- do not lay the 12 volt power cables and communication cables near power devices,
lights, antennae, transformers or hot water or steam pipes;
- never position the communication cables in any conduits, pipes, junction boxes or
other containers together with the power cables or the lighting system cables;
- always ensure there is adequate separation between the communication cables and all
other electrical cables;
- keep the communication cables, and the units themselves, at least 2 metres away from
appliances with significant inductive loads (distribution panels, motors,generators forli
-
ghting systems).
When performing the serial connection between
the appliances, follow the connection symbols:
- clamp “
D-
” with clamp “
D-
”
- clamp “
D+
” with clamp “
D+
”
- clamp “
GND
”: connect the shield of the serial
cable.
N
ever
reverse
the
coNNectioNs
.
EARTHING THE NETWORK
SETTING DIP SWITCHES
Set
KD1 dip switches
as shown in the table
below
KD1
KD1
GND