background image

10 

| EN

RIS PE 3.0 v2020.1

5.5.3.  DRAINAGE INSTALLATION

Before every heating season the condensate tube shall be filled with water as indicated during the first start-up! Before every heating 

season the condensate tube shall be filled with water as indicated during the first start-up!

AHU (1) is built on a foundation in a such way that the side of AHU (1) with drainage exhaust pipe (2) is lower 0° - 3° than the other side (the con-

crete max. value is shown on the picture). The side of AHU with drainage pipe can not be higher than the other side. 

The system must be connected with pipes (4,5) in such order: AHU (1), siphon (3) and sewerage system (6). Pipes (4,5) should be bended not 

less than 3°

 (1 meter of pipe must be bended 55 mm downwards)! Before turning on AHU (1) the draining system should be filled up with at least 

0,5 l of water (siphon (3) must be always filled with water), also check if water reaches sewerage system (6)! In other case premise can be flooded. 

Draining system must be installed in the premise where the temperature is not lower than 0°C. If temperature falls below 0°C the draining system 

should be isolated with thermal isolation or heating installed. 

The siphon (3) must be mounted below the AHU (1) level.

5.6.  CONNECTION OF THE AIR DUCT

• Connected air ducts must be straight and have their own fixing.

• Make sure that the fans can not be entered through air duct heads. If it is possible to enter the fan, protective grid should be installed. You can 

choose it in our website.

• Do not reduce the diameter of the piping near air inlet or exhaust ducts. If you want to reduce the speed of air in the system, drop of pressure 

and noise level, you can increase the diameter.

• In order to reduce the level of the noise in the air supply system, install dampers (see chapter on their installation).

• In order to reduce air loss in the system, the air ducts and profile parts should be of class C and higher. Their catalog can be found in our website.

• Outside air and exhaust system piping should be isolated in order to prevent heat loss and condensation.

• It is recommended to maintain a distance of up to 8 meters between air intake and air exhaust ducts. Air supplying system should be installed 

further from potential air pollution sources.

• Use holders while installing air ducts next to the ventilation equipment. They suppress vibration and assure a firm installation of various system 

parts. Necessary holders can be found in our catalog or website.

• A common mistake is that air ducts are connected in inappropriate place. On the ventilation equipment there are signs, indicating the air duct to 

be connected. Before starting the system carefully check whether the work was performed properly.

5.7.  CONNECTION OF THE UNIT TO ELECTRIC NETWORK

• Supply voltage to the unit must be connected by a qualified specialist following the manufacturer’s instructions and effective safety instructions.

• The unit’s power network voltage must correspond to electrotechnical parameters of the unit indicated in the technical decal.

• The unit’s voltage, power and other technical parameters are provided in the unit’s technical decal (on the unit casing). The unit must be connect-

ed to the voltage plug socket of the grounded power network in compliance with the effective requirements.

• The unit must be earthed according to the rules on installing electrical equipment.

• It is prohibited to use extension wires (cables) and power network plug socket distribution devices.

• Prior to carrying out any ventilation unit installation and connection activities (until its hand-over to the customer), the unit must be disconnected 

from the power network.

• After installation of the ventilation unit, the power network plug socket must be accessible at any time and disconnection from the power network 

is performed through the two-pole circuit breaker (by disconnecting phase pole and neutral).

• The unit must be thoroughly checked against damages (execution, control, measurement nodes) during transportation before it is connected to 

the power network.

• The power cable can be replaced only by a qualified specialist upon the evaluation of the rated power and current.

The manufacturer does not assume any liability for personal injuries and property damage due to nonconformance with the 

provided instructions.

Summary of Contents for RIS 1000 PE 3.0

Page 1: ...RIS PE 3 0 EN MOUNTING AND INSTALLATION INSTRUCTION...

Page 2: ...11 5 8 1 SYSTEM PROTECTION 11 5 8 2 PRE STARTUP RECOMENDATIONS OF THE UNIT IN THE PRESENCE OF THE ENDUSER 11 6 MAINTENANCE 12 6 1 SAFETY INSTRUCTION 12 6 2 GENERAL RECOMMENDATIONS FOR THE MAINTENANCE...

Page 3: ...place or on the dashed place of a technical manual in order to keep the important information about the unit Figure 2 1 Technical label 1 Logo 2 Product code SKU 3 Product name 4 Technical data 5 Pro...

Page 4: ...t touch heating elements until they haven t cooled down Some devices are heavy thus one should be very careful while transporting and installing Use suitable lifting equipment While connecting electri...

Page 5: ...control devices Acoustic insulation of the walls 30 50 mm Easy to mount The unit can not be used as an air heater Not suitable for swimming pools saunas and other similar facilities 4 2 DIMENSIONS AN...

Page 6: ...0 2750 protection class IP 44 IP 44 IP 44 IP 44 Total power consumption power current kW A 3 35 15 24 4 68 20 50 6 6 11 27 9 73 16 19 Heater phase voltage 50 Hz VAC 1 230 1 230 3 400 3 400 power consu...

Page 7: ...and with the average ambient temperature ranging between 5 C and 30 C The place of storage must be protected against dirt and water The units must be transported to the storage or installation site u...

Page 8: ...Supply air temp sensor POSSIBLE PCB INPUTS OUTPUTS FA Fire alarm H1 Working indication output FPP Fireplace protection H2 Alarm indication output System mode switch START STOP Fans speed switch BOOST...

Page 9: ...tect the unit during transportation It is recommended to remove the film because other wise oxidation signs may occur Before every heating season the condensate tube shall be filled with water as indi...

Page 10: ...nsation It is recommended to maintain a distance of up to 8 meters between air intake and air exhaust ducts Air supplying system should be installed further from potential air pollution sources Use ho...

Page 11: ...k whether operation systems and unit elements as well as automation and automation devices were not damaged during installation all electrical devices are connected to power supply and fit for service...

Page 12: ...eck the operation and tune up if necessary Air intake and discharge system Check the connections Clean Air duct system Check the tightness Clean Dampers diffusers grid Check the tightness of connectio...

Page 13: ...EXCHANGER MAINTENANCE Be sure the fan is disconnected from power source before performing any maintenance or repair Proceed to maintenance and repair after any rotation in the fan stopped Clean it onc...

Page 14: ...e water cooler is set accordingly to the PI regulator in the range between 0 and 100 The halocarbon cooler is switched on when PI regulator value exceeds the value set in the menu see section II 6 4 2...

Page 15: ...nd RS485_2 RS485_1 remote control panel socked RS485_2 ModBus port S touch control panel must be connected to RS485_2 ModBus connection RJ11 socket contacts reference 1 COM 2 A 3 B 4 24V Microswitches...

Page 16: ...extract 04h_Read_Input 2 1 Exhaust air temperature sensor value Hex E0 23 ToutDoor 04h_Read_Input 3 1 Ouside air temperature sensor value Hex FFEC 7 4 ELECTRICAL CONNECTION OF THE HVAC UNIT Electrical...

Page 17: ...lso install measuring and operating devices in line with the provided guidelines Air temperature sensors and air quality converters Supply air temperature sensors and air quality converters if additio...

Page 18: ...ON OFF 230V 50Hz O 3A 100 X3 RS485_2 ModBus I O X4 RS485_1 Remote controller FLEX I O X32 1 LOW Electrical heater guard from overheat ing I X32 3 HIGH BOOST increase the flow of air I X32 4 COM COM X3...

Page 19: ...temperature sensor X41 1 Exhaust air temperature sensor AI X41 2 COM 7 9 REGULAR SYSTEM CHECK UP The operation of the switching device contactor should be visually inspected every 3 4 months the casi...

Page 20: ...000 PE 3 0 RIS 1500 PE 3 0 VK Summer casette VK FR Spare filters FR FR Spare filters FR SK1 Fresh air damper SKM SD Pressure switch SK2 Extract air damper SKG SK Air damper SKG SKP1 outdoor air damper...

Page 21: ...1 PE N L1 L1 N PE X16 7 CE7 7 120V 80V 6 N Mid Max C N L Min X43 X44 X15 X28 X11 X12 X14 5 X3 1 2 3 4 N PV PE C1 L 0 140V 170V 230V ATR X16 4 TA U HR DTJ 100 TK 1 2 T set COM X33 21 X33 22 BK Black BN...

Page 22: ...E X16 7 CE7 7 120V 80V 6 N Mid Max C N L Min X43 X44 X15 X28 X11 X12 X14 5 X3 1 2 3 4 N PV PE C1 L 0 140V 170V 230V ATR X16 4 TA U HR DTJ 100 TK 1 2 T set COM X33 21 X33 22 BK Black BN Brown BU blue R...

Page 23: ...1 24VDC Y1 Control OPEN AC 24 V Y2 Control CLOSE AC 24 V G System potential AC 24 V X35 2 X35 1 X33 13 X33 14 X33 18 X33 12 X33 17 X33 25 X33 26 X34 1 X34 2 X34 3 X34 4 X34 5 X34 6 X34 7 X34 8 X40 1...

Page 24: ...W5 black X10 X8 X44 X15 X43 A4 1 A4 2 X11 X12 X14 X28 X25 X31 LOW COM AC N PUMP B 0 10 COM RG1 PRV V1 1 02 1 1 PE PE ina 2 4 5 L1 Black L2 Brown L3 Grey N Blue 1 3 11 11 13 14 13 14 15 15 16 16 4 8 7...

Page 25: ...X21 2 3 4 5 77 77 W3 brown 79 79 W3 white TRUE TRUE 83 83 W8 2 81 81 W8 1 TRUE TRUE VAL VAL VAL HIGH TIMER COM CHILL COM ALARM COM ANTI F 24V A1 1 A1 2 AC N EXT EXT A 0 10 COM X39 1 X39 2 A2 1 A2 2 D...

Page 26: ...100 101 101 110 110 105 105 106 107 116 111 106 119 120 119 120 113 115 115 118 112 104 109 1 2 3 4 5 6 M X29 769 612 002 000 7 8 9 10 11 12 100 116 111 107 102 102 Figure 9 6 RIS 1500 PE 3 0 PV 2750...

Page 27: ...yellow 96 96 W6 grey 94 94 W6 red 99 99 98 98 142 TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE TRUE PE N 1 2 F X34 EPN1214 127 W1 black 127 128 W1 black W2 black 128 W2 black 123 W1 gr ye 123 124 W1...

Page 28: ...perat ing or malfunctioning if installed Too low air flow in air ducts activates auto matic protection Check if air filters are not clogged Check if fans are rotating Manual protection is activated Po...

Page 29: ...e equipment to manufacturer Delivery costs should be covered by customer Manufacturer reserves the right to change this technical passport any time without prior notice if some typographic errors or i...

Page 30: ...30 RIS PE 3 0 v2020 1...

Page 31: ...31 RIS PE 3 0 v2020 1...

Page 32: ...ANCE TABLE Product name SERIAL number Instalation Interval Date Fan cleaning Once a year Heat exchanger cleaning Once a year Filter replacement Every 3 4 months Look at the product label At least NOTE...

Reviews: