Installation
15
Fig.2-7Installing UPS
2.3 Connect Input/Output Power
1.Notes for installation
(1) The UPS must be installed in a location with good ventilation, far away from water,
inflammable gas and corrosive agents.
(2)Ensure the air vents on the front and rear of the UPS are not blocked. Allow at least 0.5m of
space on each side.
(3) Condensation to water drops may occur if the UPS is unpacked in a very low temperature
environment. In this case it is necessary to wait until the UPS is fully dried inside out before
proceeding installation and use. Otherwise there are hazards of electric shock.
(4)The circuit breaker (CB) with residual current device (RCD) should not be used in the input
of UPS.
2. Installation
Installation and wiring must be performed in accordance with the local electric code and the
following instructions by professional personnel.
For safety, please cut off the mains power switch before installation. Open the battery breaker
for long backup time model (“H” model).
(1)Open the terminal block cover located on the rear panel of the UPS, please refer to the
appearance diagram.
(2)For 6kVA) UPS, it is recommended to select the UL1015 10 AWG(6 mm
2
) wire or other
insulated wire which complies with AWG Standard for the UPS input and output wirings.
(3) For10kVA UPS, it is recommended to select the UL1015 8 AWG(10 mm
2
) wire or other
insulated wire which complies with AWG Standard for the UPS input and output wirings.
NOTICE
:
Do not use the wall receptacle as the input power source for the UPS, as its rated