Operating manual - ChillPAC and LP ChillPAC Mk 3
010823 en 2021.06
11/68
2. Safety
2.1
Areas of application
2.1.1
Application
To prevent unintentional application which could injure personnel or damage equipment, the following
must be observed:
•
The unit must only be used as a liquid refrigeration unit intended for water or brine cooling.
•
The unit must not be installed in areas where the relative humidity (RH) may exceed 85% (95%
if the motor is made for 100% RH).
•
The primary side must only be charged with refrigerant R717.
•
Johnson Controls Denmark further accept no liability of any kind for damage to compressor unit
and plant parts caused by torsional oscillation or the like which is attributable to built-in VSD sol-
utions initiated by the customer after delivery.
•
The secondary side on the evaporator and condenser is only intended for water or brine as cool-
ing medium. The secondary medium is stated on the P&I diagram. Deviations are only permitted
with a written permission from Johnson Controls Denmark.
•
Installation of the chiller in potentially explosive atmospheres must only take place if the chiller is
fitted with approved explosion-proof equipment.
•
The compressor must only be used as a refrigeration compressor and within the operating limits
specified in the manual or in a written agreement with Johnson Controls Denmark.
•
The compressor must only be used with the number of revolutions per minute, as shown on the
compressor name plate.
The compressor must NOT be used:
•
To evacuate the refrigeration plant of air and moisture.
•
To put the refrigeration plant under air pressure in view of a pressure testing.
•
As an air compressor.