Recommended remote controllers:
For user and service –
„
FLEX
“
Only for the user –
„
Stouch
“
The proper functioning of the device, at outside air temperatures below -5, is guaranteed by using fresh air pre-heater (to be ordered
additionally). It provides the necessary fresh air temperature at which the system can operate without disruption at optimally sustaining
consumption of electricity.
Performance
Fresh air pre-heater is turned on at the risk of freezing. It is controlled by PID (proportional-integral-derivative controller) controller by 0-10 V signal
according to exhaust air temperature sensor “TE” and the set (service menu items) exhaust temperature limit.
Anti-frost temperature (outside air temperature) limit is set by practical experimental way at + 21 °C of extracted air temperature and 50% relative
humidity. By default fresh air tempe1 °C is preserved by pre-heater. When the temperature reaches -3°C, anti-frost protection stars to work.
Pre-heater (EKA NIS) for anti-frost protection has to be ordered additionally. The pre-heater has overheat protection (protection limiting the tempera-
ture) which starts at + 50 °C and manual which starts at +100°C.
Other information
Adjusting and setting of the function
Configuration is impossible with “Stouch”
Default configuration for unit’s safe and effective operation is - outdoor temperature lower than -5 °C. That’s why the change of the set-
tings is FORBIDDEN:
Menu -> Extra -> Service -> AF1 -> OutDoorTemp – (temperature, which the pre-heater has to preserve according to fresh air sensor LT).
Default value +1 °C.
Smarty 3X VE purpose of the ter-
minals:
32 – protective earth (PE)
33 – neutral (N)
34 – supply phase (L1)
35 – control (COM)
36 – control (0-10VDC)
Connection of a functional node to a ventilation unit:
A preheater is connected to a terminal block of a unit control system “X16”:
Maximum permissible connection power is 1kW (230V 50Hz)
For user –
„
Stouch
“
Smarty 3X VE 3.0 purpose of the ter-
minals:
29 protective earth (PE)
30 – neutral (N)
31 – supply phase (L1)
32 – protective earth (PE)
33 – neutral (N)