EN |
53
AMBERAIR COMPACT S-CX v2023.3
List of integrated components
Availability List of optional accessories
Availability
SAF
Air fan supply
+
CW2
Heating/cooling coil combined
Two for single
Air Handling
unit (depends
on version)
EAF
Air fan exhaust
+
HW2
Heater water
OF
Air filter outdoor
+
DX2
Cooler DX
EF
Air filter extract
+
PE3
Preheater electrical
One for single
Air Handling
unit
PS1
Differential pressure switch for OF
+
HW3
Preheater water
PS2
Differential pressure switch for EF
+
P1
Pump CW1 water circulation
Only with CW1
PS3
Differential pressure switch for C
+
M1
Actuator CW1 water valve
HE1
Heater electrical
One for
single Air
Handling unit
(depends on
version)
T2
Thermostat CW1 reverse
CW1
Heating/cooling coil combined
P2
Pump HW1 water circulation
Only with HW1
HW1
Heater water
M2
Actuator HW1 water valve
Without Coil1
no heater or cooler (empty)
T3
Thermostat CW2/HW2 protection
Only with CW2
(when HE1/
HW2 is not
used) or HW2
WTO1
Temperature sensor CW1 return water
Only with
CW1
WTO4
Temperature sensor CW2 return water
Only with CW2
WTO2
Temperature sensor HW1 return water
Only with
HW1
P4
Pump CW2 water circulation
T1
Thermostat CW1/HW1 protection
Only with
CW1 (when
HW2 is not
used) or
HW1
M4
Actuator CW2 water valve
C
Heat exchanger plate
+
T4
Thermostat CW2 reverse
M3
Actuator heat exchanger bypass air damper
+
WTO5
Temperature sensor HW2 return water
Only with HW2
SUP
Air temperature sensor supply
+
P5
Pump HW2 water circulation
ODA
Air temperature sensor outdoor
+
M5
Actuator HW2 water valve
EHA
Air temperature sensor exhaust
+
WTO6
Temperature sensor HW3 return water
Only with HW3
ETA
Air temperature sensor extract
+
P6
Pump HW3 water circulation
U3(f)
Pressure sensor for constant SUP flow control
+
M6
Actuator HW3 water valve
U4(f)
Pressure sensor for constant EHA flow control
+
ST1
Air damper outdoor
+
ST2
Air damper exhaust
+
A1
Fire dampers supply air
+
A2
Fire dampers extract air
+
AQS
Sensor air quality 0-10V duct/room
2
Remote control panel
1
MB-Gateway interfaces
+
U3(p)*
Pressure sensor for constant SUP
pressure control
Converts from
U3(f),U4(f)
U4(p)*
Pressure sensor for constant ETA
pressure control
* U3(p) and U4(p) are converted from U3(f) and U4(f) to control fan speed by constant air pressure