61
Energy Smart |
SELECTION PROCEDURE
Example of model selection
Let’s suppose a designer is interested in a vertical ENY-SP unit to be installed in a newly built flat.
Let's suppose that the designer calculates the following data, with the resulting identification of the maximum flows:
Model ENY-SP-280
is selected as the most suitable unit.
Supply flow
Extraction flow
Q
SN
= 160 m
3
/h
Q
EN
= 140 m
3
/h
∆p
SN
= 90 Pa
∆p
EN
= 80 Pa
Q
SN_MAX
= 1.3 (160) ≈ 210 m
3
/h
Q
EN_MAX
= 1.3 (140) ≈ 180 m
3
/h
Quick selection flow rate Q
QS
= max (210; 180) =
210 m3/h
Air flow [m3/h]
Ex
ternal sta
tic pr
essur
e [P
a]
ENY-SP-180
ENY-SP-280
ENY-SP-370
ENY-SP-460
ENY-SP-600
Q
max
[m
3
/h]
180
280
370
460
600
Q
rif
[m3/h]
130
200
260
320
420