The unit name plate is positioned on the frame and contains this information:
Refrigeration unit No.
Identification no. (serial no.)
Year
Year of manufacturing.
Type
Manufacturer's type designation.
Scope
For EC PED/EAC approval: ‘Unit & Piping’ means that the CE/EAC
mark applies to the complete unit including the piping system.
’Piping’ means that the CE/EAC mark applies to the piping system on-
ly, and it is the sole responsibility of the owner to ensure and declare
that the complete unit is in conformity with the provisions of all relevant
rules.
Design code
Design code used for the unit and piping system.
Approval no.
If the unit/manufacture has been approved by a 3rd party/notified
body.
Refrigerant - Fluid
Refrigerant of the unit.
Refrigerant designation according to ISO 817.
Refrigerant - Group
For EC PED approval:
Fluid group 1 or 2 according to the PED directive.
Supply voltage - Control
Supply voltage and frequency of the control system.
Refrigerant charge
Weight of the refrigerant charge on the unit.
This is only stated if the unit includes an evaporator and/or a
condenser.
Pressure system
The low-pressure side of the unit piping system is referred to as the LP
side.
The high-pressure side of the unit piping system is referred to as the
HP side.
Category
For EC PED approval:
The maximum category of the piping system (CAT 1, 2 or 3) or of the
assembly unit and piping (CAT 3 or 4).
Allowable pressure, max.
The max. pressure (pressure relative to atmospheric pressure) that
the unit/piping system has been designed for in terms of pressure
strength design.
The maximum practical operation pressure is lower than the maximum
allowable pressure depending on the operating conditions and safety
equipment settings.
Test pressure
The test pressure that the unit/piping system has been strength tested
with.
Allowable temperature, min./
max.
The minimum and maximum temperatures that the unit/piping system
has been designed for at the indicated maximum allowable pressures.
CE xxxx
The CE mark appears on the name plate for EC PED approval only.
The four digits make up the registration no. of the notified body/3rd
party in charge.
Ex
If the unit is designed in accordance with the EC ATEX directive, there
is an Ex mark on the name plate.
EAC
The EurAsian Conformity mark (EAC) indicates that the unit is in com-
pliance with all relevant technical regulations of the Eurasian Customs
Union.
Note: Main supply voltage