General notes

–  This device may only be used in pollutant-free non-precipitating air without above-atmospheric or below-atmospheric pressure at the sensor  element. 

–  On outdoor and duct sensors, the sinter filter of the senor element protects the humidity sensor against potential dust exposure.  

In case of pollution  ⁄  contamination, this filter should be cleaned on a regular basis.

–  Dust and pollution falsify measurement results and are to be avoided. Slight pollution and dust sediments can be removed by using compressed air. 

–  Touching the humidity element is under any circumstances to be avoided, as that would result in considerable mismeasurements.

–  In case of pollution, we recommend cleaning and recalibration in the factory.

–  In any case, the sensor must not get in contact with chemicals or other cleaning agents.

–  The relative humidity of 0 ...100 % is indicated by an output signal of 0 -10 V or 4...20 mA. 

The device operating range covers 10.0 ... 99.9 % r. H. Outside of that range, mismeasurements or increased deviations may occur.

–  When several sensors (0  -10 V) are connected to one voltage supply of 24 V  AC, correct polarity must be regarded as otherwise the  alternating  voltage 

source may be short-circuited. 

–  The voltage outputs are short-circuit proof. Applying overvoltage or voltage supply to the voltage output will destroy the device.

–  If this device is operated beyond the specified range, all warranty claims are forfeited.

Our “General Terms and Conditions for Business“ together with the “General Conditions for the Supply of Products and Services of the Electrical and 
Electronics Industry“ (ZVEI conditions) including supplementary clause “Extended Retention of Title“ apply as the exclusive terms and conditions.

In addition, the following points are to be observed:
–  These instructions must be read before installation and putting in operation and all notes provided therein are to be  regarded!
–  Devices must only be connected to safety extra-low voltage and under dead-voltage condition. To avoid damages and errors at the device (e.g. by voltage 

induction) shielded cables are to be used, laying parallel with current-carrying lines is to be avoided, and EMC directives are to be observed.

–  This device shall only be used for its intended purpose. Respective safety regulations issued by the VDE, the states, their  control authorities, the TÜV and 

the local energy supply company must be observed. The purchaser has to adhere to the building and safety regulations and has to prevent perils of any kind.

–  No warranties or liabilities will be assumed for defects and damages arising from improper use of this device.
–  Consequential damages caused by a fault in this device are excluded from warranty or liability.
–  These devices must be installed and commissioned by authorised specialists.
–  The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are exclusively valid. Deviations 

from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous improvement of our products.

–  In case of any modifications made by the user, all warranty claims are forfeited.
–  This device must not be installed close to heat sources (e.g. radiators) or be exposed to their heat flow.  

Direct sun irradiation or heat  irradiation by similar sources (powerful lamps, halogen spotlights) must absolutely be avoided.

–  Operating this device close to other devices that do not comply with EMC directives may influence functionality.
–  This device must not be used for monitoring applications, which serve the purpose of protecting persons against hazards or injury,  

or as an EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes.

–  Dimensions of enclosures or enclosure accessories may show slight tolerances on the specifications provided in these instructions.
–  Modifications of these records are not permitted.
–  In case of a complaint, only complete devices returned in original packing will be accepted.

Notes on commissioning: 

This device was calibrated, adjusted and tested under standardised conditions. When operating under deviating conditions, we recommend performing an 
initial manual adjustment on-site during commissioning and subsequently at regular intervals. 

Commissioning is mandatory and may only be performed by qualified personnel!  
These instructions must be read before installation and commissioning and all notes provided therein are to be regarded!

Summary of Contents for HYDRASGARD AFTF-20-VA ID Series

Page 1: ...ure sensors 1 8 calibratable with multi range switching and active output F Notice d instruction Sonde d humidit et de temp rature 1 8 pour montage en saillie talonnable avec commutation multi gamme e...

Page 2: ...143 61 126 8 8 17 126 8 8 17 Geh use mit M12 Steckverbinder Housing with M12 connector Bo tier avec connecteur M12 M12 Geh use mit Kabelverschraubung Housing with cable gland Bo tier avec presse toupe...

Page 3: ...erende Luft Abweichung Feuchte typisch 1 8 10 90 r H bei 25 C sonst 2 0 Ausgang Feuchte 0 10 V bei U Variante 4 20 mA bei I Variante TEMPERATUR Messbereich Temperatur Mehrbereichsumschaltung siehe Tab...

Page 4: ...0 8 8 20 4 0 10 4 25 5 0 12 0 30 6 0 13 6 35 7 0 15 2 40 8 0 16 8 45 9 0 18 4 50 10 0 20 0 HYGRASGARD AFTF 20 VA Aufputz Feuchte und Temperaturf hler 1 8 ID HYGRASGARD AFTF 20 VAQ Aufputz Feuchte und...

Page 5: ...undbeleuchtung Shield 3 Leiter Anschluss f r Ger te ohne mit Display unbeleuchtet 4 Leiter Anschluss f r Ger te mit beleuchtetem Display Bei der I Variante ist der Feuchte pfad zwingend anzuschlie en...

Page 6: ...de integriert Diese interne Einweggleichrichtung erlaubt auch den Betrieb mit AC Versorgungs spannung bei 0 10 V Ger ten Das Ausgangssignal ist mit einem Messger t abzugreifen Hierbei wird die Ausgang...

Page 7: ...Dieses Ger t ist nur f r den angegebenen Verwendungszweck zu nutzen dabei sind die entsprechenden Sicherheitsvorschriften des VDE der L nder ihrer berwachungsorgane des T V und der rtlichen EVU zu bea...

Page 8: ...Deviation in humidity typically 1 8 10 90 r H at 25 C otherwise 2 0 Output humidity 0 10 V for U variant 4 20 mA for I variant TEMPERATURE Measuring range temperature multi range switching see table...

Page 9: ...12 0 30 6 0 13 6 35 7 0 15 2 40 8 0 16 8 45 9 0 18 4 50 10 0 20 0 ACCESSORIES SF M Metal sinter filter 16 mm L 32 mm exchangeable stainless steel V4A 1 4404 7000 0050 2200 100 WS 01 Sun and ball impa...

Page 10: ...ut temperature 4 20mA in C UB GND optional for LCD backlighting 3 wire connection for devices with without display not illuminated 4 wire connection for devices with illuminated display At the I varia...

Page 11: ...tage reverse polarity protection a one way rectifier or reverse polarity protection diode is integrated in this device variant This internal one way rectifier also allows operating 0 10 V devices on A...

Page 12: ...ed and EMC directives are to be observed This device shall only be used for its intended purpose Respective safety regulations issued by the VDE the states their control authorities the T V and the lo...

Page 13: ...t humidit typique 1 8 10 90 h r 25 C sinon 2 0 Sortie humidit 0 10 V pour variante U 4 20 mA pour variante I TEMP RATURE Plage de mesure temp rature commutation multi gamme voir tableau 35 35 C 35 75...

Page 14: ...0 30 6 0 13 6 35 7 0 15 2 40 8 0 16 8 45 9 0 18 4 50 10 0 20 0 ACCESSOIRES SF M filtre fritt en m tal 16 mm L 32 mm rempla able en acier inox V4A 1 4404 7000 0050 2200 100 WS 01 protection contre le s...

Page 15: ...N 0 80 C O N OFF Affectation des plots de connexion M12 Affectation des plots de connexion M12 AFTF xx U AFTF xx I 1 2 3 4 5 45 1 2 3 4 5 UB 24V AC DC Output humidity 0 10V r H Output temperature 0 1...

Page 16: ...re l inversion de polarit c d elle comprend un redressement demi onde diode de redressement Gr ce cette diode de redressement int gr e les appareils 0 10 V peuvent galement tre aliment s en courant al...

Page 17: ...ll le avec des c bles de puissance les directives CEM sont respecter Cet appareil ne doit tre utilis que pour l usage qui est indiqu en respectant les r gles de s curit correspondantes de la VDE des L...

Page 18: ...2 2 24 0 100 95 1 8 10 90 25 C 2 0 0 10 B U 4 20 I 35 35 C 35 75 C 0 50 C 0 80 C 35 85 C 30 80 C 0 2 K 25 C 0 10 B U 4 20 I 0 14 1 5 V2A 1 4305 M 20 x 1 5 6 12 M12 5 A DIN EN 61076 2 101 V4A 1 4571 14...

Page 19: ...0 0 7 5 1 25 1 4 6 3 20 2 1 7 4 15 2 9 8 6 10 3 6 9 7 5 4 3 10 9 0 5 0 12 0 5 5 7 13 1 10 6 4 14 3 15 7 1 15 4 20 7 9 16 6 25 8 6 17 7 30 9 3 18 9 35 10 0 20 0 0 50 C C UA B IA A 0 0 0 4 0 5 1 0 5 6 1...

Page 20: ...perature 4 20mA C UB GND optional for LCD backlighting Shield 3 4 I DIP 1 DIP 2 35 75 C O N O N 35 35 C OFF OFF 0 50 C default OFF O N 0 80 C O N OFF 1 2 3 4 1 2 3 4 5 6 ON DIP C offset r H Plug for d...

Page 21: ...range 4 20 AFTF xx U 0 10 AFTF xx I 4 20 A 2 1 2 3 4 230V AC 24VAC DC PLC PC UB 24V AC DC Output humidity in r H 0 10V Output temperature in C 0 10V UB GND 1 2 3 4 230V AC 24V DC UB 24V DC Output humi...

Page 22: ...22 r 0 100 0 10 4 20 10 0 99 9 0 10 24 ZVEI VDE EMV...

Page 23: ...ol their particular suitability must be verified by each customer and or end user themselves Existing property rights must be observed We warrant the faultless quality of our products as stated in our...

Page 24: ...24 HYGRASGARD AFTF 20 VA D G F r AFTF 20 VA AFTF 20 VAQ AFTF 20 VA LCD AFTF 20 VAQ LCD...

Reviews: