Operating manual - ChillPAC and LP ChillPAC Mk 3
60/68
010823 en 2021.06
Check the settings
You can check your settings
by pressing
twice.
Press to return to
default screen.
AKS 4100
COAX D22 280 mm
(0%) 4 mA
210 mm
(100%) 20 mA
060 mm
After running the quick set-up, go to the supervisor menu and change the following parameters:
•
2.3.2 Blocking distance
•
2.3.3 Time constant
•
2.5.3 Epsilon R gas constant (Er gas)
Change to the value indicated for the temperature of the media. If a media range is given,
choose the value of the lowest operating media temperature. See the List of Er gas constant in
Fig. 39.
•
2.5.7 Level threshold
•
4.1.1 Full area
•
4.1.2 Empty area.
The supervisor menu is protected by a passcode.
1.
Name the buttons on the AKS head 1-2-3-4 from left to right, see Fig. 29.
Fig. 29
Supervisor passcode = 1-2-3-4-1-2
2.
Press
Arrow right
(no. 1) once - the first digit 1 is marked, see Fig. 30.
Fig. 30
1 2 3 4