General notes

Connecting scheme 

Parallel operation

Connecting scheme 

Individual operation

SUPPLY  VOLTAGE :

For operating voltage reverse polarity protection, a one-way rectifier or 
reverse polarity protection diode is integrated in this device variant. 

 

This internal one-way rectifier also allows operating 0 - 10 V devices on AC 
supply voltage.

The output signal is to be tapped by a measuring instrument. Output 
 voltage is measured her against zero potential (O V) of the input voltage!

When this device is operated on 

DC supply voltage

,  the operating voltage 

input UB+ is to be used for 15...36 V DC supply and UB – or GND for ground 
wire!

When several devices are supplied by one 24 V

 AC voltage supply

, it is to 

be ensured that all ”positive“ operating voltage input terminals (+) of the 
field devices are connected with each other and all ”negative“ operating 
voltage input terminals (–) (= reference  potential) are connected together 
(in-phase connection of field devices). All outputs of field devices must be 
referenced to the same potential!

In case of reversed polarity at one field device, a supply voltage short- 
circuit would be caused by that device. The consequential short-circuit 
current flowing through this field device may cause damage to it.

Therefore, pay attention to correct wiring!

Circuitry

Circuitry

0...10V

0V/GND

0...10V

0V/GND

Power supply

AC 24V~ 

0V

DC 15-36V =  GND

Circuitry

0...10V

0V/GND

V

Power supply

AC 24V~ 

0V

DC 15-36V =  GND

–  This device must only be used in non-precipitating air without above-atmospheric or below-atmospheric pressure at the sensor element. 
–  To achieve optimum measurement results, provide for good intermixture of air at the measuring point 
–  Dust and contamination falsify measurement results and are to be avoided. Slight pollution and dust deposits can be removed by using compressed air. 
–  Touching the humidity element is under any circumstances to be avoided, as that would result in considerable mismeasurements.
– In case of pollution, we recommend cleaning and recalibration in the factory. 
– In any case, the sensor must not get in contact with chemicals or other cleaning agents.
– Prevent these devices from exposure to direct influence of water, e.g. splash water. 
– If this device is operated beyond the specified range, all warranty claims are forfeited.

Our “General Terms and Conditions for Business“ together with the “General Conditions for the Supply of Products and Services of the Electrical and 
 Electronics Industry“ (ZVEI conditions) including supplementary clause “Extended Retention of Title“ apply as the exclusive terms and conditions.

In additionIn addition, the following points are to be observed:
– These instructions must be read before installation and putting in operation and all notes provided therein are to be  regarded!
–  Devices must only be connected to safety extra-low voltage and under dead-voltage condition. To avoid damages and errors the device (e.g. by voltage 

induction) shielded cables are to be used, laying parallel with current-carrying lines is to be avoided, and EMC directives are to be observed.

–  This device shall only be used for its intended purpose. Respective safety regulations issued by the VDE, the states, their  control authorities, the TÜV 

and the local energy supply company must be observed. The purchaser has to adhere to the building and safety regulations and has to prevent perils 
of any kind.

–  No warranties or liabilities will be assumed for defects and damages arising from improper use of this device.
– Consequential damages caused by a fault in this device are excluded from warranty or liability.
– These devices must be installed by authorised specialists only.
– The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are exclusively valid. 

 Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous improve- 
ment of our products.

– In case of any modifications made by the user, all warranty claims are forfeited.
– This device must not be installed close to heat sources (e.g. radiators) or be exposed to their heat flow. Direct sun irradiation or heat  irradiation by 

similar sources (powerful lamps, halogen spotlights) must absolutely be avoided.

–  Operating this device close to other devices that do not comply with EMC directives may influence functionality.
– This device must not be used for monitoring applications, which solely serve the purpose of protecting persons against hazards or injury, or as an 

EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes.

–  Dimensions of enclosures or enclosure accessories may show slight tolerances on the specifications provided in these instructions.
– Modifications of these records are not permitted.
– In case of a complaint, only complete devices returned in original packing will be accepted.

These instructions must be read before installation and putting in operation and all notes provided therein are to be regarded!

Summary of Contents for HYGRASREG RH-30

Page 1: ...t stetigem schaltenden Ausgang G Operating Instructions Mounting Installation Room hygrostats and humidity sensors electronic two step with continuous switching outputs F Notice d instruction Hygrosta...

Page 2: ...HYGRASREG RH 30 D G F r Ma zeichnung RH 30 Dimensional drawing Plan cot RH 30U mit Inneneinstellung with internal setting avec r glage interne...

Page 3: ...a e Geh use 98 x 106 x 34 mm Frija II Montage Wandmontage oder auf UP Dose 55 mm Unterteil mit 4 Loch f r Befestigung auf senkrecht oder waagerecht installierten UP Dosen f r Kabeleinf hrung hinten mi...

Page 4: ...rsorgung AC DC 1 24 V 15 36 V DC 3 0 V GND Ausgang AC DC 2 r F 0 10 V 0 10 V 4 A1 Relais 1 ffnerkontakt 5 W1 Relais 1 Wechselkontakt 6 B1 Relais 1 Schlie erkontakt 7 A2 Relais 2 ffnerkontakt 8 W2 Rela...

Page 5: ...ugnisse und Leistungen der Elektro industrie ZVEI Bedingungen zuz glich der Erg nzungsklausel Erweiterter Eigentumsvorbehalt Au erdem sind folgende Punkte zu beachten Vor der Installation und Inbetrie...

Page 6: ...tallation wall mounting or on in wall flush box 55 mm base with 4 hole for mounting on vertically or horizontally installed in wall flush boxes for cable entry from the back with predetermined breakin...

Page 7: ...2 Relay 2 Breaker contact 8 W2 Relay 2 Changeover contact 9 B2 Relay 2 Normally open contact Mode 1 Switch points for both relay outputs can be defined independent from each other in the range of 5 95...

Page 8: ...Electrical and Electronics Industry ZVEI conditions including supplementary clause Extended Retention of Title apply as the exclusive terms and conditions In additionIn addition the following points...

Page 9: ...65 C Bo tier mati re plastique mat riau ABS couleur blanc pur similaire RAL 9010 Dimensions du bo tier 98 x 106 x 34 mm Frija II Montage montage mural ou sur bo te d encastrement 55 mm partie inf rieu...

Page 10: ...eur 9 B2 relais 2 contact NO Mode 1 Le potentiom tre R1 pour relais 1 R2 pour relais 2 voir sch ma de raccordement permet de d terminer pour chacun des deux relais des points de commutation ind pendan...

Page 11: ...entre la soci t S S et ses clients Il convient en outre de respecter les points suivants Avant de proc der toute installation et la mise en service veuillez lire attentivement la pr sente notice et t...

Page 12: ...98 x 106 x 34 Frija II 55 III EN 60 730 IP 20 EN 60 529 0 14 2 5 2 CE 2004 108 EC 36 x15 x 1 4 5 3 S1 4 5 2 7 8 3 S2 7 8 2 0 10 0 100 1 5 6 S1 5 6 2 8 9 S2 8 9 2 0 10 0 100 2 RH 30 RH 30W 5 95 2 x 1x...

Page 13: ...our when preset limit value is exeeded Switching back when humidity falls below preset limit value with 3 r H hysteresis below preset RH 30 1 2 3 4 5 6 7 8 9 GND UB 24V AC DC Humidifying Relay 1 Dehum...

Page 14: ...r 0 10 0 UB 15 36 UB GND 24 Circuitry Circuitry 0 10V 0V GND 0 10V 0V GND Power supply AC 24V 0V DC 15 36V GND Circuitry 0 10V 0V GND V Power supply AC 24V 0V DC 15 36V GND ZVEI VDE EMV...

Page 15: ...he bottom frame slightly Pull top cover forward and hold it Pour ouvrir le bo tier placer le tournevis 2 0 au centre de l encoche pousser vers le bas et soulever l g rement le cadre inf rieur Tirer le...

Page 16: ...HYGRASREG RH 30 D G F r...

Reviews: