Saia-Burgess
Controls Ltd.
Manual PCD7.D23x│Document 26/795; Edition E7│15.04.2005
Hardware-System Overview
2
2-8
User created interface connection cables
2.4.3 Connection in RS 422 Multi Drop (example with PCD7.F110 module)
PCD7.D23x
PCD7.D23x
PCD1/2, PCS1
Address 01
Address 01
Display Control
Full Control
2.4.4 Connection in RS 232 ( with Handshake RTS/CTS) for an autonomous
version without 24 VDC power supply
Connection between terminal PCD7.D23x and PGU socket
PCD7.D23x
PGU: PCD1, PCD2,
PCD3 or PCD4
●
+ 5 V of the PGU is mapped on Pin 6 (/RX) of the D-sub 9 of the terminal
●
Power consumption (5V / max 500mA)
●
Cable maximum one meter length is recommended
●
No external supply 24 VDC (in parallel) must be present
●
Increase the contrast of the graphics-display in the setup menu of the terminal
●
EMV test is not yet released
TXD 2
RXD 3
SGND 5
CTS 7
RTS 8
2 RXD
3 TXD
5 SGND
7 RTS
8 CTS
9-pole
D-type connector
(male)
9-pole
D-type connector
(male)
Shield housing
Shield housing
Cable RS 232
/Rx 6
9 +5V
11 TX
12 /TX
13 RX
14 /RX
10 GND
Module
PCD7.F110
TX 4
/RX 6
/TX 9
GND 5
9-pole
D-type connector
RX 1
TX 4
/RX 6
/TX 9
GND 5
9-pole
D-type connector
RX 1