background image

9

 4

EN

4.3.1. System blocking settings

Fire protection settings.

Controller box heating settings.

CO2 reduction settings.

B11

B12

F1

F2

Number

Function

Block automatic control:

   

Auto: 

automatic control is enabled;

   

Block:

 automatic control is disabled.

Standby blocking mode:

     

Never:

 standby is allowed;

     

Always: 

standby is not allowed;

     

Heating season:

 standby is prohibited during heating season;

   

  Cooling season: 

standby is prohibited during cooling season.

Standby time limit per day (in minutes). Maximum allowed standby 

time per 12 h. Standby timer resets at 0:00 and 12:00.

F1

F2

B13

I1

F3

F3

Number

Function

Current setting indication.

I1

Summary of Contents for Ptouch

Page 1: ...Ragain s g 100 LT 78109 iauliai Lithuania Tel 370 41 540415 Fax 370 41 540417 office salda lt www salda lt Art no PRGPU081 Remote control panel Ptouch Service manual MCB MCB_P0096_AZ_0001...

Page 2: ...YSTEM MODE SWITCH SETTINGS 12 8 FAN SPEED SWITCH SETTINGS 13 9 AIR FILTER PROTECTION SETTINGS 14 10 FIRE PROTECTION SETTINGS 15 11 CONTROLER BOX HEATING SETTINGS 16 12 CO2 REDUCTION SETTINGS 17 13 FAN...

Page 3: ...PROTECTION INPUT SETTINGS 33 27 HEATER PROTECTION INPUT SETTINGS 34 28 COOLER PROTECTION INPUT SETTINGS 35 29 FILTER PRESSURE RELAY INPUT SETTINGS 35 30 FIRE DAMPER SWITCH INPUT SETTINGS 36 31 BYPASS...

Page 4: ...hich displays the status of the system fault reports and service settings Features Simple use Surface mounted 4 3 touch screen Display of functions and set points Acoustic response to touch Maximum fa...

Page 5: ...n plugs and the hole throughout the wall to install the cable Insert the nylon plugs NOTE You can use special metal plugs included instead of nylon ones 6 Use included 2 9x16 DIN7981C screws and mount...

Page 6: ...6 B2 B1 I1 4 1 Service login 4 SERVICE Number Function Entered code masked 2200 Number Function Clear last entered digit Confirm entered code I1 B1 B2 4 EN 4 2 Service menu B2 B6 B1 B5 B3 B4 B7 B8...

Page 7: ...r Function Main settings Fan settings Damper settings Heat exchanger settings Heater settings Cooler settings Digital input settings Sensor settings Communication settings B1 B4 B2 B3 B5 B6 B7 B8 B9 B...

Page 8: ...settings Air temperature control settings Air temperature protection settings System mode switch settings Fan speed settings Air filter protection settings Fire protection settings Controller box hea...

Page 9: ...ock automatic control is disabled Standby blocking mode Never standby is allowed Always standby is not allowed Heating season standby is prohibited during heating season Cooling season standby is proh...

Page 10: ...rature Extract room air supplied air temperature is variable and includes supply temperature compensation Supplytemperaturecompensation Onlyavailableiftemperaturecon trol type is extract room air Supp...

Page 11: ...air Range 200 600 C 20 0 60 0 C Supply temperature limit timeout If supplied air temperature remains outside set limits for specified period supply temperature limit alarm and its related action is e...

Page 12: ...itch type None no remote switch Push push button type switch On Off normal switch PIR passive infrared sensor Mode selected using the remote switch Standby Building protection Economy Comfort F1 F2 F1...

Page 13: ...al switch for enabling custom fan speeds BOOST Push push button type switch for operating fans at their maximum speeds BOOST On Off normal switch for operating fans at their maximum speeds Supply fan...

Page 14: ...pressure relays for filter contamination detection Supply one pressure relay in supplied air duct Extract one pressure relay in extracted air duct Both two pressure relays Number of days between filte...

Page 15: ...topped Boost extract air supply fan is stopped extract fan is operated at full speed Boost supply and extract air both fans are operated full speed NOTE Fire protection action can be canceled by cance...

Page 16: ...11 CONTROLER BOX HEATING SETTINGS Number Function AHU Control box heating Enabled Disabled Control box heating temperature set point Range 0 20 C F1 F2 F1 F2 I1 Number Function Current setting indica...

Page 17: ...INGS Number Function CO2 Level protection Enabled Disabled Optimal CO2 level Range 0 1000 ppm Allowed CO2 level range around the desired CO2 level Range 0 1000 ppm F1 F2 F3 F1 F2 F3 I1 Number Function...

Page 18: ...18 13 EN 13 FAN SETTINGS B2 B1 B3 Number Function Fan speed settings Fan voltage settings Fan protection settings B1 B2 B3 13 1 Fan speed control settings F1 F5 F2 F4 F3 I1...

Page 19: ...ified minimum and maximum voltages Pressure control using pressure sensor signals using maximum air pressure setting Air flow control using pressure sensor signal calculated to air flow volume Use K f...

Page 20: ...SETTINGS Number Function Minimal fan voltage in V 100 Used as a limiting value Range 0 1000 0 10 00 V Maximal supply fan voltage in V 100 Used as a limiting value or when Fan control type is Percent...

Page 21: ...ction by monitoring duct pressure Enabled alert is risen and system is stopped if pressure in a duct does not increase after fan start Disabled fan created pressure monitoring is off Time limit for ai...

Page 22: ...22 16 DAMPER SETTINGS B2 B1 B3 Number Function Supply extract damper settings Recirculation damper settings Fire damper settings B1 B2 B3 16 1 Supply extract damper settings F1 F2 I1 16 EN...

Page 23: ...rovided Can be opened or closed partially Time required for supply extract damper to fully open in seconds Range 0 255 s F1 F2 Number Function Current setting indication I1 17 RECIRCULATION DAMPER SET...

Page 24: ...1 Number Function Fire damper type None One switch Two switches Time required for fire damper to fully open in seconds Range 0 255 s Fire damper testing Enabled Disabled Fire damper testing interval i...

Page 25: ...te heat exchanger frost protection strategy None Pre heating by set point Pre heating by frost point Recirculating by set point Recirculating by frost point Set point as a difference from frost point...

Page 26: ...HEATER SETTINGS Number Function Supplied air heater settings Fresh air pre heater settings Electrical heaters cooling settings Hydraulic heater protection B1 B2 B3 B4 19 1 Supplied air heater settings...

Page 27: ...ical pre heater PWM time interval if pre heater type is Electri cal on off Range 0 300 s Alarm overheat action None Stop system Intensive ventilation F1 F2 F3 Number Function Current setting indicatio...

Page 28: ...er Function Current setting indication I1 Number Function Fresh air pre heater type None Electrical 0 10VDC Electrical on off Hydraulic Electrical pre heater PWM time interval if pre heater type is El...

Page 29: ...rature In a case of lower supplied air temperature system is stopped Range 30 10 C Water temperature low limit In a case of lower returning fluid temperature system is stopped Range 30 10 C Hydraulic...

Page 30: ...ing indication I1 Number Function Hydraulic cooler Enabled Disabled Hydraulic cooler frost temperature In a case of lower supplied air temperature system is stopped Range 30 10 C DX cooler Enabled Dis...

Page 31: ...Function External control input settings Fan protection input settings Heater protection input settings Cooler protection input settings Filter pressure relay settings Fire damper switch input setting...

Page 32: ...umber Function Current setting indication I1 Number Function Fire protection input NO normally open NC normally closed System mode switch input NO normally open NC normally closed Fan speed switch inp...

Page 33: ...UT SETTINGS Number Function Supply fan protection input NO normally open NC normally closed Extract fan protection input NO normally open NC normally closed F1 F2 Number Function Current setting indic...

Page 34: ...unction Heater manual protection input NO normally open NC normally closed Heater automatic protection input NO normally open NC normally closed Pre heater manual protection input NO normally open NC...

Page 35: ...ion DX cooler protection input NO normally open NC normally closed F1 Number Function Current setting indication I1 28 COOLER PROTECTION INPUT SETTINGS F1 I1 29 FILTER PRESSURE RELAY INPUT SETTINGS F1...

Page 36: ...closed Extract filter pressure relay input NO normally open NC normally closed Number Function Fire damper opened input NO normally open NC normally closed Fire damper closed input NO normally open N...

Page 37: ...TINGS Number Function Bypass opened input NO normally open NC normally closed Bypass closed input NO normally open NC normally closed F1 F2 Number Function Current setting indication I1 F1 F2 I1 32 SE...

Page 38: ...B1 Number Function 0 10VDC sensor settings Temperature sensor settings Number Function Supplied air quality sensor settings Extracted air quality sensor settings B1 B1 B2 B2 F1 F2 F3 I1 33 SUPPLIED AI...

Page 39: ...in ppm at minimum voltage 0 VDC Range 0 2000 ppm CO2 level in ppm at maximum voltage 10 VDC Range 0 2000 ppm Number Function Supplied air quality sensor type None RH Relative humidity sensor CO2 Carbo...

Page 40: ...ed air temperature sensor settings Outdoor air temperature sensor settings Hydraulic heater water temperature sensor settings Hydraulic pre heater water temperature sensor settings Hydraulic cooler wa...

Page 41: ...ce using Modbus NTC 3997 thermo resistive sensor Temperature sensor alarm activated if temperature sensor value is less than 50 C or more than 50 C None Stop system Emergency run F1 F2 Number Function...

Page 42: ...B1 Number Function Internal Modbus port settings BMS Modbus port settings B1 B2 36 COMMUNICATION SETTINGS Number Function Current setting indication I1 F1 F2 F3 I1 36 1 Internal modbus port settings...

Page 43: ...ts 1 stop bit O 8 1 Odd parity 8 data bits 1 stop bit N 8 2 No parity 8 data bits 2 stop bits E 8 2 Even parity 8 data bits 2 stop bits O 8 2 Odd parity 8 data bits 2 stop bits F1 F2 F3 37 BMS MODBUS...

Page 44: ...y 8 data bits 1 stop bit E 8 1 Even parity 8 data bits 1 stop bit O 8 1 Odd parity 8 data bits 1 stop bit N 8 2 No parity 8 data bits 2 stop bits E 8 2 Even parity 8 data bits 2 stop bits O 8 2 Odd pa...

Reviews: