Hardware Manual for the PCD3 Series│Document 26/789; Version E 5│31.01.2005
Saia-Burgess
Controls Ltd.
RIOs
Configuration
6-21
6
Command buttons
Loads the current configuration of the PCD3.T76x
Loads the configuration displayed into the device-specific
web pages for the PCD3.T76x
Saves the current configuration of the PCD3.T76x to the
PCD3.T76x EEPROM
Clears the PCD3.T76x EEPROM
Clears all “locks” configured in the PCD3.T76x
Starts or stops Monitoring mode
Upload function
This function loads the PCD3.T76x configuration and displays it in the configuration
list within the device-specific web pages for the PCD3.T76x. This function is not
available in Monitoring mode.
Download function
This function loads the configuration from the configuration list into the PCD3.T76x.
This function is not available in Monitoring mode.
Where a DP-Master is connected to the PCD3.T76x, the DP-Master configuration has
priority. This applies when downloading or attempting to load a configuration into the
PCD3.T76x. In this case, it is impossible to download without losing the connection
to the Master. If the PCD3.T76x is disconnected from the network, the download can
continue.
When attempting to download a configuration while still connected to the Master, the
system displays a warning message offering the option either to disconnect from the
Master and continue with the download, or to cancel the download.
Saving to EEPROM
This function is not available in Monitoring mode. The two configurations, in the
PCD3.T76x itself and in the device-specific web pages for the PCD3.T76x, must be
identical. This function saves the configuration from the PCD3.T76x to its EEPROM.