A410 [Preset Freq 0]
(1)
Related Parameter(s):
P108, P109, P110, t201, t202, A401, A402
A411 [Preset Freq 1]
A412 [Preset Freq 2]
A413 [Preset Freq 3]
Values
A410 Default
A411 Default
A412 Default
A413 Default
0.0 Hz
5.0 Hz
10.0 Hz
20.0 Hz
Min/Max:
0.0/400.0 Hz
Display:
0.1 Hz
Provides a fixed frequency command value when
t201 - t202
[Digital Inx Sel] is set to 4
“Preset Frequencies”.
An active preset input will override speed command as shown in the flowchart on
page 1-20
.
(1)
To activate
A410
[Preset Freq 0] set
P108
[Speed Reference] to option 4
“Preset Freq 0-3”
Input State of Digital In 1(I/O
Terminal 05)
Input State of Digital In 2(I/O
Terminal 06)
Frequency Source
Accel / Decel Parameter Used
(2)
0
0
A410 [Preset Freq 0]
[Accel Time 1] / [Decel Time 1]
1
0
A411 [Preset Freq 1]
[Accel Time 1] / [Decel Time 1]
0
1
A412 [Preset Freq 2]
[Accel Time 2] / [Decel Time 2]
1
1
A413 [Preset Freq 3]
[Accel Time 2] / [Decel Time 2]
(2)
When a Digital Input is set to
“Accel 2 & Decel 2”, and the input is active, that input overrides the settings in this table.
A418 [Skip Frequency]
Related Parameter(s
): A419
Sets the frequency at which the drive will not operate.
A setting of 0 disables this parameter.
Values
Default
0Hz
Min/Max:
0/400 Hz
Display:
1