Saia-Burgess
Controls Ltd.
Manual PCD7.D23x│Document 26/795; Edition E7│15.04.2005
Use of the PCD7.D23x terminals for the whole PCD range
Quickstart
1-10
1
B - with one RS 485 port
Up to 31 PCD7.D230 or D231 or D232 terminals can be connected to one RS 485
port.
PCD7.D23x setup (recommended):
(see also chapter 3)
Baudrate:
9600 bps
Serial mode:
RS 485 FTP
Addresses:
same number of different addresses
as number of terminals: from 01 to 31
Use of HMI-Editor V 1.3 (recommended):
Select the terminal:
D230 with 8 x 20 (or D231 or D232)
Terminal topology:
bus
Terminal number:
xx terminals
Terminal list:
number 1, 2, 3…31 corresponding to the identification
number (address) of each terminal.
Serial line:
1
Type of serial line:
RS 485
Baudrate:
9600 bps
Handshake:
None
Connection diagram:
see chapter 2.4
For further detail see the manual “HMI-Editor” 26/768.
i