26
Smarty 3X VE / Smarty 3X VE 3.0
www.salda.lt
EKA
Forced pressing of the door switch by side tools is prohibited.
All measurement, control and execution devices must be installed in easy-to-access places for maintenance, repair or replacement.
Prior to the unit hand-over to the user, the pre-commissioning must be carried out so that the automatic control system of the ventilation unit operates
properly.
The plug socket must be installed at a distance preventing the unit’s power cable from stretching. The standard length of the unit’s power cable is: ~
2.5 m long from the unit casing.
The supply air sensor (SS) must be installed as far from the unit as the sensor cable enables or to the first branching, turn of the air transportation
system. It is recommended to install supply air sensors as far from the heater (cooler) as possible in order to receive more accurate temperature
measurement results.
Where the supply air heater is used, the supply air sensor (SS) must be installed downstream of the heater (or cooler), if the sensor cable long enough,
or to the first branching, turn of the air transportation system.
Prior to connecting the unit to the power network, the door must be closed.