Operating
Warning
The batteries are already charged when delivered, and are fitted with a protective cap on
each terminal. They should be unpacked with care.
Avoid short-circuiting terminals of opposite polarity, because these units are capable of
discharging at a very high current especially if the lid or the container is damaged.
Unpacking the battery
Each shipment is accompanied by a packing list
The packing list should be checked, and the Sales Department should be told immediately
of any missing items.
Setting up the battery racks
The structure should be assembled in accordance with instructions supplied with the
equipment.
Racks
Ensure that the stretchers and cross-members are correctly interlinked.
Take up any irregularity in floor surface using shims.
Ensure that all frame members are correctly interlinked.
Use the adjustable feet to take up irregularities in the floor surface.
Metal racks should always be connected to the building earth in accordance with current
regulations.
Mounting in a cabinet
Is sufficiently strong to cope with the weight of the battery.
Is covered with a layer of insulation.
Is naturally ventilated.
Connection of cells
All connections should be insulated
In series:
The number of cells in series will determine the total float of voltage:
U = V x N
U --- Total float voltage
V --- Float voltage for one cell
N --- Number of cells