22. ECODESIGN DATA TABLE
RIRS EKO 3.0
1200 HE
1200 HW
1900 HE
1900 HW
Declared typology
bidirectional
bidirectional
bidirectional
bidirectional
Type of drive
Variable
Variable
Variable
Variable
Type of HRS
regenerative
regenerative
regenerative
regenerative
Thermal efficiency of heat recovery
[ % ]
75,2
75,2
73
73
Nominal NRVU flow rate
[ m
3
/s ]
0,36
0,36
0,41
0,41
Effective electric power input
[ kW ]
0,84
0,84
0,79
0,79
SFPint
[ W/(m
3
/s) ]
818
818
741
741
Face velocity
[ m/s ]
1,3
1,3
1,48
1,48
Normal external pressure
[ Pa ]
250
250
250
250
Internal pressure drop of ventilation components
[ Pa ]
170/108
170/108
198/125
198/125
Static efficiency of fans used in accordance with
Regulation No 327/2011
[ % ]
31,8
31,8
39,8
39,8
Declared maximum external leakage
[ % ]
<1
<1
<1
<1
Declared maximum internal leakage
[ % ]
<3
<3
<3
<3
Energy clasification of the filters
E
E
E
E
Description of visual filter warning
Pressure contro
Pressure contro
Pressure contro
Pressure contro
Casing sound power level (Lwa)
[ dB(A) ]
53
53
59
59
ErP Compliance
2018
2018
2018
2018
Internet address for disassembly instructions
www.salda.lt
RIRS EKO 3.0
2500 HE
2500 HW
3500 HE
3500 HW
5500 HE
5500 HW
Declared typology
bidirectional bidirectional bidirectional bidirectional bidirectional bidirectional
Type of drive
Variable
Variable
Variable
Variable
Variable
Variable
Type of HRS
regenera-
tive
regenera-
tive
regenera-
tive
regenera-
tive
regenera-
tive
regenera-
tive
Thermal efficiency of heat recovery
[ % ]
84,1
84,1
81,3
81,3
76,4
76,4
Nominal NRVU flow rate
[ m
3
/s ]
0,69
0,69
1,11
1,11
1,69
1,69
Effective electric power input
[ kW ]
1,37
1,37
2,37
2,37
3,58
3,58
SFPint
[ W/(m
3
/s) ]
847
847
1159
1159
1061
1061
Face velocity
[ m/s ]
1,55
1,55
1,73
1,73
2,11
2,11
Normal external pressure
[ Pa ]
250
250
250
250
250
250
Internal pressure drop of ventilation
components
[ Pa ]
192/179
192/179
355/242
355/242
353/282
353/282
Static efficiency of fans used in accor
-
dance with Regulation No 327/2011
[ % ]
43,5
43,5
48,7
48,7
65,2
65,2
Declared maximum external leakage
[ % ]
<1
<1
<1
<1
<1
<1
Declared maximum internal leakage
[ % ]
<3
<3
<3
<3
<3
<3
Energy clasification of the filters
E
E
E
E
E
E
Description of visual filter warning
Pressure
contro
Pressure
contro
Pressure
contro
Pressure
contro
Pressure
contro
Pressure
contro
Casing sound power level (Lwa)
[ dB(A) ]
59
59
63
63
69
69
ErP Compliance
2018
2018
2018
2018
Internet address for disassembly instructions
www.salda.lt
Summary of Contents for RIRS EKO 3.0 1200 HE
Page 1: ...RIRS 1200 5500 H EKO 3 0 EN MOUNTING AND INSTALLATION INSTRUCTION ...
Page 28: ...28 EN RIRS 1200 5500 H EKO 3 0 v2019 06 21 7 RIRS 3500 HW EKO 3 0 ...
Page 37: ... 37 RIRS 1200 5500 H EKO 3 0 v2019 06 ...
Page 38: ...38 RIRS 1200 5500 H EKO 3 0 v2019 06 ...