33
SL6+ v.3.30 EN
Operating
"DB Special"
relay function
A relay function combining 3 different relay
functions in one. When function is active it is
affected by 3 failures:
1. Battery failure
•
Deactivates in case of failed battery test
•
Resets by pressing the “Reset Button”
2. Automatic emergency button check fault
•
Relay activates once every day. If something is wrong with button,
an alarm is sent to the alarm receiver.
•
If DB collective fault is programmed on an output, this is
released.
•
Resets when emergency button input is changed.
3. Call retry failure
•
Deactivates if the unit after programmed number of tries fails
with alarm drop-off (if Fallback is activated both interfaces have
failed).
•
Resets in case of successful alarm delivery
•
Resets by pressing the “Reset Button”
Activate this relay function in
the SafeLine CONNECT app or
SafeLine Pro.