Internal Relay Wiring (Normally open)
Inductive load management requires a parallel diode for a better contact lifetime.
Warning
The internal relay is limited to a maximum current of 2A @ 30V. If the deadbolt / door strike draws
more than 2A, damage to the device may occur. If the deadbolt / door strike load exceeds 2A, an
external relay must be used.
The internal relay is designed for 100.000 cycles. If more cycles are needed, an external relay
driven by GPO must be used.
Power supply
VCC < 30V
Imax < 2A
Deadbolt / Door strike
Push Button
on other side
of the door
Snubber Diode
1
D
2
Relay_NO
Relay_Com
A B C
(Sample)
Warning
This applies only for small
or stand-alone applications
where access control
panels are not available.
In this mode it is strongly
recommended to monitor
the Tamper Detection of
the device
St
ep
four:
AC
P
or
SD
AC
Relay mode can be
changed to “normally
close” instead of
“normally closed” (default)