Factory settings for alarm limits:
The following table indicates the alarm li-
mits which have been set by SABROE befo-
re the unit is delivered. (White fields).
Low alarm
Low
High
High alarm
Limit for
setting
Factory
setting
(Add to low
(Subtract from
high alarm)
Factory
setting
Limit
for setting
Bar
Bar
Bar
Bar
Bar
warning
warning
alarm)
Suction pressure
Discharge pressure
Diff. pressure
Superheat
Discharge temp.
Oil temperature
Brine temp.
-1
3,5
5
°
C
Sat
--
--
7
-1
0
0
-20
0
-45
-1
0
2
0
20
0
1 Bar
0,5 Bar
1
5
5
2
1
0,5
5
5
5
--
18
1,5
80
120
60
--
25
25
120
145
105
15
°
C
°
C
°
C
°
C
°
C
°
C
A table is provided at the end of this
manual, in the chapter entitled
Appendix
, so
that you can record the warning and alarm
limits you have set.
Note:
·
At the
low alarm limit
, the differential
pressure alarm will be delayed 45
seconds after start-up and during opera-
tion.
·
At the
low alarm limit
, the superheat
alarm is delayed 300 seconds after start-
up.
·
At the
high alarm limit
, the superheat
alarm is delayed 300 seconds after start-
up.
·
At the
high alarm limit
, the oil filter
differential pressure alarm is delayed 20
seconds.
·
At the low and high limits, the oil tem-
perature alarm is delayed 300 seconds
after start-up.
UNISAB S-Control has an alarm relay
which changes position when an alarm situ-
ation occurs in the compressor. This relay
can be used to provide a remote alarm
(flashing light or warning bell). Please refer
to the wiring diagram.
Reverting to factory settings for
alarm limits
If you have coded in new limits, it is pos-
sible to revert to the alarm limits originally
set by SABROE. This is done by using the
configuration function. Please refer to the
chapter
Configuration
.