21
Smarty 3X P
www.salda.lt
Code
Alarm/warning information
Automatically cancels
A.01
Rotor broken belt alarm
A.02
Fireplace protection activated
A.03
Dryness protection activated
+
A.04
Plate heat exchanger frost protection activated
+
A.05
Plate heat exchanger frost protection. System stopped.
A.06
Plate heat exchanger frost protection (pressure relay). System stopped.
A.07
Hydraulic heater frost protection. System stopped.
A.08
Too low supply temperature
+
A.09
Too high supply temperature
+
A.10
Too low supply temperature. System stopped.
A.11
Too high supply temperature. System stopped.
A.12
Change supply air filter (pressure relay). System stopped.
A.13
Change extract air filter (pressure relay). System stopped.
A.14
Change supply and extract filters.
+
A.15
Change supply and extract filters. System stopped.
A.16
Supply air temperature sensor failure. Emergency run.
+
A.17
Extract air temperature sensor failure. Emergency run.
+
A.18
Exhaust air temperature sensor failure. Emergency run.
+
A.19
Fresh air temperature sensor failure. Emergency run.
+
A.20
Hydraulic heater water temperature sensor failure. Emergency run.
+
A.21
Hydraulic preheater water temperature sensor failure. Emergency run.
+
A.22
Hydraulic cooler water temperature sensor failure. Emergency run.
+
A.23
Control box temperature sensor failure. Emergency run.
+
A.24
Supply air temperature sensor failure. System stopped.
Nr.
Name
Possible values
Default
value
P
.
01
Sleep mode
0 - Off
1 - 99 sleeping time in seconds
0
P
.
02
Sound
0: Off
1: 1 –9 sound tone
2
P
.
03
Supply air temperature display
0: Not shown
1: Shown interchangeably with the set temp
0
P
.
04
CO
2
required (ppm)
0 – 99 x10ppm
20 x10
P
.
05
CO
2
allowed difference
0 – 99 x10ppm
5 x 10
P
.
06
Filtrer timer
Shows the period that passed after the
change of the filters.
0
It is possible to set desired temperature from 15 - 35 °C.
Possible alternate display of supply and set air temperature display (5 seconds - set air temperature display, 2 seconds - supply air temperature).
• In order to reach user menu, press down both B2 and B3 for 3 seconds.
• In user menu, settings of menu items (P.01, P.02 etc.) are displayed sequentially.
• Menu item is selected using elements B4 and B6.
• Pressing B5 element value of selected parameter is shown and can be changed using elements by B4 and B6.
• Press B5 to save the parameter and return to menu.
• Due to limitations of segment display, values of the element P.04 and P.05 are shown in division by 10, i.e. if 20 is displayed, it means that real value is
20 x 10 = 200.
• Touch element B1 to exit menu.
• Left time for changing filters can be monitored in users menu.
• User can reset the timer. P.06 - hold for 5 seconds item B5.
• User is warned about filter change, cancelling the warning filter timer is reset automatically.