background image

WFDN Vane-type Waterflow Detectors

INSTALLATION AND MAINTENANCE INSTRUCTIONS

IMPORTANT

Please Read Carefully And Save
This instruction manual contains important information about the installation and 

operation of waterflow detectors. Purchasers who install waterflow detectors for use 

by others must leave this manual or a copy of it with the user.
Read all instructions carefully before beginning. Follow only those instructions that 

apply to the model you are installing.

CAUTION

The model WFDN is a vane-type waterflow detector for use in wet-pipe fire sprinkler 

systems only. Vane-type waterflow detectors shall not be used as the sole initiating 

device in both deluge and preaction systems; waterflow detectors used in these types 

of systems may result in an unintended discharge caused by a surge, trapped air or a 

short retard time. 

WARNING

Installation must be performed by qualified personnel and in accordance with all na-

tional and local codes and ordinances.
Shock hazard: Disconnect power source before servicing. Serious injury or death 

could result.
Risk of explosion: Not for use in hazardous locations. Serious injury or death could 

result.

PRINCIPLES OF OPERATION

Vane-type waterflow detectors mount to water-filled pipes in fire sprinkler systems. 

Waterflow in the pipe deflects a vane, which produces a switched output, usually af-

ter a specified delay. All WFDNs have a pneumatically controlled mechanical delay 

mechanism. Delays do NOT accumulate; they reset if the flow of water stops or drops 

below minimum triggering flow rate before the entire delay has elapsed. 
All switches actuate when the waterflow rate is 10 gallons per minute or greater, but 

will not actuate if the flow rate is less than 4 gallons per minute. This Safe Signal 

installation manual covers the following waterflow detectors for fire sprinkler/fire 

alarm applications.

Model

Pipe Size

(inches)

Pipe

Schedule

Max. Pressure

Rating (psig)

WFD20N

2

7 thru 40

450

WFD25N

2.5

7 thru 40

450

WFD30N

3

7 thru 40

450

WFD40N

4

7 thru 40

450

WFD50N

5

10 thru 40

450

WFD60N

6

10 thru 40

450

WFD80N

8

10 thru 40

450

SPECIFICATIONS

Contact Ratings: 

10 A @ 125/250 VAC 

; 2.5 A @ 24 VDC 

Triggering Threshold Bandwidth (Flow Rate): 

4 to 10 gpm

Static Pressure Rating: 

See models listed below

Dimensions, Installed: 

2.6 in H x 3.5 in W x 6.7 in D

Operating Temperature Range: 

32°F to 150°F (0°C to 66°C)

Compatible Pipe: 

Steel water pipe, schedule 7 through 40 (See chart below)

Shipping Weight: 

3 to 6 lbs (according to size)

Enclosure Rating: 

NEMA Type 4, as tested by Underwriters Laboratories, Inc.

U. S. Patent Numbers:  

5,213,205

CAUTION

Do NOT use any of the WFDN models on copper pipe. The clamping forces of the 

mounting bolts may collapse the pipe sufficiently to prevent the detector from func-

tioning properly.

Do NOT install steel or iron pipe sections in copper piping for mounting a waterflow 

detector. Incompatibility between the dissimilar metals causes bimetallic corrosion.

INSTALLATION GUIDELINES

Before installing any waterflow alarm device, be thoroughly familiar with:
NFPA 72:   National Fire Alarm Code

NFPA 13:    Installation of Sprinkler Systems, Sect. 3.17

NFPA 25:    Inspection, Testing and Maintenance of Sprinkler Systems,   Sect. 5.3.3.2

Other applicable NFPA standards, local codes, and the requirements of the authority 

having jurisdiction
NOTE: Installation methods other than those listed in this installation manual may 

prevent the device from reporting the flow of water in the event the associated fire 

sprinkler system is activated by a fire. Safe Signal is not responsible for devices that 

have been improperly installed, tested, or maintained.
1.   Mount the detector where there is adequate clearance for installation and re-

moval and a clear view of it for inspections. See Figure 1 for mounting dimen-

sions.

2.   Locate the detector 6 to 7 feet above the floor to protect from accidental 

damage.

3.   On horizontal runs, position the detector on the top or side of the pipe. Do not 

mount it upside down because condensation may collect in the housing and 

impair the operation of the detector. For vertical flow applications, mount the 

detector on pipe through which water flows upward. Otherwise, the unit may 

not operate properly.

4.   Mount the detector at least 6 inches from a fitting that changes the direction of 

waterflow and no less than 24 inches from a valve or drain.

5.   Be sure the direction-of-flow arrows and directional cover match the direction 

of flow in the pipe. See Figure 6.

MOUNTING INSTRUCTIONS

1.  Drain the pipe.
2.   Cut a hole in the pipe at the desired location. Center the hole on the pipe, as 

shown in Figure 2, and be sure the hole is perpendicular to the center of the 

pipe. Before drilling, use a punch or scribe to mark the drill site to prevent the 

bit from slipping. If the hole is off center, the vane will bind against the inside 

wall of the pipe. Use a drill or hole saw to cut a hole of the proper diameter. See 

Table 1 for hole size.

CAUTION

When drilling the hole with a hole saw, make certain that the center of the cut does 

not remain in the pipe.

I56-4045-E

  

I56-4045-E 

 

 4/21

Summary of Contents for WFDN

Page 1: ...ow Shipping Weight 3 to 6 lbs according to size Enclosure Rating NEMA Type 4 as tested by Underwriters Laboratories Inc U S Patent Numbers 5 213 205 CAUTION Do NOT use any of the WFDN models on copper pipe The clamping forces of the mounting bolts may collapse the pipe sufficiently to prevent the detector from func tioning properly Do NOT install steel or iron pipe sections in copper piping for mo...

Page 2: ... drain the system and remove the detector refer to Maintenance Check for dirt or foreign objects under the gasket and make sure that the pipe surface is not dented Reinstall the detector and check again for leaks Do not proceed until all leaks have been stopped 2 Connect an ohmmeter or continuity tester across the COM and B NO switch terminals The ohmmeter should indicate an open circuit 3 Deflect...

Page 3: ...rational Testing to ensure proper operation Test more often if required by the authority having jurisdiction Under normal conditions Safe Signal waterflow detectors should provide years of trouble free service However if the delay mechanism becomes faulty a replacement kit is available To replace the delay mechanism request Part No FS RT Complete instructions are enclosed with replacement parts Th...

Page 4: ...ESTED EOL RESISTOR SSM24 X SSV120 X NOTE COMMON AND B NO CONNECTIONS WILL CLOSE WHEN VANE IS DEFECTED I E WHEN WATER IS FLOWING DUAL SWITCHES PERMIT APPLICATIONS TO BE COMBINED ON A SINGLE DETECTOR CONTACT RATINGS SCHEMATIC OF INDIVIDUAL SWITCH IN NO WATERFLOW CONDITION A NC COM B NO BREAK WIRE AS SHOWN FOR SUPERVISION OF CONNECTION DO NOT ALLOW STRIPPED WIRE LEADS TO EXTEND BEYOND SWITCH HOUSING ...

Reviews: