Installation
01.4IB.77020
PowlVac-ND
®
and PowlVac-NDA
™
Series 4
Vacuum Circuit Breakers
5) Removing the Circuit Breaker from the
Test/Disconnected Position out of the Circuit
Breaker Compartment
Prior to removing the circuit breaker from the
circuit breaker compartment, make sure that
the control circuits are deenergized.
!
CAUTION
Prior to removing the circuit breaker from the
circuit breaker compartment, make sure the
circuit breaker is in the open position and all
springs are discharged.
!
CAUTION
a. Open the circuit breaker compartment
door.
b. Push the secondary disconnect latch
to the left. This will
unlock the secondary disconnect plug,
allowing it to be removed. Remove the
secondary disconnect plug.
Removal of the secondary disconnect plug will
trip a closed breaker and discharge the main
closing spring.
!
CAUTION
c. Press the anti-rollout latch
to release the circuit breaker and pull
the circuit breaker out of the circuit
breaker compartment.
6) Emergency Racking Out Procedure
In the event of an emergency, such as loss
of control power, the NDA circuit breaker
is equipped with an emergency racking
mechanism which enables racking the circuit
breaker into or out of the connected position.
NOTICE
Prior to removing the circuit breaker from the
circuit breaker compartment, make sure that
the control circuits are deenergized.
!
CAUTION
a. To remove the circuit breaker from
the Connected position to the
Test/Disconnect position perform
the following:
1. Verify that the circuit breaker
open/closed indicator displays
“
BREAKER OPEN
”. If “
CLOSED
”,
operate the circuit breaker control
switch to open the circuit breaker.
2. Open the compartment door. If
the padlock seal is present, remove
the seal
. Open the
emergency racking drive shaft
shutter
and place the
racking handle socket onto the
emergency racking drive shaft. The
racking handle socket may be used
to push down the shutter to gain
access to the racking drive shaft.