SMARTY RV v2019.12
X10
1
MCB PE
Recirculation damper control 3P
2
MCB GND
3
MCB 24VDC_OPEN (DO4)
4
MCB 24VDC_CLOSE (DO5)
X11
1
MCB PE
By-pass damper control 3P
2
MCB GND
3
MCB 24VDC_OPEN (DO2)
4
MCB 24VDC_CLOSE (DO3)
X12
1
PE
24VDC Power supply for water heater actuator
2
GND
3
+24VDC
X13
1
+24VDC
By-pass step motor control
2
STEP_B/
3
STEP_B
4
STEP_A/
5
STEP_A
6
+24VDC
X14
1
GND
Supply air fan control output (0-10VDC)
2
MCB AO1(0-10VDC)
3
GND
Extract air fan control output (0-10VDC)
4
MCB AO2(0-10VDC)
5
GND
Supply air heater control output (0-10VDC)
6
MCB AO3(0-10VDC)
X15
1
+24VDC
MCB Power supply 24VDC
2
GND
3
PE
C
X18
Remote Control connection (RS485)
X19
K? [`?+! " ?Z\
8.1.2. CO
2
SENSOR OR CONNECTION OF HUMIDITY SENSOR RH
Settings:
CO
2
converter (S-KCO2 or S-RCO2-F2)
1. Set that next to 0.10 V input an extracted air CO
2
converter is connected “
SERVICE › SENSORS › 0-10 VDC SENSORS › AIR QUALITY SENSOR 1
” (choose “Extract CO
2
”)
% &
X 7 & /
X 7 X & %///
3. CO
2
reduction function is activated
“SERVICE › MAIN › CO
2
REDUCTION FUNCTION”
(controlled recirculation damper and fans)
4. To see the CO
2
&
ADJUSTER › MONITORING › EXTRACT AIR CO
2
”
Humidity RH converter (S-KFF-U) or room RH converter (S-RFF-U-D-F2)
1. Set that next to 0.10 V input an extracted air RH converter is connected
“SERVICE › SENSORS › 0-10 VDC SENSORS › AIR QUALITY SENSOR 2”
(choose “Extract RH”)
% &
X 7 & / [//// z\
X 7 X & /// [////¡// z\
j ¢ `$ &
“ADJUSTER › MONITORING › EXTRACT AIR RH”