CO2
DIP 4
0...2000 ppm (default)
OFF
0...5000 ppm
O N
Point zéro automatique CO2
DIP 6
désactivé
OFF
activé (default)
O N
Affectation relais
DIP 7 DIP 8
CO2 (default) 600...1900 ppm / 900...4700 ppm
OFF
OFF
Particules fines 10 %...95 % de la plage de mesure
O N
OFF
Température +5...+48 °C
OFF
O N
Humidité
10...95 % h.r.
O N
O N
Sortie
DIP 9
Tension 0 -10 V (default)
OFF
Courant 4...20 mA
O N
Remarque:
DIP 5
n’est pas affecté !
Interrupteur DIP
RPS - SD
Particules fines (PM) Plage de mesure
DIP 1 DIP 2
0...50 µg/m
3
OFF
OFF
0...100 µg/m
3
(default)
O N
OFF
0...300 µg/m
3
OFF
O N
0...500 µg/m
3
O N
O N
Particules fines (PM) Taille de particules
DIP 3
PM 2,5 (default)
O N
PM 10
OFF