5
Smarty 3X P
www.salda.lt
- Do not use the unit for purposes other than its’ intended.
- Do not disassemble or modify the unit in any way which may lead to mechanical failure or injury.
- Use special clothing and be careful while performing maintenance and repair jobs – the unit’s and its components’ edges may be sharp and cut-
ting.
- Do not wear loose clothing that could be entangled in to operating unit.
- If a outside object enters the unit, immediately disconnect power source. Before removing object, make sure that any mechanical motion has
stopped, the heater has cooled down and the restart is not possible.
- Do not connect to any other power source than indicated on the model label.
- Do not place or operate unit on unsteady surfaces and mounting frames.
- Mount the unit firmly to ensure safe operating.
- Never use this unit in the environment containing any explosive or aggressive elements.
- Do not use the unit if external connections are broken or damaged. If there are any defects, stop operating the unit and replace the damaged parts
immediately. That can be performed only by qualified electrician.
- Do not use water or another liquid to clean electrical parts or connections.
- If you notice condensat on electrical parts or connections, stop operating the unit.
Unit is designed to operate only indoors.
It is forbidden to use the unit in potentially explosive environment.
Unit is designed to supply/extract only clean air (free of chemical compounds causing metal corrosion, of substances aggressive to zinc, plastic and
rubber, and of particles of solid, adhesive and fibred materials).
1. Mounting bracket with anti-vibration mounts - 4 pcs.
2. Outdoor air filter and the cover (IF).
3. Outdoor air temperature sensor (TL).
4. Bypass damper (M1).
5. Control board.
6. CE7/7 power supply cable - 3m.
7. Pressure sensor 2 pcs.
8. Supply air fan (PV)
9. Air flow marking.
10. Flange 4 pcs.
11. Condensate tray.
12. Exhaust air fan (IV)
13. Condensate tube plugs.
14. Heat exchanger (PR)
15. Extract air sensor (TA).
16. EPP casing.
17. Extract air filter and the cover (PF).
18. Galvanized steel casing.
Outdoor
- temperature min./max.
*
[°C]
-15 / +40
- humidity
[%]
90
Extract
- temperature min./max.
*
[°C]
+15 / +40
- max. humidity
[%]
70
*Can be used at temperatures below -15 ° C with pre-heater, the power of which is over 1000 W.
extract
air
supply
air
outdoor
air
exhaust
air