Page 6 of 9 

Installing and Configuring MA-SIGMA Readers 

 

Wiring the MA SIGMA Reader at Galaxy Controllers 

 

The SIGMA reader supports the reader wiring and is compatible with the 600/635 DRM Board. The Sagem 

install guide recommends 20-24AWG, non-stranded wiring. Galaxy recommends 22 AWG shielded cable.  

 

1.

 

Turn the reader to the back side where you can see the connectors. Rotate the reader upside-down so that the 

wiring pin-out stickers

 are upright/readable.  

2.

 

Locate the first two connectors (from the left) that are used for 

power input

 and 

data wiring

.  

3.

 

On the second connector, insert the Data-0 (D0out) into pin-3, &  Data-1 (D1out) into pin-4 .  

4.

 

On the first connector, insert the Data-GND Wire (DGND) into pin-6. 

5.

 

Land Data 0, Data 1, and Data GND at the correct terminals of the 600 DPI/DRM Board Ground the drain-wire of 

the reader cable shielding to ground at the Galaxy DRM reader terminal.  

6.

 

Insert 

+12V power input wire

 into 

pin-1

 of the first connector 

7.

 

insert the 

ground wire

 into 

pin-2

 of the first connector. 

8.

 

Install (insert) the 3v battery into the battery slot. 

9.

 

Connect Ethernet cable to RJ45 jack. 

WARNING:  Before applying power to the reader, be sure to reference the PIN-OUT STICKER on the 

back of reader to match the wiring according to the reader markings. 

10.

 

Once you test the reader for correct card/biometric recognition, you can permanently mount the reader to the 

wall using the Sagem mounting instructions that came with the reader packaging. 

Diagram of MA SIGMA Reader with back open 

 
 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 1 

 6 

 +12v 

 GND 

 DGND 

 Ethernet 

Connector 

Battery Inserts 

      Here 

Back of reader enclosure 

Housing 

Openings 

 

 D0 OUT 

 D1 OUT 

Reader PIN-OUT sticker  

Summary of Contents for Morpho SIGMA

Page 1: ...Page 1 of 9 Galaxy Configuration Guide for Morpho SIGMA Readers Compatible with Galaxy Hardware JAN 2019 SG 11 1 0 2 Galaxy supports Legacy Mode in SG 10 3 1 or higher...

Page 2: ...ss of this document Copyright 2014 Galaxy Control Systems All rights reserved No part of this document may be reproduced copied adapted or transmitted in any form or by any means electronic or mechani...

Page 3: ...MA SIGMA Reader front rear with back open 5 Installing and Configuring MA SIGMA Readers 6 Wiring the MA SIGMA Reader at Galaxy Controllers 6 Diagram of MA SIGMA Reader with back open 6 About Sagem s I...

Page 4: ...mode for new and existing installations of System Galaxy 10 3 1 or higher NOTE MA SIGMA is compatible with preexisting installations of Sagem Morpho readers by using the Legacy Morpho mode PRESENTING...

Page 5: ...ufacturer s documentation NOTICE the wiring stickers are affixed upside down thus you should turn the reader upside down to read the pin out correctly BE AWARE it is perfectly possible to insert wirin...

Page 6: ...0 Data 1 and Data GND at the correct terminals of the 600 DPI DRM Board Ground the drain wire of the reader cable shielding to ground at the Galaxy DRM reader terminal 6 Insert 12V power input wire in...

Page 7: ...each step depicted in diagrams with no words On the front page top right corner is the pin out diagram of the Sigma reader as viewed from the back with the reader turned upside down Bottom of reader f...

Page 8: ...rnet and IPv4 Static Mode Enter IP Subnet and Gateway addresses recommended DNS OFF disabled Protocol Config choose Legacy Morpho Create a new password recommended First Boot Config Storage recommende...

Page 9: ...entered into the appropriate field in the General tab 6 Setting the Reader recognition mode Use GCS MA Loader Utility program from the System Galaxy communication server to quickly set the reader rec...

Reviews: