SAL National Pty Ltd. 40 Biloela Street Villawood NSW 2163 ABN 21 633 189 474
Copyright SAL V16 JUL 2021 |
www.sal.net.au
| Page 2 of 3
12. Specific installation procedures (if any) - this device must be installed by a licensed electrician:
Specifications
Parameter setting
TIME
: S3,S4,S5
SENS
: S1,S2
LUX: S6
S1
S2 S3 S4
S5
S6
Switch to the ON position as "1",
Switch to the OFF position as "0”
TIME
:
S3
,
S4
,
S5
S3
S4
S5
S3
S4
1
1
1
1
0
1
0
1
1
0
S5
TIME
1
30min
20min
3min
5min
0
0
1
0
10min
0
0
10s
0
0
0
1min
1
1
0
15min
1
Troubleshooting
360
Detection angle
2
.
5
-
3
.
5m
Height of installation 2.5~3.5M
Min
:
1m Min
:
1m
Max: 6m
Max: 6m
Height of installation 2.5m
detection range
Detection range setting (sensitivity)
Detection range is the term used to describe the less circular detection zone
produced on the ground the sensor light at a height of 2.5m, switch location
and detection range of the corresponding table is as follows:
SENS
:S1,S2
S1
S2
S1
S2
detection range
0
0
25%
0
1
50%
1
0
75%
100%
1
1
NOTE:
the above detection range is gained if the detected person is between
1.6m~1.7m tall and moves at a speed of 1.0~1.5m/sec. if a person’s stature,
figure or moving speed changes, the detection distance will also change.
Switch to the ON position as "1",
Switch to the OFF position as "0”,
Time setting
The light can be set to stay ON for any period of time between approx.10sec
and a maximum of 30min. Any movement detected before this time elapse
will re-start the timer.
It is recommended to select the shortest time for adjusting the detection zone
and for performing the walk test. Switch location and detection range of the
corresponding table is as follows:
•
Transmission power: <0.2mW
•
Rated load:
1000W/5A, Max, incandescent lamp (cosφ=1)
300W/2.5A, Max, fluorescent lamp and LED lamp (cosφ=0.5)
•
HF system: 5.8GHz CW electric wave, ISM band
•
Detection angle: 360°
•
Detection range: 25%/50%/75%/100% (radii).(adjustable)
•
Time setting: 10sec/1min/3min/5min/10min/15min/20min/30min(adjustable)
•
L
ight-control: 24H/10
-80lux range
•
Power consumption: approx 0.5W
•
The advantage of this product is stable performance at working
temperatures: 0°C~+40°C, SMS830 adopts a microwave sensor
(highfrequency output<0.2mW), so that it is safe to use.
Shown in chart below
:
By setting the S1, S2 to set the detection RANGE
of products, by setting S3,S4,S5 to set the DELAY time of products, by
setting the S6 to set the LIGHT-control of products.
NOTE: The product will not function correctly where the sensor is
located behind metallic structures or enclosed in a ceiling cavity.
Malfunction
Cause
Adjust setting
Load faulty
Change load
Mains switch OFF
Switch ON
check zone setting
the sensor location is incorrect
securely mount the enclosure location
Check zone setting
Check zone setting
Incorrect light-control setting selected
Remedy
Movement occurred, but was not identified by the sensor
(movement behind wall, movement of a small object in
immediate lamp vicinity etc. )
Rapid movements are being suppressed to minimize
malfunctioning or the detection zone you have set is too small
The sensor/light will not operate
despite movement
The sensor/light operates without
any identifiable movement
The sensor/light is ON all of the time
The sensor/light will not work
Continuous movement in the detection zone
NOTE: after the light switches OFF, it takes approx. 4sec before it is able to
start detecting movement again. The light will only switch on in response
to movement once this period has elapsed.
Light-control setting
LUX
:
S6
S6
S6
LUX
0
24H
1
10-80 LUX
The chosen light response threshold can be infinitely from a
pprox. 10
-80
lux/24H, s
witch to the ON position as "1" , switch to the OFF position as "0”,
switch location and light-control of the corresponding table is as follows:
Wiring diagram