G  

General notes

–  This device must only be used in non-precipitating air without above-atmospheric or below-atmospheric pressure at the sensor element. 
–  On outdoor and duct sensors, the sinter filter of the senor element protects the humidity sensor  against potential dust exposure.  

In case of pollution ⁄ contamination, this filter should be cleaned on a regular basis. 

–  Dust and pollution falsify measurement results and are to be avoided. Slight pollution and dust sediments can be removed by  using compressed air. 
–  Touching the humidity element is under any circumstances to be avoided, as that would result in considerable  mismeasurements. 
– In case of pollution, we recommend cleaning and recalibration in the factory. 
– In any case, the sensor must not get in contact with chemicals or other cleaning agents. 
– The relative humidity of 0...100 % is indicated by an output signal of 0 -10 V or 4 ... 20 mA. 
–  The device operating range covers 10.0 ... 99.9 %  r. H. Beyond that range, mismeasurements or increased deviations may  occur. 
– When several sensors (0 -10 V) are connected to one voltage supply of 24 V AC, correct polarity must be regarded as  otherwise the alternating 

 voltage source may be short-circuited. 

– The voltage outputs are short-circuit proof. Applying overvoltage or voltage supply to the voltage output will destroy the device. 
– If this device is operated beyond the specified range, all warranty claims are forfeited.

Our “General Terms and Conditions for Business“ together with the “General Conditions for the Supply of Products and Services of the Electrical and 
 Electronics Industry“ (ZVEI conditions) including supplementary clause “Extended Retention of Title“ apply as the exclusive terms and conditions.
In additionIn addition, the following points are to be observed:
– These instructions must be read before installation and putting in operation and all notes provided therein are to be  regarded!
– Devices must only be connected to safety extra-low voltage and under dead-voltage condition. To avoid damages and errors the device (e.g. by 

voltage induction) shielded cables are to be used, laying parallel with current-carrying lines is to be avoided, and EMC directives are to be observed.

– This device shall only be used for its intended purpose. Respective safety regulations issued by the VDE, the states, their  control authorities, the 

TÜV and the local energy supply company must be observed. The purchaser has to adhere to the building and safety regulations and has to prevent 
perils of any kind.

–  No warranties or liabilities will be assumed for defects and damages arising from improper use of this device.
– Consequential damages caused by a fault in this device are excluded from warranty or liability.
– These devices must be installed by authorised specialists only.
–  The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are exclusively valid. 

 Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous  improve- 
ment of our products.

– In case of any modifications made by the user, all warranty claims are forfeited.
– This device must not be installed close to heat sources (e.g. radiators) or be exposed to their heat flow.  

Direct sun irradiation or heat  irradiation by similar sources (powerful lamps, halogen spotlights) must absolutely be avoided.

–  Operating this device close to other devices that do not comply with EMC directives may influence functionality.
– This device must not be used for monitoring applications, which serve the purpose of protecting persons against hazards or injury,  

or as an EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes.

–  Dimensions of enclosures or enclosure accessories may show slight tolerances on the specifications provided in these instructions.
– Modifications of these records are not permitted.
– In case of a complaint, only complete devices returned in original packing will be accepted.

These instructions must be read before installation and putting in operation and all notes provided therein are to be regarded!

Connecting scheme 

Parallel operation

Connecting scheme 

Individual operation

SUPPLY VOLTAGE:

For operating voltage reverse polarity protection, a one-way rectifier or 
reverse polarity protection diode is integrated in this device variant. 

 

This internal one-way rectifier also allows operating 0 - 10 V devices on AC 
supply voltage.

The output signal is to be tapped by a measuring instrument. Output volt-
age is measured against zero potential (O V) of the input voltage!

When this device is operated on 

DC supply voltage

, the operating voltage 

input UB+ is to be used for 15...36 V DC supply and UB – or GND for ground 
wire!

When several devices are supplied by one 24 V

 AC voltage supply

, it is to 

be ensured that all ”positive“ operating voltage input terminals (+) of the 
field devices are connected with each other and all ”negative“ operating 
voltage input terminals (–) (= reference  potential) are connected together 
(in-phase connection of field devices). All outputs of field devices must be 
referenced to the same potential!

In case of reversed polarity at one field device, a supply voltage short- 
circuit would be caused by that device. The consequential short-circuit 
current flowing through this field device may cause damage to it.

Therefore, pay attention to correct wiring!

Circuitry

Circuitry

0...10V

0V/GND

0...10V

0V/GND

Power supply

AC 24V~ 

0V

DC 15-36V =  GND

Circuitry

0...10V

0V/GND

V

Power supply

AC 24V~ 

0V

DC 15-36V =  GND

Summary of Contents for HYGRASREG TW-W

Page 1: ...ing Instructions Mounting Installation Dew point control switches including strap with detached sensor head with active switching outputs F Notice d instruction Contrôleur de point de rosée y compris collier de serrage ou avec sonde déportée avec sortie active en tout ou rien r Руководство по монтажу и обслуживанию Реле контроля точки росы вкл хомут с вынесенной чувствительной головкой с активным ...

Page 2: ...Plan coté Габаритный чертеж TW prodynamische Querkonvektion pro dynamic cross convection convection transversale prodynamique Высокоэффективная поперечная конвекция TW mit Spannband zur direkten Rohrmontage including strap for installation directly on pipes y compris collier de serrage pour montage direct sur tube с хомутом непосредственный монтаж на трубах ...

Page 3: ...stärkt mit Schnellverschlussschrauben Schlitz Kreuzschlitz Kombination Farbe Verkehrsweiß ähnlich RAL 9016 Deckel ist transparent Abmaße Gehäuse 72 x 64 x 43 3 mm Tyr 1 Kabelverschraubung M 16 x 1 5 mit Zugentlastung auswechselbar max Innendurchmesser 10 4 mm Montage TW mit Spannband zur direkten Rohrmontage oder zur direkten Montage auf geraden Oberflächen z B Wänden Decken TW extern mit abgesetz...

Page 4: ...taut Öffner betaut UB Versorgungsspannung 24V AC DC Wechsler 24 V Anschlussbild betaut r H Schaltpunkt Anschlussbild betaut r H Schaltpunkt TW UW TW W 1 2 3 13 11 12 Ausgang Betauung 0 10V stetig GND Schliesser nicht betaut Öffner betaut UB Versorgungsspannung 24V AC DC Wechsler 24 V 1 2 3 13 11 12 frei GND Schliesser nicht betaut Öffner betaut UB Versorgungsspannung 24V AC DC Wechsler 24 V Anschl...

Page 5: ...d von der Gewährleistung und Haftung ausgeschlossen Die Installation der Geräte darf nur durch Fachpersonal erfolgen Es gelten ausschließlich die technischen Daten und Anschlussbedingungen der zum Gerät gelieferten Montage und Bedienungs anleitung Abweichungen zur Katalogdarstellung sind nicht zusätzlich aufgeführt und im Sinne des technischen Fortschritts und der stetigen Verbesserung unserer Pro...

Page 6: ...head combination colour traffic white similar to RAL 9016 enclosure cover is transparent Enclosure dimensions 72 x 64 x 43 3 mm Tyr 1 Cable gland M 16 x 1 5 including strain relief exchangeable max inner diameter 10 4 mm Mounting TW with strap for direct mounting on pipes or for direct mounting on flat surfaces e g walls ceilings TW external with detached sensor head cable length KL 1 5 m for moun...

Page 7: ...g 0 10V Potentiometer Swithpoint setting 75 100 r H Schematic diagram TW W Schematic diagram TW UW Schematic diagram TW U Connecting diagram TW U 1 2 3 GND UB supply voltage 24V AC DC Output bedewing 0 10V continuous 1 2 3 13 11 12 GND UB supply voltage 24V AC DC Normally open contact no dew Breaker dew changeover 24 V Output bedewing 0 10V continuous 1 2 3 13 11 12 free GND UB supply voltage 24V ...

Page 8: ...arranty or liability These devices must be installed by authorised specialists only The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are exclusively valid Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous improve ment of our products In ca...

Page 9: ...0 de billes de verre avec vis de fermeture rapide association fente fente en croix couleur blanc signalisation similaire à RAL 9016 Le couvercle est transparent Dimensions du boîtier 72 x 64 x 43 3 mm Tyr 1 Presse étoupe M 16 x 1 5 avec décharge de traction remplaçable diamètre intérieur max 10 4 mm Montage TW avec collier de serrage pour un montage direct sur tube ou pour un montage direct sur de...

Page 10: ...Schéma de raccordement TW W Schéma de raccordement TW UW Schéma de raccordement TW U Schéma de raccordement TW U 1 2 3 GND UB supply voltage 24V AC DC Output bedewing 0 10V continuous 1 2 3 13 11 12 GND UB supply voltage 24V AC DC Normally open contact no dew Breaker dew changeover 24 V Output bedewing 0 10V continuous 1 2 3 13 11 12 free GND UB supply voltage 24V AC DC Normally open contact no de...

Page 11: ...clinons toute responsabilité ou garantie au titre de tout dommage consécutif provoqué par des erreurs commises sur cet appareil L installation des appareils doit être effectuée uniquement par un spécialiste qualifié Seules les données techniques et les conditions de raccordement indiquées sur la notice d instruction accompagnant l appareil sont applicables des différences par rapport à la présenta...

Page 12: ...янными шариками с быстрозаворачиваемыми винтами комбинация шлиц крестовой шлиц цвет транспортный белый аналогичен RAL 9016 крышка прозрачная Размеры корпуса 72 x 64 x 43 3 мм Tyr 1 Присоединение кабеля M 16 x 1 5 с разгрузкой от натяжения сменное исполнение макс внутренний диаметр 10 4 мм Монтаж TW с хомутом для непосредственного монтажа на трубах или для непосредственного монтажа на прямых поверх...

Page 13: ...V Potentiometer Swithpoint setting 75 100 r H Схема подключения TW W Схема подключения TW UW Схема подключения TW U Схема соединения TW U 1 2 3 GND UB supply voltage 24V AC DC Output bedewing 0 10V continuous 1 2 3 13 11 12 GND UB supply voltage 24V AC DC Normally open contact no dew Breaker dew changeover 24 V Output bedewing 0 10V continuous 1 2 3 13 11 12 free GND UB supply voltage 24V AC DC No...

Page 14: ... устранению по гарантии Установка приборов должна осуществляться только квалифицированным персоналом Действительны исключительно технические данные и условия подключения приведенные в поставляемых с приборами руководствах по монтажу и эксплуатации Отклонения от представленных в каталоге характеристик дополнительно не указываются несмотря на их возможность в силу технического прогресса и постоянног...

Page 15: ...ensor on top outside Capteur en haut à l extérieur Датчик сверху снаружи Sensor außen seitlich Sensor outside at the side Capteur à l extérieur sur le côté Датчик снаружи сбоку Copyright by S S Regeltechnik GmbH Nachdruck auch auszugsweise nur mit Genehmigung von S S Regeltechnik GmbH gestattet Reprints in part or in total are only permitted with the approval of S S Regeltechnik GmbH La reproducti...

Page 16: ...esetzten Fühlerkopf zur Rohrmontage TW external with detached sensor head for mounting on pipes TW externe avec sonde déportée pour montage sur tube TW наружный с вынесенной чувствительной головкой монтаж на трубах 15 Sensor 107 72 KL 35 15 10 13 7 ø3 M12x1 5 64 14 8 43 3 M16x1 5 15 Sensor 107 72 KL 35 15 10 13 7 ø3 M12x1 5 64 14 8 43 3 M16x1 5 ...

Reviews: