Installation

Reception of goods

Each  device  is  thoroughly  checked  before  transportation.  While  receiving  goods  it  is  recommended  to  check  whether  devices  were  not  damaged
during  transportation.  If  a  damage  to  the  device  is  noticed,  immediately  address  the  representatives  of  a  transport  company.  Please  inform  a
representative  of  the  manufacturer,  if  any  deviation  from  the  order  is  noticed.

Transportation and storage

The  package  is  only  for  protection  purpose!
While  unloading  and  storing  the  units,  use  suitable  lifting  equipment  to  avoid  damages  and  injuries.  Do  not  lift  units  by  holding  on  power
supply  cables,  connection  boxes,  air  extract  or  exhaust  flanges.  Avoid  hits  and  shock  overloads.  Before  installation  units  must  be  stored  in  a
dry  room  with  the  relative  air  humidity  not  exceeding  70%  (at  +20  °C)  and  with  the  average  ambient  temperature  ranging  between  +5  °C
and  +30  °C.  The  place  of  storage  must  be  protected  against  dirt  and  water.
The  units  must  be  transported  to  the  storage  or  installation  site  using  forklifts.
The  storage  is  not  recommended  for  a  period  longer  than  one  year.  In  case  of  storage  longer  than  one  year,  before  the  installation  it  is
necessary  to  verify  whether  the  bearings  of  fans  and  motor  rotate  easily  (turn  the  impeller  by  hand)  and  if  the  electric  circuit  insulation  is
not  damaged  or  the  moisture  is  accumulated.
AmberAir  Compact  CX  P  are  lifted  from  the  pallet  with  a  forklift  or  slings.

When lifting with a forklift, protect the condensate
drainage pipes. The product is heavy. Exercise
caution when transporting and installing. Follow
safety requirements established in your country.

Unit

Dimensions, [mm]

H

W

L

Comapct 1 CX V

1750

1000

1945

Comapct 2 CX V

2095

1200

2190

Comapct 3 CX V

2400

1200

2165

Comapct 4 CX V

2580

1200

2465

Summary of Contents for AmberAir Compact 4 CX P

Page 1: ...AIR HANDLING UNIT WITH HEAT RECOVERY SYSTEM Mounting and installation instructions Subject to technical modifcation AmberAir Compact 4 CX P...

Page 2: ...f accessories 28 Arrangement of controller connections in MCB 28 Arrangement of controller connections in EX1 31 Arrangement of controller connections in EX2 33 Abbreviation in electrical circuit diag...

Page 3: ...le protective clothes should be worn Beware of sharp angles while performing installation and maintenance tasks Do not touch heating elements until they haven t cooled down Some devices are heavy thus...

Page 4: ...f the Eurovent association Europe s Industry Association for Indoor Climate HVAC Process Cooling and Food Cold Chain Technologies AmberAir Compact SD50 units designed of the VDI 6022 Part 1 guideline...

Page 5: ...pass damper 100 Integrated heater Water Control type Comfort MCB Filter type Panel Outdoor installation version Indoor Selected parameters Parameter Unit of measurement Value Winter Summer Air ow supp...

Page 6: ...e class F7 Thermal transmittance class T3 Thermal bridging factor class TB4 Thickness of double skin panel 50 mm Insulation material Mineral wadding Insulation material density 40 kg m3 Insulation mat...

Page 7: ...AmberAir Compact 4 CX P www salda lt 7 Dimensions and weight ODA outdoor air SUP supply air EHA extract air ETA exhaust air Weight without package and accessories kg 442...

Page 8: ...wer current kW A 0 90592 3 5 Speed min 1 2642 Control input VDC 0 10 Protection class IP54 Exhaust air fan Phase voltage frequency f VAC Hz 3 400 50 Power current kW A 0 90592 3 5 Speed min 1 2627 Con...

Page 9: ...1113x379x46 M5 Pressure losses Assembly Unit of measurement Supply air Exaust air Heat exchanger Pa 93 120 Heater Pa 17 Filter Pa 162 85 Dampers Pa 19 Total Pa 291 205 Total system pressure Pa 250 250...

Page 10: ...AmberAir Compact 4 CX P 10 www salda lt Air ow diagram operational limits power consumption Supply air Exhaust air...

Page 11: ...e site before installation shall be sealed using additional means in order to prevent the accumulation of moisture inside the unit If the unit is installed and is not started for continuous operation...

Page 12: ...r Compact 4 CX P 12 www salda lt Components Heat exchanger 1 Supply air ter 2 Exhaust air ter 3 Exhaust air fan 4 Supply air fan 5 By pass 6 Water heater 7 Control board 8 Supply air ter 9 Exhaust air...

Page 13: ...AmberAir Compact 4 CX P www salda lt 13 Accessories...

Page 14: ...0x350 F2 GNGPR168_1071_0 Filter boxes FDS 75 35 M5 GFZFDS050 Filter boxes FDS 75 35 F7 GFZFDS055 Filter boxes FDS 75 35 G4 GFZFDS056 Rails for cover Compact CXP Rails 4CXP GNGPR168_1036_0 Base frame f...

Page 15: ...lative air humidity not exceeding 70 at 20 C and with the average ambient temperature ranging between 5 C and 30 C The place of storage must be protected against dirt and water The units must be trans...

Page 16: ...ifting with a forklift the length of the fork must be greater than the length or width of the product depending on the product version AmberAir Compact CX P lifting with a forklift AmberAir Compact CX...

Page 17: ...e with wood screws After unpacking the unit examine it to make sure that it has not been damaged during transportation The installation of damaged units is prohibited AmberAir Compact CX P are very he...

Page 18: ...AmberAir Compact 4 CX P 18 www salda lt After unpacking AmberAir Compact 4 CX P open the side covers and unscrew the supporting legs which are used for transportation from the fans...

Page 19: ...AmberAir Compact 4 CX P www salda lt 19 Mounting diagram Electrical version Water version...

Page 20: ...on pump A1 Fire alarm damper actuator I A2 Fire alarm damper actuator II TJ Supply air temperature sensor TL Outdoor air temperature sensor TE Exhaust air temperature sensor DTJ Extract air temperatur...

Page 21: ...e 1xD in air exhaust duct 3xD where D is diameter of the air duct It is recommended to use the accessories holders This will reduce vibration transmitted by the unit to the air duct system and environ...

Page 22: ...tion Transportation and Storage AmberAir Compact 1 CX P is installed straight using a level AmberAir Compact 2 4 CX P should be turned by 0 5 1 Installation on the oor When installing on the oor the s...

Page 23: ...llet is withdrawn Rails are o ered as an accessory to be screwed up to the suspended product after installing the cover holders to the appropriate position If the thickness of the cover is 30 mm inser...

Page 24: ...shown in the section Unpacking After screwing up 4 lifting brackets to the product fasten the lifting slings to the brackets use washers and screws for screwing up Using a crane lift the product by n...

Page 25: ...Put lifting belts on bracket how in the picture below Lift the unit with crane not more then 50 cm Unite legs are di erent It s depend on unit doors thickness 30 mm or 50 mm Unpacked unit is unstable...

Page 26: ...the pipe should descent by 55 mm Prior to starting the recovery unit the system should be led with 0 5 litre or more water the siphon 4 should always be led up and make sure that water goes to the se...

Page 27: ...the air supply system install silencers see chapter on their installation In order to reduce air loss in the system the air ducts and pro e parts should be of class C and higher Their catalog can be...

Page 28: ...AmberAir Compact 4 CX P 28 www salda lt Connection of accessories Arrangement of controller connections in MCB...

Page 29: ...r fan failure NC 6 12VDC X4 1 MCB DI4 Fire protection input NC 2 12VDC 3 MCB DI5 By pass closed NC 4 12VDC 5 MCB DI6 Rotor alarm NC Heat exchanger pressure relay NC 6 12VDC 7 MCB DI7 Extract air fan f...

Page 30: ...3P 2 MCB GND 3 MCB BYPASS_ 24VDC_OPEN 4 MCB BYPASS_ 24VDC_CLOSE X12 1 PE 24VDC Power supply for water heater actuator 2 GND 3 24VDC X13 1 24VDC By pass step motor control 2 STEP_B 3 STEP_B 4 STEP_A 5...

Page 31: ...AmberAir Compact 4 CX P www salda lt 31 Arrangement of controller connections in EX1...

Page 32: ...re place protection NC 6 12VDC X23 1 DI9 Fire damper opened NC 2 12VDC 3 DI10 Fire damper closed NC 4 12VDC 5 DI11 Recirculation damper closed NC 6 12VDC X24 1 GND Electric Water preheater control 0 1...

Page 33: ...ND Reserved input 0 10VDC 6 AI3 0 10V X29 1 GND Water cooler temperature sensor 2 AI4 NTC 3 GND Hydraulic preheater water temperature 4 AI5 NTC X30 1 24VDC 24VDC Power supply for Air quality transmitt...

Page 34: ...uator 1 max 100 mA 2 N L1 3 PE 4 DO2 Power supply for Fire damper actuator 2 max 100 mA 5 N L1 6 PE X33 1 DO3 Water cooler circulation pump 2 N L1 3 PE X34 1 DO4 Control box heater control or Control...

Page 35: ...Dunctional block name EX2 X40 1 DO9 NO DX cooler reverse NO cooling NC heating 2 DO9 NO X41 1 DO10 NO DX cooler power line 2 DO10 NO X42 1 DO11 Preheater power line circulation pump 2 N L1 3 PE X43 1...

Page 36: ...FA Fire alarm FPP Fireplace protection START Operation indicator START Warning indicator System mode switch System mode switch START STOP Fan speed switch Fan speed switch BOOST M4 Water heater circu...

Page 37: ...AmberAir Compact 4 CX P www salda lt 37 Electrical external pre heater...

Page 38: ...AmberAir Compact 4 CX P 38 www salda lt External water pre heater...

Page 39: ...AmberAir Compact 4 CX P www salda lt 39 External water cooler...

Page 40: ...AmberAir Compact 4 CX P 40 www salda lt External DX cooler...

Page 41: ...AmberAir Compact 4 CX P www salda lt 41 Fire protection connection...

Page 42: ...AmberAir Compact 4 CX P 42 www salda lt Motorised air dampers...

Page 43: ...AmberAir Compact 4 CX P www salda lt 43 CO2 arba RH sensors...

Page 44: ...n input The jumpers are installed by the manufacturer see on the automatics switchboard All the external electrical connections must be made in accordance with e ective legal acts and safety requireme...

Page 45: ...efore it is connected to the power network The power cable can be replaced only by a quali ed specialist upon the evaluation of the rated power and current The manufacturer does not assume any liabili...

Page 46: ...s activated Possible heater or unit failure MUST address the servicing sta for failure detection and its elimination Too low air ow at rated fan speed Clogged supply and or extract air ter s Filter re...

Page 47: ...nd similar electrical appliances Safety Part 1 General requirements LST EN 60529 1999 Degrees of protection provided by enclosures IP code LST EN 61000 6 2 2005 Electromagnetic compatibility EMC Part...

Page 48: ...AmberAir Compact 4 CX P 48 www salda lt Notes...