LED (H) Range
6
INTRODUCTION - Description and Characteristics
SURELINE
incorporates a highly advanced and innovatory technology for protection and metering, with built-in motor-drive in the module
itself and protected by user code.
An outstanding feature is the very high-speed cut-off (2ms typical in the H range); intelligent automatic reset (conditioned); automatic
sequential reset in the event of MCB and differential tripping.
SURELINE provides the user with a universal protection which monitors, evaluates, warns and makes automatic decisions. This small,
compact unit for 35mm DIN rail is supplied all ready to be installed in a standard enclosure and used in any installation or sector
whatsoever. These integrated protections are totally automatic and both these and other characteristics can be extended simply by
linking up to other SURELINE modules.
- Description
Presentation: standard (EN 50 022) enclosure for 35mm DIN rail. This is a compact unit monitored by a microcomputer. Highly stable
due to its built-in double process monitor (Watchdog). It withstands permanent and transient overvoltage and low voltage and is
capable of protecting multiple lines, both single and three-phase, of up to 63A.
The unit provides diverse protections :
Differential protection with very high-speed cut-off:
Protection against overvoltage by means of very high-speed cut-off
Protection against low voltage
Moreover, its constant supervision at the supply input permits its automatic, intelligent (conditioned)
reset, i.e. it resets solely when the
power supply returns to normal. Certain models/versions have input and output Remote Control.
Technical characteristics of reclosure module
(please, refer to synoptical tables for characteristics of models and versions)
Overvoltage protection V Peak
Rapid version: > 374 Vpk / Delay >800 microseconds (no suffix)
Medium version: > 374 Vpk / Delay >3 milliseconds (model + M suffix)
Slow version: > 374 Vpk / Delay >4,2 milliseconds (harsh conditions) (model + S suffix)
Overvoltage protection V Efficient
Rapid version: > 265 V / Delay >800 microseconds (no suffix)
Medium version: > 265 V / Delay >250 milliseconds (model +M suffix)
Slow version: > 265 V / Delay >500 milliseconds (harsh conditions) (model +S suffix)
Protection against low voltage
<180 V (Delay >500ms)
Tiempo desconexión gama H
2 to 3ms typical 2- pole (consult “Cut-off. Tripping times”)
Tiempo desconexión gama HL
5 to 6ms typical 2- pole (consult “Cut-off. Tripping times”)
Tiempo desconexión gama HLL
8 to 9ms typical 2- pole (consult “Cut-off. Tripping times”)
Tiempo desconexión gama OVD106
8 to 9ms typical 2- pole (consult “Cut-off. Tripping times”)
Delay REMOTE IN
3 ms
Mechanical endurance Safeline reclosure module
100.000 complete manoeuvres (ON/OFF)
Mechanical endurance Schupa MCB
20.000 complete manoeuvres (ON/OFF)
Mechanical endurance General Electric MCB 2-pole
20.000 complete manoeuvres (ON/OFF)
Mechanical endurance General Electric MCB 4-pole
15.000 complete manoeuvres (ON/OFF)
Typical precision specs. For module in overvoltage
1 year
(1,5 % + 0,5% of F.E.)
with 22
C
5
C, humidity 30 to 75% HR, 50Hz sinusoidal
Full scale (F.E.): Voltage L1, L2, L3: 500V
Working temperature 230V AC ± 20 %
0 a +40
o
C. Standard version
-10
o
a +50
o
C. Industrial version (I)
-15
o
a +70
o
C. Extended industrial version (E)
Dimensions: 2-pole
128mm (7 modules) height: 81mm 35mm DIN rail
Dimensions: 4-pole
163mm (9 modules) height: 81mm 35mm DIN rail
Weight : 2-pole
900 gr.
Weight : 4-pole
1.170 gr.
Weight of toroidal (TRDF18)
185 gr.
Weight of toroidal (TRDF26)
300 gr.
Guarantee
3 years
Design in accordance to norms
EN 60947-2 (annexe B), CEI 60947-2 (annexe B)
UNE 20-600-77 (CEI-278)
Differential protection type A
I
N
alternating 50 Hz senoidal
30 mA or 300 mA, rated tripping intensity (acc. version)
alternating 50 Hz senoidal rectified
1,41 x I
n, for pulsing senoidal currents (rectified alternating single wave)
preventive cut-off
In the event of power failure
protection I
N
Peak
(versión 30 mA dividir mA entre 10)
Rapid version: > 420 mApk / Delay >2 milliseconds (no suffix)
Medium version: > 420 mApk / Delay >5 milliseconds (model + M suffix)
Slow version: > 420 mApk / Delay >7,5 milliseconds (harsh conditions) (model + S suffix)
protection I
N
Efficient
(versión 30 mA dividir mA entre 10)
Rapid version: > 300 mA / Delay >2 milliseconds (no suffix)
Medium version: > 300 mA / Delay >60 milliseconds (model + M suffix)
Slow version : > 300 mA / Delay >100 milliseconds (harsh conditions) (model + S suffix)
Version: 230V AC 50Hz power supply
Consumption: POWER L1-N
1W at
230V AC RMS 50Hz alternating sinusoidal
Input voltage: POWER L1-N (normal conditions)
230V AC - 20 % + 30% RMS 50Hz alternating sinusoidal
Input voltage: POWER L1-N (abnormal conditions - maximum limit)
from 300V up to 450V AC RMS 50Hz alternating sinusoidal
Transient input voltage L-N (peak voltage)
1 KV max. (vp) / 300 ms
Input voltage: RMS phase neutral (INPUT 1 L1-N)
up to 450V RMS AC 50Hz
Input voltage: Pk phase neutral (INPUT 1 L1-N)
up to 635V Pk
Input voltage: RMS phase neutral (INPUT 2 L2-N)
up to 450V RMS AC 50Hz
Input voltage: Pk phase neutral (INPUT 2 L2-N)
up to 635V Pk
Input voltage: RMS phase neutral (INPUT 3 L3-N)
up to 450V RMS AC 50Hz
Input voltage: Pk phase neutral (INPUT 3 L3-N)
up to 635V Pk
Input voltage: RMS between phases L1 and L2, L1 and L3, L2 and L3
up to 500V RMS AC 50Hz
Input voltage: Pk between phases L1 and L2, L1 and L3, L2 and L3
up to 700V Pk