Type ⁄ WG1 

Application

FM 020

 

Field bus module (Modbus) for climate control convectors, heating and air conditioning units

Note: 

For manual intervention and room temperature measurement, an analog room device is used. 

Analog inputs

The device has four passive analog inputs:

• Room temperature (Pt1000 sensor)  

• Setpoint adjustment (potentiometer 0...500 Ohm)

• Step switch for fan coil convectors   

Auto:  500 Ohm or more (not connected)  
Off:  100 Ohm or less (short-circuited) 
St1:  180 Ohm 
St2:  270 Ohm 
St3:  390 Ohm 

• Reserve (for a Pt1000 sensor)  

This has no influence on the control functions, however it can be read out and displayed by the central building control system. 

When the setpoint adjustment collects a value of more than 1500  Ohm (not connected), the correction value is 0  K. The correction value an be 
adjusted in the range of 0 ... 500  Ohm using configuration software. Standard values are – 3.5 ...+ 3.5  K. 

Analog outputs

The device has four passive analog outputs: 

The analog outputs provide a 0...10 V signal for the activation of heating and cooling valves.  
Reference potential for 0...10 V is the same as for 24 V AC, reference point G0.  
The same signal converted to 24 V AC pulse width modulated optimised for thermovalves is available at DO1 and DO2.

Digital inputs

The device has four potential-free digital inputs, which are operated at 24 V AC (the G – G0 voltage):  

• Input – presence, switches to normal temperature (daytime) ⁄ setback (nighttime)

• Input – window contact, switches to OFF (setback) when window is open while heating, or when a dew point sensor responds in cooling operation.  

• Input – changeover contact for 2-pipe systems, signals that fan coil convector is supplied with coldwater instead of hot water.  

This is connected to a mechanical thermostat being installed at the water inflow.  
Instead, the switchover signal can also be set remote controlled via the bus.

• Input – party button, for connecting the party button.  

Upon short activation, the controller switches over from setback (nighttime) to normal temperature (daytime) for a period of 2 hours.  
Afterwards it switches back to setback (nighttime).  
This function overrides the timer switch programme, and itself is overridden by the window contact input. 

Digital outputs

The device has four digital outputs: 

The ventilator steps are either controlled automatically (upon  control offset, or better via a PI controller output),  
or manually (if this function is set). 1 to 3 ventilator steps can be selected in the configuration software.  
Simultaneously only one switching step can be active. There is a safety pause of 1 s between switching steps.

The semiconductor relay auxiliary contact outputs DO4 and DO5 are provided for future applications.  
However they can be actuated remote-controlled via the bus – Modbus address see Modbus table. 

Summary of Contents for THERMASREG FM Series

Page 1: ...makonvektoren Heiz und Klimager te G Operating Instructions Mounting Installation Field bus module Modbus for fan coil convectors climate control convectors heating and air conditioning units F Notice...

Page 2: ...THERMASREG FM D G F r Ma zeichnung FM010 Dimensional drawing Plan cot Ma zeichnung FM020 Dimensional drawing Plan cot 94 1 23 4 82 8 29 0 114 0 90 5...

Page 3: ...lsbreitenmodulierte Zweiweg Thyristoren PWM TRIAC zur Ansteuerung der Thermoventile Diese Regler sind zum Betrieb in einer normalen und chemisch nicht aggressiven Umgebung vorgesehen Sie bed rfen kein...

Page 4: ...ensterkontakt schaltet Normaltemperatur Absenkung AUS G Spannung f r Eing nge und Ausg nge G0 Spannung f r Eing nge und Ausg nge Referenzpunkt DO1 Ausgang Heizungsventil G gegen G0 DO2 Ausgang K hlung...

Page 5: ...nicht in dieser Firmware Version erh ltlich kann ein kommunikatives Raumger t ber einen zugeordneten Bus K2 K2 verwendet werden Das Raumger t erfasst die Raumtemperatur Sollwert Einstellung mittels D...

Page 6: ...le Eing nge die an 24 V AC der G G0 Spannung betrieben werden Eingang Anwesenheit schaltet Normaltemperatur Tag Absenkung Nacht Eingang Fensterkontakt schaltet auf AUS Absenkung wenn das Fenster offen...

Page 7: ...tor Relaisstufe 2 Q3 Ventilatorkonvektor Relaisstufe 3 COM Gemeinsamer Kontakt f r Q1 Q2 Q3 DO4 Halbleiterrelais Ausgang DO4 C4 Halbleiterrelais Ausgang DO4 DO5 Halbleiterrelais Ausgang DO5 C5 Halblei...

Page 8: ...ht den EMV Richt linien entsprechen kann zur Beeinflussung der Funktionsweise f hren Dieses Ger t darf nicht f r berwachungszwecke welche ausschlie lich dem Schutz von Personen gegen Gef hrdung oder V...

Page 9: ...er Produkte m glich Bei Ver nderungen der Ger te durch den Anwender entfallen alle Gew hrleistungsanspr che Dieses Ger t darf nicht in der N he von W rmequellen z B Heizk rpern oder deren W rmestrom e...

Page 10: ...d by a PI algorithm at the output of which pulse width modulated two way thyristors PWM TRIAC for activating the thermovalves are installed These controllers are intended for operation in a normal and...

Page 11: ...DI2 Input window contact switches normal temperature setback OFF G Voltage for inputs and outputs G0 Voltage for inputs and outputs reference point DO1 Output heating valve G against G0 DO2 Output coo...

Page 12: ...m devices with display are not applicable Alternatively not available in this firmware version a communicative room device can be used via an assigned bus K2 K2 The room unit detects the room temperat...

Page 13: ...e digital inputs which are operated at 24 V AC the G G0 voltage Input presence switches to normal temperature daytime setback nighttime Input window contact switches to OFF setback when window is open...

Page 14: ...ep 1 Q2 Fan coil convector relay step 2 Q3 Fan coil convector relay step 3 COM Common contact for Q1 Q2 Q3 DO4 Semiconductor relay output DO4 C4 Semiconductor relay output DO4 DO5 Semiconductor relay...

Page 15: ...MERGENCY STOP switch for systems or machinery or for any other comparable safety relevant purposes Dimensions of enclosures or enclosure accessories may show slight tolerances on the specifications pr...

Page 16: ...s and continuous improvement of our products In case of any modifications made by the user all warranty claims are forfeited This device must not be installed close to heat sources e g radiators or be...

Page 17: ...impulsion MLI triac pour la commande des vannes thermiques Ces r gulateurs sont con us pour une exploitation en environnement normal et chimiquement non agressif Ils ne n cessitent aucun entretien ni...

Page 18: ...male DI2 entr e contact fen tre commute la temp rature normale l abaissement ARR T G tension pour entr es et sorties G0 tension pour entr es et sorties point de r f rence DO1 sortie vanne de chauffage...

Page 19: ...tiliser un appareil d ambiance communiquant via un bus attri bu K2 K2 L appareil d ambiance mesure la temp rature ambiante Pour r gler la valeur de consigne utilisez le bouton rotatif et appuyez bri v...

Page 20: ...es num riques libres de potentiel aliment es en 24 V ca de la tension G G0 entr e pr sence commute la temp rature normale jour l abaissement nuit entr e contact fen tre commute sur ARR T abaissement s...

Page 21: ...du ventilo convecteur Q2 niveau relais 2 du ventilo convecteur Q3 niveau relais 3 du ventilo convecteur COM contact commun pour Q1 Q2 Q3 DO4 sortie relais semi conducteur DO4 C4 sortie relais semi co...

Page 22: ...tection des personnes contre les dangers ou les blessures ni comme interrupteur d arr t d urgence sur des installations ou des machines ni pour des fonctions relatives la s curit comparables Il est po...

Page 23: ...ion continue de nos produits En cas de modifications des appareils par l utilisateur tous droits de garantie ne seront pas reconnus Cet appareil ne doit pas tre utilis proximit des sources de chaleur...

Page 24: ...STA71 Danfoss TWA 24 230 5 A RS485 Modbus RTU 9600 N 8 1 Master RS485 Modbus RTU 9600 N 8 1 Slave 75 x 90 x 24 104 x 90 x 24 0 14 1 5 2 DIN II EN 60730 IP 20 EN 60529 CE EN 61326 A1 A2 89 336 EEC 73...

Page 25: ...M010 G G0 K1 K1 K2 K2 DI1 DI2 G G0 DO1 G G0 DO2 G G0 COM Q1 Q2 Q3 Q1 1 Q2 2 Q3 3 G G0 FM010 DI2 DI1 G G G0 G0 DO2 DO1 COM Q3 Q2 Q1 N L 6 7 4 3 K K MBR010 MBR011 24 V AC 230 V AC G TE G0 G0 G K1 K1 K2...

Page 26: ...1 Danfoss TWA 24 230 5 A 3 2 AO 0 10 10 20 10 10 20 RS485 Modbus RTU 9600 N 8 1 Master RS485 Modbus RTU 9600 N 8 1 Slave 113 x 90 x 24 0 14 1 5 2 DIN II EN 60730 IP 20 EN 60529 CE EN 61 326 A1 A2 89 3...

Page 27: ...1 FM020 Fieldbus Modbus Pt1000 0 500 500 Off 100 1 180 2 270 3 390 Pt1000 1500 0 K 0 500 3 5 3 5 K 0 10 0 10 GO 24 24 D01 D02 24 G G0 2 PI 1 3 1 D04 D05 Modbus Modbus...

Page 28: ...2 RS485 G 24 V AC G0 24V AC TE Q1 1 Q2 2 Q3 3 COM Q1 Q2 Q3 DO4 DO4 C4 DO4 DO5 DO5 C5 DO5 DO1 G G0 DO2 G G0 G0 DI1 G0 DI2 DI3 G0 DI4 K1 K1 K2 K2 G0 G TE AO2 AO1 G0 G0 G0 G0 G0 AI4 AI3 AI2 AI1 COM Q3 Q2...

Page 29: ...Geb udeleittechnik endet hier USR Benutzer Schalter nicht belegt INIT setzt COM auf 9600 N 8 1 und die Adresse im Geb udeleittechnik Bus auf 1 EMV VDE VDI DDC PLC 0 5 G BUS END K1 Bus Geb udeleittech...

Page 30: ...ZVEI VDE EMV VDE r...

Page 31: ...niques Copyright by S S Regeltechnik GmbH Nachdruck auch auszugsweise nur mit Genehmigung von S S Regeltechnik GmbH gestattet Reprints in part or in total are only permitted with the approval of S S R...

Page 32: ...THERMASREG FM D G F r...

Reviews: