background image

7

EKS (NI, NIS, NV, NV PH, NV PTC/PS)

www.salda.lt

Standard circular duct heaters type EKS has no internal controller, in this case can be used external heating controllers EKR 15.1, EKR 15.1P, EKR 

30, EKR 30P and temperature sensor TJK 10 K. Controllers and sensor are not included in the package of product.

Model

Controlled load [kW] Extra load control*

Full load

Relay output

Voltage output

EKR15.1

15

Up to 12 kW

27 kW

1x5A/230V

3x230/3x400

EKR15.1P

15

Up to 225 kW

240 kW

4x5A/230V

3x230/3x400

EKR30

30

Up to 42 kW

42 kW

1x5A/230V

3x230/3x400

EKR30P

30

Up to 420 kW

450 kW

4x5A/230V

3x230/3x400

* Extra load control with contactor

For one-phase and two-phase heaters control we recommend to use proportional controller EKR6.1 and temperature sensor TJK10K. Controller and 

sensor are not included in the package of product.

Model

Controlled load [kW]

Maximum controlled current [A] Voltage output

EKR6.1

6,4 kW/400V

16 A

2x400V

3.2 kW/230V

1x230V

Electric duct heaters with built-in control has installed internal controller EKR-KN which works by algorithm impulse/pause..., that enables fine tem-

perature control. Regulator controls load by triacs without moving parts, which causes no-noise commutation. Following models of heaters are with 

internals controllers, and there are differences between them:

Type 

NV

 - you can set temperature of heater with potentiometer installed on heaters casing. 

Type 

NI

 - you can set temperature from distance with wired remote potentiometer 

TR5K

Type 

NIS

 – heater control from distance with 0 – 10V signal.

Type 

PTC

 – heater with installed air flow sensor.

Type 

PS

 – heater with installed pressure sensor

Type 

NV PTC/PS

 or 

NV PH

 – heater with installed air flow sensor and pressure sensor.

Heaters with built-in controls comes with temperature duct sensor in the package of the product (except type EKS NIS).

The duct heaters are designed for a minimum air velocity of 1,5 m/s. If the air flow is lower than 1.5 m/s it can often be activated overheat protection.

Model

Control

Control type

EKS

External controller EKR

External control

EKS NV

Built-in controller EKR-KN

Control on heaters casing, default temperature 

setpoint 

0°C ... +30°C

EKS NV PTC/PS, EKS NV PH

Built-in controller EKR-KN

Control on heaters casing, default temperature 

setpoint 

-10°C  ...  +50°C

. Air  flow  sensor  and 

pressure sensor are installed inside the heater. 

Difference between heaters is EKS NV PTC/PS 

and EKS NV PH, that EKS NV PH temperature 

setpoint is 

-20°C iki -5°C

.

EKS NI

Built-in controller EKR-KN

Remote  control  with  wired  potentiometer,  de-

fault temperature setpoint 

0°C ... +30°C

EKS NIS

Built-in controller EKR-KN

0-10V control

In heaters type NV PTC/PS, NV PH are installed controllers with default temperature setpoint -10°C ... +50°C, on your needs we 

can install controllers with different temperature setpoints:

-40 °C till -10 °C

0 °C till +30 °C

-5 °C till 0 °C

-20 °C till -5 °C

-10 °C till 0 °C

-

Please inform about needed temperature setpoint before production, othervise heater will be produced with factory default 

setpoint.

Summary of Contents for EKS

Page 1: ...Subject to technical modification EKS_P0082_AZ_0002 ELECTRIC DUCT HEATERS EKS EKS NI EKS NIS EKS NV EKS NV PH EKS NV PTC PS USER MANUAL...

Page 2: ...NSTALATION 4 Electrical connection 4 WIRING DIAGRAMS 5 HEATERS DESCRIPTION STRUCTURE 6 Double overheat protection 6 Duct connection 6 CONTROL 7 External control of three phase heaters 7 External contr...

Page 3: ...dry place with humidity not more 70 20 C average ambient temperature must be 5 40 C Storing place must be covered from water and dirt Avoid long term storing It is not recommended to store products m...

Page 4: ...air filter before the heater AHU air handling unit with heat recovery F filter for supply air Depending on the installation location of the heater in the duct relative to the engine before or behind...

Page 5: ...Control board TR 5 external potentiom eter TJK10K Temperature sensor X3 X26 the control board contacts see on PCB EKS NV EKS NI EKS NIS 3x400V I V heater steps B protection from overheat ing 50 C auto...

Page 6: ...r a minimum period of 15 years To ensure security in case of fire in all electric air heaters are installed 2 heat protection thermostats First overheat protection automatically activates if temperatu...

Page 7: ...u can set temperature from distance with wired remote potentiometer TR5K Type NIS heater control from distance with 0 10V signal Type PTC heater with installed air flow sensor Type PS heater with inst...

Page 8: ...NI NIS NV NV PTC PS NV PH 800x500 WxH Length L mm 370 420 440 500 Power kW 9 12 15 18 21 24 27 30 33 36 39 42 45 51 54 60 66 EKS NI NIS NV NV PTC PS NV PH 1000x500 WxH Length L mm 370 420 440 500 Powe...

Page 9: ...3 x 400 3 x 230 Power kW 18 0 9 9 30 0 15 15 54 0 15 9 12 18 18 0 9 9 30 0 9 9 12 54 0 9 12 15 18 EKS NIS 1200x550 WxH Length L mm 370 440 370 440 Voltage V 50Hz 3 x 400 3 x 230 Power kW 21 0 12 9 36...

Page 10: ...kers data it must correspond to heaters electrical data 2 Check isolation of connection cables wires check is heater grounded 3 Check power supply source data it must correspond to heaters elec trical...

Page 11: ...11 EKS NI NIS NV NV PH NV PTC PS www salda lt...

Page 12: ...tos descriptions and etc has to be sent with this form Photos must be taken in such a way that product or product part label and possible defect part is clearly visible and identified Warranty claim w...

Reviews: