14
G
PREMASREG
®
716x
Setup button assignment:
SELECT
Pressing for more than 5 seconds =>
switches to setup mode
A short push following thereafter =>
switches to the next input value respectively
terminates setup mode
UP
▲
(arrow pointing up) increases the input value.
Keeping it depressed increases the increment step by step
by which the parameter is increased.
DOWN
▼
(arrow pointing down) decreases the input value.
Pressing for longer increases the increment
step by step by which the parameter is decreased.
1
2
3
UP
DOWN
SELECT
AUTO ZERO
SET
min. max.
min. max.
OFFSET
1 2 3 4 5 6
ON DIP
12
11
13
1
2
3
UP
DOWN
SELECT
AUTO ZERO
SET
min. max.
min. max.
OFFSET
1 2 3 4 5 6
ON DIP
12
11
13
Configuring the measuring function:
The first line of the display shows the measured
ACTUAL value
for volume flow rate, pressure,
contamination degree, or level.
The second line shows the corresponding
unit
(e.g.: Pa, m
3
/h, %, cm).
In the third line, the
switching status of the relay
(circuit completed/empty) with the corresponding set value
can be read.
If the set value can no longer be represented,
the "
limit
" designation is issued instead of the value.
If the switching function is deactivated (DIP 3 = OFF),
the third line remains blank empty.
On devices fitted with a valve, the third line is used to
display the time remaining
until the next
automatic zero point correction (optional).
Display readout:
Setting the function type
Press the
SELECT
pushbutton to activate setup mode.
Use the two
UP
and
DOWN
pushbuttons to select the desired function
type (formulas for the function types, see page 11).
Type 0:
Volume flow rate
Type 1:
Differential pressure
Type 2:
Filter contamination
Type 3:
Liquid level
Complete the entry by pressing the
SELECT
pushbutton.
After selecting the measuring function, you are automatically guided
through the parameters that must be set (see next page).