11
Smarty 3X P
www.salda.lt
Subject to technical modification.
Smarty 3X P
LWA total,
dB(A)
LWA, dB(A)
125 Hz 250 Hz 500
Hz 1 kHz 2 kHz 4 kHz 8 kHz
Supply
57
49
50
53
48
47
45
40
Extract
50
41
43
44
42
39
37
34
Surrounding
42
34
35
36
34
32
31
27
Measured at 230 m
3
/h, 99 Pa
Temperature efficiency (balanced mass flow):
Extract air = 20 °C/60 % RH
Outdoor air = -7 °C / 2 °C / 7 °C
Smarty 3X P
Fans
phase/voltage
[50Hz/VAC]
1,230
exhaust
power/current
[kW/A]
0,084/0,75
speed
[min
-1
]
3200
supply
power/current
[kW/A]
0,084/0,75
speed
[min
-1
]
3200
protection class
IP
34
Thermal efficiency up to
94%
Total power consumption (
power/current)
[kW/A]
0,168/1,5
Insulation of walls
[mm]
15 - 30
Color
RAL
white (9016)
Weight (net, without packing)
[kg]
53
Automatic control integrated
MCB
Exhaust air filter
class
G4
width
L [mm]
225
height
H [mm]
195
depth
W [mm]
25
model
MPL
Supply air filter
class
G4/F7*
width
L [mm]
225
height
H [mm]
195
depth
W [mm]
25
model
MPL
W
*F7 optional.
v [m /h]
3
Δ P
[Pa]
stat
v [l/s]
Δ P
[Pa]
stat
v [l/s]
v [m /h]
3
Δ P
[Pa]
stat
v [m /h]
3
v [l/s]
P [W]
Δ P
[Pa]
stat
v [m /h]
3
v [l/s]
P [W]
Performance
Power consumption
Supply air
Exhaust air
Specific fan power (SFP)
SFP= x 3600
total power for supply air & exhaust fans
kW
air flow
m
3
/h
Temperature efficiency