Discharge gas temperature:
H
igh
al
ar
m
Oil cooler
HLI R717
HLI R22
BLI
SAB 110/
128/163
VMY Mk2/
2.5/3
100
°
C
110
°
C
65
°
C
65
°
C
CT + 45 K
CT + 45 K
65
°
C
65
°
C
High warning always 5 K
lower than high alarm.
Low warning always 5 K
higher than low alarm.
Oil cooler
HLI R717
HLI R22
BLI
25
°
C
CT + 5 K
CT + 15 K
30
°
C
25
°
C
CT + 5 K
CT + 15 K
30
°
C
Low
al
ar
m
Oil temperature:
Set high alarm acc. to table:
HLI R717
HLI R22
BLI
Oil cooler
60
°
C*
CT + 40 K
60
°
C
60
°
C
* If special oils are used, the max. temper-
ature is set acc. to the table
Selecting lubri-
cating oil
in the compressor instr.
10 K.
High warning always 5 K lower than high
alarm.
Set low alarm to stop the compressor at
20
°
C.
Low warning always 5 K higher than low
alarm.
Actual warning and alarm limits
If you have changed the warning and alarm
limits set by SABROE Refrigeration, use
the following table to record the new set-
tings. (White fields).
Low alarm
Low
High
High alarm
Limit for
setting
Actual
setting
(Add to low
(Subtract from
high alarm)
Actual
setting
Limit for
setting
Bar
Bar
Bar
Bar
Bar
warning
warning
alarm)
Suction pressure
Discharge press.
Diff. pressure
Superheat
Discharge temp.
Oil temp.
Brine temp.
°
C
°
C
°
C
°
C
°
C
°
C
-1
--
7
-1
0
0
-20
0
-45
1 Bar
0,5 Bar
1
5
5
2
1
0,5
5
5
5
--
25
25
120
145
105
15
5
°
C
Sat