Powered by Safety
®
39
Installation
01.4IB.77020
b. Racking the Circuit Breaker into the
Circuit Breaker Compartment
The described racking procedures
apply only for the PowlVac-NDA
™
Series 4 circuit breakers. For all other
constructions, refer to the appropriate
instructions or instruction bulletin(s) for
the applicable racking procedures.
The PowlVac-NDA circuit breaker is
designed to be electrically racked into
the circuit breaker compartment from a
remote location with the compartment
door closed. The PowlVac-NDA circuit
breaker may also be manually racked
using the emergency override option
with the compartment door open.
Note:
The described racking procedures
are for racking the circuit breaker
into the lower circuit breaker
compartment only. To rack the circuit
breaker into an upper circuit breaker
compartment, refer to the metal-clad
switchgear instruction bulletin for
detailed information.
Before inserting any circuit breaker into a
compartment, the user must verify that the
circuit breaker rating meets or exceeds the
metal-clad switchgear rating.
CAUTION
Before inserting a circuit breaker into the
circuit breaker compartment, be sure that
the indicator flag on the front cover
of the circuit breaker displays “TEST”.
CAUTION
Before attempting to rack a circuit breaker
in or out of a circuit breaker compartment
equipped with a key interlock, make sure
that the interlock is unlocked and in the open
position.
CAUTION
The illustrations shown for all racking
procedures are provided to show device
locations and are intended only as a guideline.
These illustrations may not be representative
of site specific safety practices for performing
the procedure. Before attempting any racking
procedure, review
.
NOTICE
2) Inserting the Circuit Breaker to the
Test/Disconnected Position
To insert the circuit breaker into the upper
compartment a lifting device must be used.
Refer to the Lifting Device instruction bulletin
for details on how to insert a circuit breaker
into the upper compartment.
NOTICE
Prior to inserting the circuit breaker into the
circuit breaker compartment, make sure that
the control circuits are deenergized.
!
CAUTION