Electronic single-room controllers ⁄ clock thermostats THERMASREG
®
RTR-E-UP with internal sensor or 4-meter remote sensor for in-wall
installation for temperature monitoring and control, activate any kind of heating system and valves (closed when currentless), as room tem-
perature controller, room thermostat, floor temperature controller, or clock controller, e. g. for electric floor direct heating systems, for
bathrooms, for night storage, wall, ceiling and gas heating systems.
TECHNICAL DATA:
Power supply: .............................. 230 V AC, 50 Hz
Temperature sensor: ................. NTC according to DIN 44574, sensor extension up to max. 50 m,
with double insulation according to EN 60730-2-1
Control range: ............................. see table
+ 15 °C ... + 30 °C for room temperature controllers
+ 10 °C ... + 60 °C for floor temperature controllers
+ 15 °C ... + 30 °C and
+ 20 °C ... + 60 °C for combined controllers
Output: ......................................... 1x normally open contact (single ended)
Switching capacity: .................... 3.6 kW
Switching current: ..................... 16 A (ohmic load)
(Contact load)
Safety: .......................................... with sensor breakage and sensor short circuit protection
(in case of sensor breakage or sensor short circuit heating is switched of)
Operating difference: ................ ca. 0.6 K
Enclosure: .................................... plastic, colour pure white (similar RAL 9010)
Dimensions: ................................. 80 x 80 x16 mm
Electrical connection: ............... 0.14 - 2.5 mm
2
via terminal screws on circuit board
Temperature
range limitation: ......................... in the turning knob
Installation: .................................. in in-wall flush box Ø = 55 mm
Protection class: ........................ II (according to EN 60 730)
Protection type:.......................... IP 30 (according to EN 60 529)
Standards: ................................... CE conformity,
electromagnetic compatibility
according to EN 61 326 + A1 + A2,
EMC directive 2004 ⁄ 108 ⁄ EC,
low-voltage directive 2006 ⁄ 95 ⁄ EC