Installing and Configuring MA-SIGMA Readers
Wiring the MA SIGMA Reader at Galaxy Controllers
The SIGMA reader supports the reader wiring and is compatible with the 600/635 DRM Board. The Sagem
install guide recommends 20-24AWG, non-stranded wiring. Galaxy recommends 22 AWG shielded cable.
1.
Turn the reader to the back side where you can see the connectors. Rotate the reader upside-down so that the
wiring pin-out stickers
are upright/readable.
2.
Locate the first two connectors (from the left) that are used for
power input
and
data wiring
.
3.
On the second connector, insert the Data-0 (D0out) into pin-3, & Data-1 (D1out) into pin-4 .
4.
On the first connector, insert the Data-GND Wire (DGND) into pin-6.
5.
Land Data 0, Data 1, and Data GND at the correct terminals of the 600 DPI/DRM Board Ground the drain-wire of
the reader cable shielding to ground at the Galaxy DRM reader terminal.
6.
Insert
+12V power input wire
into
pin-1
of the first connector
7.
insert the
ground wire
into
pin-2
of the first connector.
8.
Install (insert) the 3v battery into the battery slot.
9.
Connect Ethernet cable to RJ45 jack.
WARNING: Before applying power to the reader, be sure to reference the PIN-OUT STICKER on the
back of reader to match the wiring according to the reader markings.
10.
Once you test the reader for correct card/biometric recognition, you can permanently mount the reader to the
wall using the Sagem mounting instructions that came with the reader packaging.
Diagram of MA SIGMA Reader with back open
1
6
+12v
GND
DGND
Ethernet
Connector
Battery Inserts
Here
Back of reader enclosure
Housing
Openings
D0 OUT
D1 OUT
Reader PIN-OUT sticker