Operating manual - ChillPAC and LP ChillPAC Mk 3
52/68
010823 en 2021.06
6. Maintenance instructions
6.1
Maintenance of the chiller unit
Read chapter
carefully before performing any maintenance on the chiller unit.
To ensure that the chiller unit operates without problems throughout a long service life, the system of
maintenance presented in the following instructions must be followed.
Daily maintenance is normally performed by the operating personnel. Other maintenance and service
tasks, which require the refrigeration system to be opened, must be performed by competent personnel.
Maintenance can be divided into:
1.
Daily maintenance
(minimum twice a week)
Daily maintenance consists of visual inspections:
•
Inspect the chiller unit and check that both noise and vibrations are normal.
•
To observe trends, it is recommended to enter the observed operating data in an opera-
tions log, see
. Check that all operating values are within
the permissible ranges. Compare them with previous values to detect trends.
•
Check the oil level.
•
Check the refrigerant charge.
•
Observe for leaks of refrigerant (smell of ammonia), oil, glycol or water.
•
Check mechanical seal oil draining bottle.
•
Check the control system for alarms/shutdowns.
2.
Half-yearly/yearly/major maintenance
•
In general, only the compressor needs to be maintained. However, it is recommended
to check that the chiller is running properly; check for fouling of heat exchangers and dirt
in the filters, for instance.
Maintenance intervals are described in detail in the compressor manual.