EN |
33
RIS 1200-2500 P EKO 3.0 v2020.1
RIS EKO 3.0
2500 PE 4.5
2500 PE 9.0
2500 PE 18.0
2500 PW
Declared typology
bidirectional
bidirectional
bidirectional
bidirectional
Type of drive
Variable
Variable
Variable
Variable
Type of HRS
recuperative
recuperative
recuperative
recuperative
7KHUPDOHႈFLHQF\RIKHDWUHFRYHU\
>@
80,4
80,4
80,4
80,4
1RPLQDO1598ÀRZUDWH
[ m
3
/s ]
0,64
0,64
0,64
0,64
(ႇHFWLYHHOHFWULFSRZHULQSXW
[ kW ]
1,32
1,32
1,32
1,32
SFPint
[ W/(m
3
/s) ]
889
889
889
889
Face velocity
[ m/s ]
1,48
1,48
1,48
1,48
Normal external pressure
[ Pa ]
250
250
250
250
Internal pressure drop of ventilation components
[ Pa ]
233/144
233/144
233/144
233/144
6WDWLF HႈFLHQF\ RI IDQV XVHG LQ DFFRUGDQFH ZLWK
Regulation No 327/2011
>@
41,1
41,1
41,1
41,1
Declared maximum external leakage
>@
<1
<1
<1
<1
Declared maximum internal leakage
>@
<3
<3
<3
<3
(QHUJ\FODVL¿FDWLRQRIWKH¿OWHUV
E
E
E
E
'HVFULSWLRQRIYLVXDO¿OWHUZDUQLQJ
Pressure control
Pressure control
Pressure control
Pressure control
&DVLQJVRXQGSRZHUOHYHO/ZD
[ dB(A) ]
61
61
61
61
ErP Compliance
2018
2018
2018
2018
Internet address for disassembly instructions
ZZZVDOGDOW