HT400 Rectangular fi re damper - UNI EN 1366-2 Certifi ed - UNI EN 13501-3 Classifi ed
CONFIGURATION
• E1 - Magnet 230V normally de-energized
1 Micro FR530 connected to the reset lever
1 Micro FR5A1 connected to fuse link
• E3 - Magnet 24V normally de-energized
1 Micro FR530 connected to the reset lever
1 Micro FR5A1 connected to fuse link
• E5 - Magnet 230V normally de-energized
1 Micro FR5A1 connected to fuse link
• E7 - Magnete 24V normally de-energized
1 Micro FR5A1 connected to fuse link
DIMENSIONS OF RELEASE SYSTEMS WITH MAGNETS
H [mm]
150
200
250
300
350
400
≥ 450
50
125
100
75
50
25
0
0
Ysup [mm]
Yinf [mm]
1.4
HTE 400 + MAGNET - Confi guration E1 / E3 / E5 / E7
(confi guration shown in the drawing E1 / E3)
MS
= Minimum space for servicing servo motor/mechanism 200 mm
BO
= Blade overhang
FAIL-CLOSE LOGIC
- Working conditions /
torsion spring loaded / lever in horizontal position / magnet powered
Î
DAMPER OPEN
- Normal conditions or failure /
torsion spring unloaded / lever in vertical position / magnet not powered
Î
DAMPER CLOSED
Y
sup.
Y
inf.
H + 68
400 [± 5 ext.]
165
125
Wall limit
165
70
W [± 2 int.]
36
36
80
MS
H [± 2 int.]
36
36
BO
BO
The dimensions shown on all diagrams are expressed in [mm]
For dampers with height > 400 mm blade overhang is:
H - 400 mm
2