background image

8

Smarty 3X P

www.salda.lt

1. All equipment manufactured in our factory is checked in operating conditions and tested befor delivery. Test protocol is supplied together with the 

unit. The equipment is shipped in good working order and condition to the direct client. The unit is warrantied for the period of two years from the 

invoice date.

2. If equipment is found to have been damaged during transportation, a claim should be made against carrier, as we assume no responsibility for 

such damage.

3. This warranty does not apply:

3.1. when transportation, storage, installation and maintenance instructions of the unit are violated;

3.2. when the equipment is improperly maintained, mounted - inadequate maintenance; 

3.3. when the equipment without our knowledge and permission has been upgraded or unskilled repairs were made;

3.4. when the unit was used not for its original purpose.

4. This warranty does not apply at these malfunction cases:

4.1. mechanical damage; 

4.2. damage caused by entering outside objects, materials, liquids; 

4.3. damage caused by natural disaster, accident (voltage change in the electricity network, lightning, etc..).

5. The company assumes no liability for its products either directly or indirectly damage, if the damage is caused by failure to comply with installation 

and mounting regulations, deliberate or careless users or third-party behavior.

These conditions are readily discernable when the equipment is returned to our factory for inspection.

If the direct client determines that equipment is found to be faulty, or a breakdown occurred, he should inform the manufacturer within five working 

days and deliver the equipment to manufacturer. Delivery costs should be covered by customer.

Installation should only be performed by qualified and trained staff.

• When connecting air ducts, consider the notices indicated on the casing of the unit.

• Before connecting to the air duct system, the connection openings of ventilation unit should be closed.

• Do not connect the bends close to connection flanges of the unit. The minimum distance of the straight air duct between the unit and the first branch 

of the air duct in the supply air duct must be 1xD, in air exhaust duct 3xD, where D is diameter of the air duct.

• It is recommended to use the accessories-holders. This will reduce vibration transmitted by the unit to the air duct system and environment.

• Enough space must be left for opening of the maintenance door and filter covers.

• If the installed ventilation unit is adherent to the wall, it may transmit noise vibrations to the premises. Though the level of noise caused by the fans 

is admissible, it is recommended to mount the unit at the distance of 400 mm from the nearest wall. If it is not possible, the mounting of the unit is 

recommended on the wall of the room where the level of noise is not important.

• Ducts are connected to the unit in such way that they could be easily disassembled and the heater could be removed from the unit when performing 

service or repair works.

324 mm

318 mm

1381,5 mm

685,5 mm

269 mm

1225 mm

408,5 mm

21,3 mm

685,5 mm

128 mm

324 mm

318 mm

150 mm

149 mm / 159 mm*

* according to the diameter of the duct.

Summary of Contents for Smarty 3X P

Page 1: ...Subject to technical modification Smarty 3X P_P0094_AZ_0002 AHU WITH HEAT RECOVERY Smarty 3X P User and service technical manual...

Page 2: ...ndow 23 Ptouch mode setting window 23 Ptouch menu 24 Ptouch state 24 Ptouch menu set points window 25 Ptouch date and time setting 25 Ptouch weekly schedule 26 Ptouch holiday schedule 26 Ptouch air fi...

Page 3: ...3025238 IV PV KE PE M 0 084 kW 0 92 A 230 50 V Hz 1 0 085 kW 0 93 A 230 50 V Hz 1 kW A 0 V Hz 0 kW A 0 V Hz 0 0 005 kW 0 021 A 24 50 V Hz 0 17 kW 1 87 A IP 34 TOTAL gu072489 2014 03 www salda lt 1 3 4...

Page 4: ...x 195 x 25 mm Operating ambient temperatures 5 40 C Unsuitable for operation in pools saunas and other similar premises All units are packed in the factory to withstand regular conditions of transport...

Page 5: ...ly That can be performed only by qualified electrician Do not use water or another liquid to clean electrical parts or connections If you notice condensat on electrical parts or connections stop opera...

Page 6: ...n the heat exchanger once a year Firstly take out heat exchanger cassette carefully Submerge it into a bath and wash with warm soapy water do not use soda Then rinse it with weak hot water stream too...

Page 7: ...lead to accelerated wear on motor bearings and noise vibration Clean impeller and inner housing with mild detergent water and damp soft cloth Do not use high pressure cleaner abrasives sharp instrumen...

Page 8: ...lient determines that equipment is found to be faulty or a breakdown occurred he should inform the manufacturer within five working days and deliver the equipment to manufacturer Delivery costs should...

Page 9: ...9 Smarty 3X P www salda lt Mounting on the wall with condensate tube downwards Any slopes are necessary 1 0 o 1 0o 826 Ceiling mounting with the cover downwards The slope towards the tube 0 5 1o 826...

Page 10: ...The start up and operation of the unearthed ventilation unit is prohibited It is prohibited to use extension wires cables and power network plug socket distribution devices Prior to carrying out any...

Page 11: ...75 speed min 1 3200 protection class IP 34 Thermal efficiency up to 94 Total power consumption power current kW A 0 168 1 5 Insulation of walls mm 15 30 Color RAL white 9016 Weight net without packing...

Page 12: ...sor PIR Motion detector DJ Smoke detector TJ Supply air temperature sensor CEE7 7 Power cable with plug X19 BMS network connection place X18 Control panel connection place PC Personal computer MBGatew...

Page 13: ...CO2 CO2 sensor ZAKKT0049 AKS 160 9 Silencer GSOAKS006 Stouch Remote control panel PRGPU51 Levelling feet GAGKSMARTY168_1000 Smarty 3X P legs S KFF U Dust RH sensor ZAKKT0051 Humidity RH sensor ZAKKT00...

Page 14: ...1 By default temperature is not controlled but under request it is possible to specify the desired temperature economy the mode is intended to save energy when there are no people in the premises In t...

Page 15: ...e the current mode manu ally System will inform about the next change of the mode under the schedule If any of the above mentioned functions has changed it s state into Stand by mode system checks if...

Page 16: ...g results etc Event description and time is saved in the history Filter timer setting Air filter timer informs the user about time to change the filters After changing the filters timer should be rese...

Page 17: ...oolers are used for supply air temperature and humidity reduction Water freezing temperature should be indicated for the water cooler Minimal time period between the on and off should be specified for...

Page 18: ...ng operated directing exhaust air flow to outdoor air flow by outdoor air and calculated frost temperature The difference between calculated and specified temperature during activation is indicated El...

Page 19: ...r failure Emergency run Warning Exhaust air temperature sensor failure Emergency run Warning Fresh air temperature sensor failure Emergency run Warning Hydraulic heater water temperature sensor failur...

Page 20: ...of the func tion by touching B4 and B6 Maximum BOOST running time 180m 3h B4 B6 L4 L7 Review and cancel alarms For canceling press down B2 and B3 for 3 seconds In case of alarms L4 L5 L6 L7 flash and...

Page 21: ...box temperature sensor failure Emergency run A 24 Supply air temperature sensor failure System stopped Nr Name Possible values Default value P 01 Sleep mode 0 Off 1 99 sleeping time in seconds 0 P 02...

Page 22: ...n pressure protection System stopped A 43 Extract fan pressure protection System stopped A 44 Internal system error A 45 Heater manual protection Boosting A 46 Preheater manual protection Boosting Sim...

Page 23: ...re B1 B2 B3 I1 B4 B5 Number Definition Number Definition I1 Current operating mode B1 STANDBY AHU is stopped B2 BUILDING PROTECTION maintain minimal air move ment Temperature can be maintained dependi...

Page 24: ...perating mode B9 List of current faults B4 Review or modify set temperatures for all modes B10 Service menu B5 Filter maintenance status B11 Show previous menu row B6 Set AHU control unit s date and t...

Page 25: ...mode I4 Room air temperature during comfort mode B4 On off switch for temperature maintaining function during economy mode I5 State of temperature maintaining function during build ing protection mode...

Page 26: ...ivated on oc currence of selected event I5 Event time 24h format B5 Buttons to select active weekdays for selected event B6 Dials to set event hour and minute I1 B1 B5 I4 B5 I3 B2 I3 I2 B6 I5 B6 B4 Nu...

Page 27: ...s remaining till filter service B1 Button to reset filter timer Use only after filter replacement and at Your own risk B1 I1 B2 I2 Number Definition Number Definition I1 Set boost period B1 Button to...

Page 28: ...Default range Number Definition Default range I1 Function state green strip on gray off OFF B1 Function on off switch I2 Set temperature indication B2 Buttons to increase value I3 Minimum day temperat...

Page 29: ...3 3 STEP_B X13 4 STEP_A X13 5 STEP_A X13 6 24VDC N3 MCB X4 1 DI4 X4 2 12VDC N3 MCB X5 1 AI1 NTC X5 2 GND X5 3 AI2 NTC X5 4 GND X5 5 AI3 NTC X5 6 GND X6 1 AI5 NTC X6 2 GND N3 MCB Bypass actuator Fire a...

Page 30: ...rba vartotojas Components and cables marked with the dash line connected by SALDA or customer PE N L KE1 EKA 0 3 1F PE N L1 0 10V GND PE1 EKA NIS 1 0 1F 22 22 29 29 27 27 21 21 X3 1 DI1 X3 2 12VDC X3...

Page 31: ...1 control GND X24 2 control 0 10VDC Note connection of the components to the unit The maximum permissible pre heater s power 1kW 230V 50Hz Power circuit at EX2 X 39 Purpose of connectors EX2 X 39 1 pr...

Page 32: ...OFF N L1 L1 M3 Vin GND AO1 Transmitter 1 Vin GND AO1 Transmitter 2 Jumper 5 System mode switch H1 H2 Jumper 6 Fan speed switch 42 42 41 41 37 37 38 38 35 35 39 39 36 40 36 40 37 39 39 40 41 41 38 38 3...

Page 33: ...tor M3 X35 5 Extract air actuator M3 phase DO5 opening X35 6 Extract air actuator M3 phase DO6 closing X35 7 Extract air actuator M3 neutral N 1 Actuator power supply voltage 230 V 50 Hz Extract air R...

Page 34: ...neral GND X28 4 analog input 0 10 V DC Purpose of the connectors START EX1 X27 1 signal output max 100mA X27 2 power supply 24 V DC STOP EX1 X27 3 signal output max 100mA X27 4 power supply 24 V DC Co...

Page 35: ...e connection scheme 1 04 2015 05 13 2015 05 13 2015 05 13 Punktyrine linija pa ym tus komponentus ir kabelius pajungia SALDA arba vartotojas Components and cables marked with the dash line connected b...

Page 36: ...y 1f 230VAC L1 N PE X1 Power in X15 1 24VDC X15 1 24VDC X15 2 GND X15 3 PE N3 MCB 58 59 60 61 62 63 65 72 48 48 50 50 49 49 53 54 55 56 74 52 52 73 56 73 Power in Power in X46 1 L L2 X46 2 N L1 X46 3...

Page 37: ...nas GN YE Green Yellow alias Geltonas PE N L1 10V Tach GND 0 10V in PV H4 PE N L1 10V Tach GND 0 10V in IV H4 N2 N3 N3 N3 N3 43 43 47 47 49 48 48 49 50 50 45 46 46 45 44 44 71 71 68 68 70 70 67 67 69...

Page 38: ...duct Tool for drilling holes are required for its installation CO 2 concentration ppm 3000 Effect on an individual 2500 2000 Reduced concentration drowsi ness headache etc 1500 1000 Pettenkofer limit...

Page 39: ...ust be thoroughly cleaned Check whether operation systems and unit elements as well as automation and automation devices were not damaged during installation all consumers are connected to power suppl...

Page 40: ...40 Smarty 3X P www salda lt 1 LED1 indicator 2 control panel name 1 2 Supply air flow pressure sensor Extract air flow pressure sensor 1 2...

Page 41: ...41 Smarty 3X P www salda lt 1 LED1 indicator 2 control panel name 2 1 2 1...

Page 42: ...42 Smarty 3X P www salda lt 1 2 1 LED1 indicator 2 control panel name 3 remote controller 4 BMS 3 4 1 2...

Page 43: ...er supply line of the electrical heater LED7 Output DO5 of the supply extract air damper control open LED8 Output DO6 of the supply extract air damper control close SL1 DIP switch Purpose ON position...

Page 44: ...tion Fan cleaning Once a year Heat exchanger cleaning Once a year Filter replacement Every 3 4 months NOTE The purchaser is required to fill in the Product maintenance table 2 At least 2 Look at the p...

Reviews: