G
Mounting and Installation
Rev. 2017 - V15 GB
READOUT IN THE DISPLAY
By default, the first line of the display shows
the
relative humidity
.
The second line shows the information about
the
switching status of the relay
(as a circuit) on the left,
and the respective
switching value
in % r.H. on the right
(switchpoint adjustable by potentiometer,
factory setting 75 % r.H.).
○
Circuit, empty
= relay in idle state
●
Circuit, full
= relay energised
1 2 3
max.
+
min.
–
Offset ±10%
GND
UB+ 24V A
C/DC
Output bede
wing 0-10V
13 11 12
1 2 3
max.
100%
87,5%
min.
75%
(default)
Normall
y
open c
ont
act
Br
eak
er
UB+ 24V A
C/DC
fr
ee
GND
Potentiometer
Swithpoint
setting
75%...100% r.H.
13 11 12
1 2 3
max.
100%
min.
75%
(default)
87,5%
Normall
y
open c
ont
act
Br
eak
er
GND
UB+ 24V A
C/DC
Output bede
wing 0-10V
Potentiometer
Swithpoint
setting
75%...100% r.H.
Schematic diagram
TW - W
Schematic diagram
TW - UW
Schematic diagram
TW - U
Connecting diagram
TW - U
1
2
3 GND
UB+ supply voltage 24V AC/DC
Output bedewing 0-10V (continuous)
1
2
3
13
11
12
GND
UB+ supply voltage 24V AC/DC
Normally open contact
(no dew)
Breaker
(dew)
changeover
(24 V)
Output bedewing 0-10V (continuous)
1
2
3
13
11
12
free
GND
UB+ supply voltage 24V AC/DC
Normally open contact
(no dew)
Breaker
(dew)
changeover
(24 V)
Connecting diagram
(condensation)
r.H. >
switchpoint
Connecting diagram
(condensation)
r.H. >
switchpoint
TW - UW
TW - W
1
2
3
13
11
12
Output bedewing 0-10V (continuous)
GND
UB+ supply voltage 24V AC/DC
Normally open contact
(no dew)
Breaker
(dew)
changeover
(24 V)
1
2
3
13
11
12
free
GND
UB+ supply voltage 24V AC/DC
Normally open contact
(no dew)
Breaker
(dew)
changeover
(24 V)
Connecting diagram
(no condensation)
r.H. <
switchpoint
Connecting diagram
(no condensation)
r.H. <
switchpoint
TW - UW
TW - W