5.1
故障报警及对策
Failure alarm and policies
86
故障名称
Failure
name
故障 代码
Failure code
故障原因排查
Failure reason one by one check
故障处理对策
Failure treatment policies
掉载故障
Loss load
failure
Err30
1
、变频器运行电流小于
P9-64 Frequency
converter running current lower than P9-64
1
、确认负载是否脱离或
P9-
64
、
P9-65
参数设置是否符合 实际运行
工况
Confirm whether load separated or
whether P9-64, P9-65 parameter setting
accordance with actual running working
condition
运行时
PID
反馈丢失
故障
PID feedback
loss failure during
running
Err31
h PID
反馈小于
PA-26
设定值
PID feedback less
than PA-26 setting value
1
、检查
PID
反馈信号或设置
PA-26
为一个合适值
Check PID feedback
signal or set PA-26 as one suitable value
逐波限流 故障
Wave
tracing and limit
current failure
Err40
1
、 负载是否过大或发生电机堵转
Whether too
big load or happen motor blocked
2
、 变频器选型偏小
Smaller frequency
converter device model select
1
、 减小负载并检査电机及机械 情况
Reduce load and check the motor and
mechanical situation
2
、 选用功率等级更大的变频器
Select
more bigger power grade frequency
converter
运行时切换 电机故
障
Shift motor failure
during running
Err41
1
、在变频器运行过程中通过端子更 改当前电
机选择
Modify current motor select through
terminal during frequency converter running
1
、变频器停机后再进行电机切 换操作
Process motor shift operation after
frequency converter stop machine
电机过温 故障
Motor
over temperature
failure
Err45
1
、 温度传感器接线松动
Temperature sensor
wiring loosen
2
、 电机温度过高
Too high temperature motor
1
、 检测温度传感器接线并排除 故障
Test temperature sensor wiring and solve
the failure
2
、 降低载频或釆取其它散热措 施对电
机进行散热处理
Reduce carriage
frequency or adopt other heat radiation
actions to process heat radiation of motor
初始位置 错误
Initial
position error
Err51
1
、电机参数与实际偏差太大
Too big motor
parameter and actual tolerance
1
、重新确认电机参数是否正确, 重点
关注额定电流是否设定偏小
Confirm
again whether motor parameter correct,
pay attention at focus on whether lower
rated current setting