EKS (NI, NIS, NV, NV PH, NV PTC/PS)

www.salda.lt

EKS     NV     40    x    20   /   21   PTC  /  PS

Heater with installed pressure sensor

PTC/PS type can be marked also as NV PH if temperature setpoint of the heater  -20°C to -5°C

Heater with installed air flow sensor

Power of heater kW
Heaters width
Heater height cm
Heater type.

 

Type 

NV

 - you can set temperature of heater with potentiometer installed on heaters casing. 

Type 

NI 

- you can set temperature from distance with wired remote potentiometer 

TR5K

Type 

NIS

 – heater control from distance with 0 – 10 V signal.

Circular duct heater

Heater can be installed in any position (see picture below) except electrical connection box downward. If heater is installed in such way that can be 

accidental contact with heating elements, protective grill must be installed. Air flow through heater must be not less 1,5 m/s. Heaters can not be in-

stalled in explosive and aggressive substances atmosphere. Heaters can be used only for clean air heating. Heaters intended for inside installation.

Heaters installation position:

EKS NV PTC/PS, EKS NV PH installation

Casing and air duct before heater should be insulated with rock wool 10 cm (R~2,4m²K/W). It is recommended to install air filter before the 

heater.

*AHU 

– air handling unit with heat recovery. 

F

 – filter for supply air.

Depending on the installation location of the heater in the duct relative to the engine (before or behind the engine), the pressure hose therefore has to 

be attached to a “+” or the “-” tube. If heater is installed behind engine “-” tube inside, “+” tube before the engine.

3xH

 – we recommend install duct temperature sensor in minimum distance multiplied by the heater’s height. For example: heater EKS 

height 200mm, sensor’s installation length will be: 200x3=600 mm.

INDICATION of LED lamps on EKS NV PTC/PS, EKS NV PH casing

1. 

LED1

 Flashing 1 time per 3 seconds – EKR KN warming up (~30 s)

Flashing 1 time within second – EKR KN ready, Lights up – fault of duct temperature sensor T J-K10K, or air flow sensor PTC fault.

2. 

LED2

 Lights up – load is on (heating).

1. Electrical connection can be made only by qualified electrician according legal international and national electrical installation standards.

2. Power supply source must conform with data on heater label.

3. Power supply cable must be selected corresponding to heater electrical data.

4. Automatic circuit breaker with at least 3 mm contact gap must be installed. Automatic circuit breaker must and relay be selected corresponding to 

technical data table.

5. Heater must be grounded.

6. For heaters install duct temperature sensor and connect as in wiring diagram.

Summary of Contents for EKS

Page 1: ...Subject to technical modification EKS_P0082_AZ_0002 ELECTRIC DUCT HEATERS EKS EKS NI EKS NIS EKS NV EKS NV PH EKS NV PTC PS USER MANUAL...

Page 2: ...NSTALATION 4 Electrical connection 4 WIRING DIAGRAMS 5 HEATERS DESCRIPTION STRUCTURE 6 Double overheat protection 6 Duct connection 6 CONTROL 7 External control of three phase heaters 7 External contr...

Page 3: ...dry place with humidity not more 70 20 C average ambient temperature must be 5 40 C Storing place must be covered from water and dirt Avoid long term storing It is not recommended to store products m...

Page 4: ...air filter before the heater AHU air handling unit with heat recovery F filter for supply air Depending on the installation location of the heater in the duct relative to the engine before or behind...

Page 5: ...Control board TR 5 external potentiom eter TJK10K Temperature sensor X3 X26 the control board contacts see on PCB EKS NV EKS NI EKS NIS 3x400V I V heater steps B protection from overheat ing 50 C auto...

Page 6: ...r a minimum period of 15 years To ensure security in case of fire in all electric air heaters are installed 2 heat protection thermostats First overheat protection automatically activates if temperatu...

Page 7: ...u can set temperature from distance with wired remote potentiometer TR5K Type NIS heater control from distance with 0 10V signal Type PTC heater with installed air flow sensor Type PS heater with inst...

Page 8: ...NI NIS NV NV PTC PS NV PH 800x500 WxH Length L mm 370 420 440 500 Power kW 9 12 15 18 21 24 27 30 33 36 39 42 45 51 54 60 66 EKS NI NIS NV NV PTC PS NV PH 1000x500 WxH Length L mm 370 420 440 500 Powe...

Page 9: ...3 x 400 3 x 230 Power kW 18 0 9 9 30 0 15 15 54 0 15 9 12 18 18 0 9 9 30 0 9 9 12 54 0 9 12 15 18 EKS NIS 1200x550 WxH Length L mm 370 440 370 440 Voltage V 50Hz 3 x 400 3 x 230 Power kW 21 0 12 9 36...