Operating manual - ChillPAC and LP ChillPAC Mk 3
12/68
010823 en 2021.06
2.1.2
Application of combustion engines
According to EN 378/ISO 5149, no other machinery should be installed in a refrigeration machine room.
Some refrigerant types may, to a certain extent, be absorbed by the fuel in a combustion engine, and
when the contaminated fuel reaches the fuel pumps, the refrigerant will “flash out” (separate) and react
on the increased temperature and pressure by creating acids, which will destroy the pumps. However,
check with the local authorities as exemptions to this rule may be granted.
Warning!
Johnson Controls Denmark is not liable for injuries to personnel or damage to equipment resulting from
using the equipment for other purposes than the ones stated above.
2.2
Identification
2.2.1
Identification of equipment
All equipment from Johnson Controls Denmark can be identified by one or several name plates posi-
tioned as illustrated in the following drawing:
Fig. 1: Identification of equipment
Pos. no.
Name plate for
1
Compressor
2
Evaporator/Cascade cooler
3
Condenser/Receiver
4
Float housing
5
Unit/pipe system
1
2
3
4
5