LED (H) Range

 

 
 

 

INTRODUCTION - Description and Characteristics

 

SURELINE 

incorporates a highly advanced and innovatory technology for protection and metering, with built-in motor-drive in the module 

itself and protected by user code. 

An  outstanding  feature  is  the  very  high-speed  cut-off  (2ms  typical  in  the  H  range);  intelligent  automatic  reset  (conditioned);  automatic 
sequential reset in the event of MCB and differential tripping.  

SURELINE provides the user with a universal protection which monitors, evaluates, warns and makes automatic decisions. This small, 
compact  unit  for  35mm  DIN  rail  is  supplied  all  ready  to  be  installed  in  a  standard  enclosure  and  used  in  any  installation  or  sector 
whatsoever.  These  integrated  protections  are  totally  automatic  and  both  these  and  other  characteristics  can  be  extended  simply  by 
linking up to other SURELINE modules. 

- Description

 

Presentation: standard  (EN 50 022) enclosure for  35mm DIN rail. This is a compact unit monitored by a microcomputer.  Highly stable 
due  to  its  built-in  double  process  monitor  (Watchdog).        It  withstands  permanent  and  transient  overvoltage  and  low  voltage  and  is 
capable of protecting multiple lines, both single and three-phase, of up to 63A.  

 The unit provides diverse protections :

 

  Differential protection with very high-speed cut-off: 

  Protection against  overvoltage  by means of very high-speed cut-off 

  Protection against low voltage 

Moreover, its constant supervision at the supply input permits its automatic, intelligent (conditioned)

 

reset, i.e. it resets solely when the 

power supply returns  to normal. Certain models/versions have input and output Remote Control. 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Technical characteristics of reclosure module                                         

(please, refer to synoptical tables for characteristics of models and versions)

 

Overvoltage protection V Peak

 

Rapid version: > 374 Vpk / Delay  >800 microseconds (no suffix) 
Medium version: > 374 Vpk / Delay  >3 milliseconds (model + M suffix) 
Slow version: > 374 Vpk / Delay  >4,2 milliseconds (harsh conditions) (model + S suffix)

 

Overvoltage protection V Efficient

 

Rapid version: > 265 V / Delay  >800 microseconds (no suffix) 
Medium version: > 265 V / Delay  >250 milliseconds (model +M suffix) 
Slow version: > 265 V / Delay  >500 milliseconds (harsh conditions) (model +S suffix) 

Protection against low voltage

 

<180 V (Delay >500ms)

 

Tiempo desconexión gama H

 

2 to 3ms  typical 2- pole (consult “Cut-off.   Tripping times”) 

Tiempo desconexión gama HL

 

5 to 6ms  typical 2- pole (consult “Cut-off.   Tripping times”) 

Tiempo desconexión gama HLL

 

8 to 9ms  typical 2- pole (consult “Cut-off.   Tripping times”)

 

Tiempo desconexión gama OVD106

 

8 to 9ms  typical 2- pole (consult “Cut-off.   Tripping times”)

 

Delay REMOTE IN

 

3 ms 

Mechanical endurance  Safeline reclosure module 

100.000 complete manoeuvres (ON/OFF)

 

Mechanical endurance   Schupa MCB

 

20.000 complete manoeuvres (ON/OFF) 

Mechanical endurance General Electric MCB 2-pole

 

20.000 complete manoeuvres (ON/OFF) 

Mechanical endurance General Electric MCB 4-pole

 

15.000 complete manoeuvres (ON/OFF) 

Typical precision specs. For module in overvoltage

 

1 year  

 (1,5 % + 0,5%  of F.E.)  

with 22

C  

 5 

C, humidity 30 to 75% HR, 50Hz sinusoidal  

Full scale (F.E.): Voltage L1, L2, L3: 500V

 

Working temperature 230V AC ± 20 %

 

0 a +40

o

 C. Standard version 

-10

o

 a +50

o

 C. Industrial version (I) 

-15

o

 a +70

o

 C. Extended industrial version (E) 

Dimensions: 2-pole

 

128mm (7 modules) height: 81mm 35mm DIN rail 

Dimensions: 4-pole

 

163mm (9 modules) height: 81mm 35mm DIN rail 

Weight : 2-pole

 

900 gr. 

Weight : 4-pole 

1.170 gr.

 

Weight of toroidal (TRDF18) 

185 gr. 

Weight of toroidal (TRDF26) 

300 gr. 

Guarantee

 

3 years

 

Design  in accordance to norms

 

EN 60947-2 (annexe B), CEI 60947-2 (annexe B) 

 

 

 

UNE 20-600-77  (CEI-278) 

Differential protection type A 

I

N

 alternating 50 Hz senoidal

 

30 mA or 300 mA, rated tripping intensity (acc. version) 

alternating 50 Hz senoidal rectified

 

1,41 x I

n, for pulsing senoidal currents (rectified alternating single wave)

 

preventive cut-off

 

In the event of power failure

 

protection  I

N

 

 

Peak   

(versión 30 mA dividir mA entre 10)

 

Rapid version: > 420 mApk / Delay  >2 milliseconds (no suffix) 
Medium version: > 420 mApk / Delay  >5 milliseconds (model + M suffix) 
Slow version: > 420 mApk / Delay  >7,5 milliseconds (harsh conditions) (model + S suffix) 

protection  I

N

  Efficient  

(versión 30 mA dividir mA entre 10)

 

Rapid version: > 300 mA / Delay  >2 milliseconds (no suffix) 
Medium version: > 300 mA / Delay  >60 milliseconds (model + M suffix) 
Slow version : > 300 mA / Delay  >100  milliseconds (harsh conditions) (model + S suffix) 

Version: 230V AC 50Hz  power supply 

Consumption: POWER L1-N

 

1W at

 230V AC RMS 50Hz alternating sinusoidal

 

Input voltage:  POWER L1-N (normal conditions)

 

230V AC - 20 % + 30% RMS 50Hz alternating sinusoidal

 

Input voltage:  POWER L1-N (abnormal conditions - maximum limit)

 

from 300V up to 450V AC RMS 50Hz alternating sinusoidal

 

Transient input voltage L-N (peak voltage) 

1 KV max. (vp) / 300 ms 

Input voltage:  RMS phase neutral (INPUT 1 L1-N)

 

up to 450V RMS AC 50Hz

 

Input voltage:  Pk phase neutral (INPUT 1 L1-N)

 

up to 635V Pk

 

Input voltage:  RMS phase neutral (INPUT 2 L2-N)

 

up to 450V RMS AC 50Hz

 

Input voltage:  Pk phase neutral (INPUT 2 L2-N)

 

up to 635V Pk

 

Input voltage:  RMS phase neutral (INPUT 3 L3-N)

 

up to 450V RMS AC 50Hz

 

Input voltage:  Pk phase neutral (INPUT 3 L3-N)

 

up to 635V Pk

 

Input voltage:  RMS between phases L1 and L2, L1 and L3, L2 and L3

 

up to 500V RMS AC 50Hz

 

Input voltage:  Pk between phases L1 and L2, L1 and L3, L2 and L3

 

up to 700V Pk

 

Summary of Contents for Sureline DOV707H

Page 1: ...LED H Range 1 ...

Page 2: ...LED H Range 2 ...

Page 3: ...rising from the incorrect use of this information Safeline S L as also its affiliates is not liable to the purchaser or to third parties for damages costs etc in which the purchaser or third party may incur as a result of any accident or incorrect use of this product nor as a result of any unauthorised modification alteration or repair to same nor due to non observance of the operation and mainten...

Page 4: ...ls relay OUT and remote IN 6 Version number of sequential reclosures of differential and MCB AIT EAI VOD ERT ETE RET TEL 7 Protection delay No suffix rapid version standard M medium version S slow version 8 Sensitivity differential intensity 30mA I n 30mA 300mA I n 300mA standard Sin sufijo in models without differential intensity OVD706H 9 Power supply Line Neutral No suffix Not designed to allow...

Page 5: ...nd transient overvoltage 13 Protection against permanent and transient low voltage 14 Protection against tripping of MCB 14 Protection against untimely tripping of the differential 14 CHAPTER 4 Cut off Tripping times Total cut off time of the MCB 14 CHAPTER 5 Mode of Use Remote Control 14 CHAPTER 6 Description of basic components Toroidal differential intensity transformer TRDF18 15 Toroidal diffe...

Page 6: ...o 9ms typical 2 pole consult Cut off Tripping times Delay REMOTE IN 3 ms Mechanical endurance Safeline reclosure module 100 000 complete manoeuvres ON OFF Mechanical endurance Schupa MCB 20 000 complete manoeuvres ON OFF Mechanical endurance General Electric MCB 2 pole 20 000 complete manoeuvres ON OFF Mechanical endurance General Electric MCB 4 pole 15 000 complete manoeuvres ON OFF Typical preci...

Page 7: ...nt reclosure Static Green LED WORKING and Red LED s LOW VOLT I n OVERVOLT in periodic 3 second sequence autotest 3 Static Red LED s anomaly Static Red LED I N 300 mA or 30 mA acc version anomaly in the differential Due to error in the toroidal core wiring or differential circuit Static Red LED LOW VOLT anomaly in the input mains voltage Due to abnormally low voltage inferior to 150 V AC approx Oth...

Page 8: ...1 N POWER 230V SUPPLY NEUTRAL INPUT METERING SENSOR INPUT N L2 INPUT 2 INPUT METERING SENSOR L2 LINE 2 230V N INPUT 2 INPUT METERING SENSOR N NEUTRAL L3 INPUT 3 INPUT METERING SENSOR L3 LINE 3 230V N INPUT 3 INPUT METERING SENSOR N NEUTRAL Description of module s front connection terminals R type terminals I SENSOR 1 INPUT 1 DIFFERENTIAL INTENSITY SENSOR G SENSOR 1 COMMON 1 SENSOR AND TEST T SENSO...

Page 9: ... terminals U type terminals Automatic Sequential Resets RCD and MCB Nbr of automatic sequential reclosures differential I n Ten 3 3 3 3 3 3 3 3 3 and 3 mins Model suffix ETE RET TEL Nbr of automatic sequential reclosures MCB Two 3 and 3 mins Model suffix ETE RET TEL Reset to zero reclosure counter 30 mins Model suffix ETE RET TEL Nbr of automatic sequential reclosures differential I n Six 3 6 12 3...

Page 10: ...closure due to overvoltage Low voltage protection Line1 Line2 Line3 Line1 Line1 Automatic intelligent reclosure due to low voltage Line1 Line1 Protection differential intensity I n 30 mA or 300 mA acc version Automatic sequential reclosure differential protection I n MCB protection 10kA 15kA acc version EN 60947 2 Automatic sequential reclosure MCB protection Overvoltage test Low voltage test Rate...

Page 11: ...nical service must be contacted immediately in order for the unit to be examined The unit must be completely disconnected from the mains before cleaning This is to be effected with a soft dry brush and if need be with a slightly damp cloth The unit must not be reconnected to the mains until having ascertained that it is completely dry WARNING This unit must be installed in a standard enclosure the...

Page 12: ...t up Start up Connect all up stream conductors by means of switches sectionalisers or others The reinitiation sequence will automatically be carried out The ancillary MCB will then reset and the unit will be operative Carry out all the protection tests In order to carry out the protection test correctly the unit must be in the permanent ON position before pressing the test button To this end check...

Page 13: ...no difference in intensity between phase and neutral In this case the differential protections do not act but then neither would any receiver being supplied from phase to neutral The functioning of the protection devices against defect currents which derive or leak to earth differentials is based on the measurement of the difference in intensity between the live conductors phase and neutral Once t...

Page 14: ...aving read and fully understood the present manual and having started up the unit the user may then proceed to connect up the elements of consumption to the protected line and the unit will operate as described in CHAPTERS 2 and 3 Before using the unit the complete Protection Test must be carried out If the unit is to be put to permanent use testing must be done as a matter of routine Once the tes...

Page 15: ...ype EP 100 Breaking capacity 15KA IEC 60947 2 ó 10KA IEC 60898 Curve C standard D B K Intensities 6 10 16 25 32 40 50 63 A Mechanical endurance MCB 2P and 4P 20 000 Complete manoeuvres ON OFF For further information please consult the manufacturer Very high speed disconnector tripping coil Manufacturer General Electric Type TELE L 1 CA 24 60V For further information please consult the manufacturer...

Page 16: ...xternal MCB and accessories CHAPTER 9 Additional options The new range of protection metering and registering share the SURELINE philosophy and are extraordinarily versatile So much so that they permit multiple configurations thanks to their modular expansion architecture not only with present and future SURELINE elements but also with others available on the market Thus they complement and are co...

Page 17: ...t for its repair or servicing Cost of all components replacements and labour on original components The guarantee does NOT cover Transport Breakdown caused by non original components or devices Defects caused by incorrect installation Damage caused by incorrect usage or errors arising from repairs and internal manipulation by unauthorised persons Consumables fuses thermal fuses varistors and labou...

Page 18: ...inst any defect of manufacture or original components as determined by our Technical Service Any repair or substitution does not extend the guarantee period The guarantee covers Reception of the unit for its repair or servicing Cost of all components replacements and labour on original components The guarantee does NOT cover Transport Breakdown caused by non original components or devices Defects ...

Page 19: ...ORNAS TIPO U A B N L1 CONTROL OUT INPUT 1 POWER 230V SENSOR 1 I G T 1 2 3 4 AUXILIARY IN OUT CONSULT MANUAL 5 6 7 8 COM L1 L2 9 M Self Reclosing DOV 707H Consult Manual Protection Unit 300 mA O VERVO LT TEST LOW VOLT LO W VO LT I N I 300 m A N Reclosure WORKING TIM ER ON OFF TEST I N BLOCK RESET TEST OVER VOLT BORNA BORNAS NO CONECTAR VERSION BORNAS TIPO U BORNA BORNAS AUXILIARY IN OUT CONTACTO N ...

Page 20: ...X I G T 1 2 SENSO R 1 M Self Reclosing DOV 707H Consult Manual Protection Unit 300 mA O VERVO LT TEST LOW VOLT LO W VO LT I N I 300 m A N Reclosure WORKING TIM ER ON OFF TEST I N BLOCK RESET TEST OVER VOLT T G I CAUTION POSITION TRDF18 CONSULT MANUAL CONFIGURACION MONOFASICA 2 POLOS 6 10 16 20 25 32 40 50 Y 63A UNIDAD DE PROTECCION AUTORREARMABLE CON MOTOR REARMADOR INTEGRADO MODELOS DOV707H Y DOV...

Page 21: ...ARMADOR INTEGRADO MODELOS DOV707HT Y DOV107HT VERSION BORNAS TIPO U BORNA BORNAS NO CONECTAR VERSION BORNAS TIPO U BORNA BORNAS AUXILIARY IN OUT CONTACTO N O RELE CONTACTO N C RELE Nº RELE DE SALIDA 5A MAX AC1 4 2 3 RELE DE SALIDA CONMUTADO LIBRE DE POTECIAL CON FUNCION DE DESCONEXION DESBLOQUEO BORNA BORNAS AUXILIARY IN OUT ENTRADA REMOTE IN ENTRADA REMOTE IN Nº ENTRADAS REMOTE IN 8 9 ENTRADAS PA...

Page 22: ...N SENTIDO FLECHA TRDF18 ó TRDF26 PASAR LOS CONDUCTORES L1 L2 L3 Y NEUTRO T G I CAUTION POSITION TRDF18 CONSULT MANUAL UNIDAD DE PROTECCION AUTORREARMABLE CON MOTOR REARMADOR INTEGRADO MODELOS DOV707HT Y DOV107HT VERSION BORNAS TIPO R BORNA AUX CONTACTO N C RELE CONTACTO COMUN RELE Nº RELE DE SALIDA 1A MAX AC1 2 1 RELE DE SALIDA LIBRE DE POTECIAL CON FUNCION DE ACTIVACION POR BLOQUEO 1 2 RELE BORNA...

Page 23: ...R 1 I G T 1 2 3 4 AUXILIARY IN OUT CON SULT MANUAL 5 6 7 8 COM L1 L2 9 M Self Reclosing OVD 706H Consult Manual Protection Unit O VERVO LT TEST LOW VOLT LO W VO LT BLO CK Reclosure WORKING TIM ER RESET TEST OVER VOLT 1 2 3 ON OFF BORNA BORNAS AUXILIARY IN OUT CONTACTO N O RELE CONTACTO N C RELE Nº RELE DE SALIDA 5A MAX AC1 4 2 3 RELE DE SALIDA CONMUTADO LIBRE DE POTECIAL CON FUNCION DE DESCONEXION...

Page 24: ...BORNA AUX CONTACTO N C RELE CONTACTO COMUN RELE Nº RELE DE SALIDA 1A MAX AC1 2 1 RELE DE SALIDA LIBRE DE POTECIAL CON FUNCION DE ACTIVACION POR ALARMA Y BLOQUEO BORNA BORNA NO CONECTAR BORNA NO CONECTAR BORNA NO CONECTAR BORNAS NO CONECTAR I 1 2 RELE T G A B N L1 CONTROL OUT INPUT 1 POWER 230V AUX I G T 1 2 SENSOR 1 M Self Reclosing OVD 706H Consult Manual Protection Unit O VERVO LT TEST LOW VOLT ...

Page 25: ... BORNA BORNAS AUXILIARY IN OUT ENTRADA REMOTE IN ENTRADA REMOTE IN Nº ENTRADAS REMOTE IN 8 9 ENTRADAS PARA CONTACTO EXTERNO LIBRE DE POTENCIAL RELE 3 4 2 CON FUNCION DE ACTIVACION POR ALARMA Y BLOQUEO CONTACTO COMUN RELE Y PUESTA A CERO DE LA CUENTA DE DISPAROS 6 1 5 7 BORNA NO CONECTAR BORNA NO CONECTAR BORNA NO CONECTAR BORNA NO CONECTAR SENSOR 1 I G T 1 2 3 4 AUXILIARY IN OUT CONSULT MANUAL 5 6...

Page 26: ...tection Unit O VERVO LT TEST VOLT OVER LO W VO LT BLO CK Reclosure ON OFF RESET TIM ER L3 L2 TEST VOLT LOW L1 WORKING 1 2 3 BORNA AUX CONTACTO N C RELE CONTACTO COMUN RELE Nº RELE DE SALIDA 1A MAX AC1 2 1 RELE DE SALIDA LIBRE DE POTECIAL CON FUNCION DE ACTIVACION POR ALARMA Y BLOQUEO BORNA BORNA NO CONECTAR BORNA NO CONECTAR BORNA NO CONECTAR BORNAS NO CONECTAR I 1 2 RELE T G BORNA Nº 2 Y 3 CONTAC...

Page 27: ...BORNAS TIPO U BORNA BORNAS AUXILIARY IN OUT CONTACTO N O RELE CONTACTO N C RELE Nº RELE DE SALIDA 5A MAX AC1 4 2 3 RELE DE SALIDA CONMUTADO LIBRE DE POTECIAL CON FUNCION DE DESCONEXION DESBLOQUEO BORNA BORNAS AUXILIARY IN OUT ENTRADA REMOTE IN ENTRADA REMOTE IN Nº ENTRADAS REMOTE IN 8 9 ENTRADAS PARA CONTACTO EXTERNO LIBRE DE POTENCIAL RELE 3 4 2 CON FUNCION DE ACTIVACION POR ALARMA Y BLOQUEO CONT...

Page 28: ...LT MANUAL CONFIGURACION MONOFASICA 2 POLOS 6 10 16 20 25 32 40 50 Y 63A UNIDAD DE PROTECCION AUTORREARMABLE CON MOTOR REARMADOR INTEGRADO MODELOS RDI705H Y RDI105H VERSION BORNAS TIPO R BORNA AUX CONTACTO N C RELE CONTACTO COMUN RELE Nº RELE DE SALIDA 1A MAX AC1 2 1 RELE DE SALIDA LIBRE DE POTECIAL CON FUNCION DE ACTIVACION POR BLOQUEO 1 2 RELE BORNA Nº 2 Y 3 CONTACTO AUX ILIAR NORMALMENTE CERRADO...

Page 29: ...RMABLE CON MOTOR REARMADOR INTEGRADO BORNA BORNAS NO CONECTAR VERSION BORNAS TIPO U BORNA BORNAS AUXILIARY IN OUT CONTACTO N O RELE CONTACTO N C RELE Nº RELE DE SALIDA 5A MAX AC1 4 2 3 RELE DE SALIDA CONMUTADO LIBRE DE POTECIAL CON FUNCION DE DESCONEXION DESBLOQUEO BORNA BORNAS AUXILIARY IN OUT ENTRADA REMOTE IN ENTRADA REMOTE IN Nº ENTRADAS REMOTE IN 8 9 ENTRADAS PARA CONTACTO EXTERNO LIBRE DE PO...

Page 30: ... Y POSICIONARLO SEGUN SENTIDO FLECHA TRDF18 ó TRDF26 PASAR LOS CONDUCTORES L1 L2 L3 Y NEUTRO T G I CAUTION POSITION TRDF18 CONSULT MANUAL UNIDAD DE PROTECCION AUTORREARMABLE CON MOTOR REARMADOR INTEGRADO MODELOS RDI705HT Y RDI105HT VERSION BORNAS TIPO R BORNA AUX CONTACTO N C RELE CONTACTO COMUN RELE Nº RELE DE SALIDA 1A MAX AC1 2 1 RELE DE SALIDA LIBRE DE POTECIAL CON FUNCION DE ACTIVACION POR BL...

Page 31: ...H Range 31 DIMENSIONES TRANSFORMADORES TOROIDALES TRDF18 TRIT18 70 80 Ø 18 10 50 14 50 50 52 60 30 70 DIMENSIONES TRANSFORMADORES TOROIDALES TRDF26 TRIT26 Ø 26 10 50 14 70 76 30 30 90 40 76 Ø 4 20 30 10 80 ...

Page 32: ...302 MATARO Barcelona SPAIN www safeline es safeline safeline es R D Commercial Factory Administration T 34 93 8841820 T 34 93 7630801 T 34 93 7630671 T 34 93 8841821 F 34 93 7630090 F 34 93 7630090 comercial safeline es inves safeline es admin safeline es Made in EU ...