MONTAGE- UND INSTALLATIONSANLEITUNG

Summary of Contents for SMARTY XV Series

Page 1: ...SMARTY XV DE MONTAGE UND INSTALLATIONSANLEITUNG...

Page 2: ...UNG DES SCHALTNETZTEILS 17 19 DEVICE CONTROL 17 19 1 DESCRIPTION OF THE UNITS FUNCTIONS 17 19 2 SYSTEM MODES 17 19 3 SYSTEM CONTROL 18 19 4 SYSTEM STATES 18 19 5 SETTING DATE AND TIME 19 19 6 SUPPLY A...

Page 3: ...CONCENTRATION ACCORDING TO PETTENKOFER LIMIT 30 21 8 SMARTY X V 1 1 VERSION HEATER CONTROL 30 21 9 SMARTY X V 1 2 VERSION HEATER CONTROL 32 21 10 CONNECTION OF SUPPLY AND EXTRACT AIR DAMPERS 33 21 11...

Page 4: ...auliai Lithuania AHU000000 BN xxxxxx 2019 01 01 SERIAL 2514523357 XXX GAMINIO PAVADINIMAS Nominal voltage frequency Max current Max power consumption Protection class Weight xxx xx VAC Hz x xx A x xx...

Page 5: ...onieren und nicht gesperrt sind Wurde im Ger t ein Rotationsw rmetauscher montiert stellen Sie sicher ob er nicht gesperrt und nicht stecken geblieben ist ber pr fen Sie die Erdung Stellen Sie sicher...

Page 6: ...92 0 21 0 92 Drehzahl min 1 4060 4060 3200 3200 4400 4400 Steuersig nal VDC 0 10 0 10 0 10 0 10 0 10 0 10 Schutzklasse IP54 IP54 IP54 IP54 IP54 IP54 G e s a m t e Leistungsauf nahme Leistung Strom kW...

Page 7: ...rung 7 Zuluftfilter Platte Tasche 8 Abluftfilter Platte Tasche 7 ARBEITSBEDINGUNGEN 5 C o 40 C o 23 C o 40 C o 15 C o 40 C o 5 C o 40 C o 40 C o 40 C o 15 C o 40 C o 5 C o 40 C o 15 C 10 o o C 40 C o...

Page 8: ...hen 5 C und 30 C Der Lagerungsplatz soll vor Schmutz und Wasser gesch tzt werden Es ist nicht empfehlenswert die Anlage ber ein Jahr zu lagern Wenn die Anlage ber ein Jahr gelagert wird ist es vor der...

Page 9: ...ist dem Lieferanten der Anlage zu melden Smarty 2X V Smarty 3X V 1 2 3 4 11 LIEFERUMFANG SMARTY 2 XV 3 XV 4 XV Key M4 Z type 1 Outlet pipe G3 8 1 1 1 Fix PV gasket 6x20 white 550 mm 1180 mm 1180 mm S...

Page 10: ...ie im Kontext der ersten Inbetriebnahmen gezeigt W Figure 12 4 mounting positions W 400 mm Figure 12 5 mounting positions 14 ANSCHLUSS DER LUFTF HRUNG Durchmesser D2 je nach Anlage Right side connecti...

Page 11: ...kuperator 1 kleiner Rohr 2 und Abwassersystem Das Rohr 3 muss eine Winkelneigung von mindestens 3 aufweisen ein Rohr von 1 Meter muss 60mm nach unten geneigt sein Vor Einschaltung des Rekuperators 1 d...

Page 12: ...armanzeige Schalter Systemmodus START STOP Schalter Ventilatorgeschwindigkeit BOOST Bauteil Anschlussm glichkeit modellabh ngig N here Informationen siehe Anleitung 16 ANSCHLUSS DER ANLAGE ZU ELECTRIS...

Page 13: ...Stromnetz angeschlossen ist ob die Hauptschalttafel eingeschaltet ist Schutzvorrichtung ist nicht eingeschaltet oder Stromabflussrelais wurde ausgel st wenn es durch den Installateur montiert wurde N...

Page 14: ...beiten halten Sie alle Arbeitsschutzregelungen ein Ventilatoranschl sse aus der Bedienplatte herausziehen Zuluft Ventilator aus X15 X2 X4 Ventilator f r abgezogene Luft aus X16 X2 X4 In der Ausf hrung...

Page 15: ...wenn jegliche Bewegung im Ventilator zum Stillstand gekommen ist Der W rmetauscher wird einmal im Jahr gereinigt Nehmen Sie die Kassette des W rmetauschers vorsichtig aus und tauchen Sie sie in einen...

Page 16: ...arty 3 4X V 18 6 ABSCHALTUNG DER AUTOMATIK Die vordere Schraube mit der Automatiksohle zum Anlagengeh use befestigt ist abdrehen Automatik durch vorderen Teil herausziehen Anschl sse von der Automatik...

Page 17: ...talled in the software of the control board However operation and control of the device depends on the following Selected control panel Full functionality and configuration possibility can be assured...

Page 18: ...e selection Holiday Schedule Stand by mode blocking Based on the Weekly Schedule the system decides in what mode it will be operating however the user may change it manually The system informs when th...

Page 19: ...ster the supply air temperature reaches 20 C It may be too hot in the premises therefore this function both heats and cools Preferred compensated temperature is displayed in the window MONITORING REQU...

Page 20: ...system in a normal manner the Holiday Schedule period must be deactivated i e zero values must be indicated or dates must be changed Up to five holiday periods can be set The schedule is edited in the...

Page 21: ...is activated Function is activated when it receives an impulse It is deactivated when it receives the impulse again On off Boost ventilation function is controlled Function is on when contactor is on...

Page 22: ...are adjusted in the adjuster environment window ADJUSTER AIR FLOWS ADJUSTING There are 4 of them in the system and they are dedicated to specific modes Building protection Economy Comfort Maximum pow...

Page 23: ...ecirculation function is activated 19 25 DISPLAY AND CONCELLATION OF ALARMS AND WARNINGS The system notifies the user about the system failures by warnings that are canceled automatically and by alarm...

Page 24: ...d 54 Warning Too high condensation level A 25 Alarm Extract air temperature sensor failure System stopped 55 Warning Supply fan failure Emergency run A 26 Alarm Exhaust air temperature sensor failure...

Page 25: ...10V 24VDC_P STEP_B STEP_B STEP_A STEP_A 24VDC_P 3 3V_1W DI4 TACHO2_K DI3 TACHO2_A TACHO1_K DI2 TACHO1_A DI5 12VDC DI6 12VDC DI7 12VDC 12VDC DI8 AI4 NTC GND GND AI3 NTC GND AI2 NTC GND AI1 NTC DI9 3 3...

Page 26: ...4 Fire protection input NC 6 3 3V_1W X5 1 DI5 Electric Preheater automatic protection NC 2 12VDC 3 DI6 Electric Preheater manual protection NC 4 12VDC 5 DI7 Bypass closed NC 6 12VDC 7 DI8 Not used 8 1...

Page 27: ...ower line max 2kW 2 N L1 _2 3 DO2 L L2 _2 X13 1 PE Supply extract air damper control output DO3 Open DO4 Close 0 5A 2 N L1 3 DO3 L L2 4 DO4 L L2 X14 1 DO5 L L2 Not used 2 N L1 3 PE X15 1 PE Supply fan...

Page 28: ...W max 2 24VDC 3 DO2 Alarm indication output STOP 24VDC 1 2W max 4 24VDC C Connector Contactor No Contactor name Functional block name miniEX1 X23 1 DI1 Electric heater manual protection NC 2 12VDC 3 D...

Page 29: ...zones 21 4 SUPPLY AIR CO2 OR RH INPUT 0 10VDC Supply air CO2 or RH input 0 10VDC connection This connection is possible for unit version 1 1 miniMCB basic with EX1 controller Installation diagram Tran...

Page 30: ...nkofer limit Pettenkofer limit Disturbs 500 Pleasant 0 0 1 2 3 4 Duration of the presence in the room in hours Closed windows Controlled ventilation Outdoor air 21 8 SMARTY X V 1 1 VERSION HEATER CONT...

Page 31: ...er X23 connector if the electric heater is equipped with these connection terminals Otherwise jumpers are installed on X23 connector protection inputs 12VDC DI2 DI1 12VDC DI4 DI3 1 2 3 4 5 6 7 8 12VDC...

Page 32: ...0V Power over 0 6 kW 1f DRAWN BY CHECKED BY SIGNATURE DUTIES NAME DATE UAB SALDA Drawing Book CHECKED BY 1 1 2 3 4 4 5 6 7 7 External heater SP56 Principle connection scheme 12 03 2016 06 16 2016 06 1...

Page 33: ...off Set the system s response to danger 5 Go to Menu Service Digital inputs Heater protection Set the manual and automated protection statuses according to the standards it should be NC 6 Go to Menu...

Page 34: ...sistor 4 1kR line pull up resistor 5 1kR line pull down resistor 6 Galvanic isolation disable turn ON when connecting Remote Controller RS_GND will be shorted to GND OFF when connecting to BMS 21 12 O...

Page 35: ...power indication 1W mode LED1 EX1 status LED LED2 12V miniMCB power indication LED3 3 3V miniMCB power indication ON mode LED4 MiniMCB status LED LED5 Communication line Transmit indication LED6 Comm...

Page 36: ...umper 7 Punktyrine linija pa ym tus komponentus ir kabelius pajungia SALDA arba vartotojas Components and cables marked with the dash line connected by SALDA or customer Bypass actuator for versions 1...

Page 37: ...power control X22 1 I2C_SCL X22 2 I2C_SDA X22 3 GND X22 4 2 5VDC X22 5 3 3VDC X22 6 12VDC X22 7 24VDC X22 8 GND miniEX1 V0 2 Electrical preheater DI5 automatic protection DI6 manual protection X17 1 L...

Page 38: ...ND AO1 Transmitter 1 System mode switch Fan speed switch 32 30 31 J3 J4 33 Extract air CO2 or RH input 0 10VDC TE Optional Extract air temperature sensor X7 5 AI4 0 10V X7 6 GND X7 7 24VDC N1 miniMCB...

Page 39: ...DUTIES NAME DATE UAB SALDA Drawing Book CHECKED BY 1 1 2 3 4 4 5 6 7 7 EI D Aleksandravi ius EI A klenikas Pyn l Smarty 3XV PE 0k 221 1011 0 1 0 PS 0k Principle connection scheme 8 01 2015 11 24 2015...

Page 40: ...X15 2 N L1 X15 3 DO6 L L2 N1 miniMCB V0 3 X16 1 DO6 L L2 X16 2 N L1 X16 3 PE N1 miniMCB V0 3 X2 1 GND X2 2 AO1 0 10V X2 3 GND X2 4 AO2 0 10V N1 miniMCB V0 3 X4 1 DI2 Tacho1_A X4 2 Tacho1_K X4 3 DI3 T...

Page 41: ...External preheater Control 0 10V Power up to 2kW 1f 230V PE N L1 0 10V GND PE1 EKA NIS 1F W 230V X12 1 PE X12 2 N L1 X12 3 DO2 L L2 N2 miniMCB V0 3 X2 5 GND X2 6 AO3 0 10V N2 miniMCB V0 3 External pr...

Page 42: ...Max 2kW 230V X12 1 PE X12 2 N L1 X12 3 DO2 L L2 N2 miniMCB V0 3 01 6 3 X2 5 GND X2 6 AO3 0 10V N2 miniMCB V0 3 01 5 3 External preheater Control 0 10V Power over 2kW 2f 400V K1 A1 A2 230VAC 11 14 K1...

Page 43: ...394 583 583 Electric power input of the fan drive at maximum flow rate W 82 82 170 170 421 421 Sound power level Lwa dB A 51 51 50 50 54 54 Reference flow m3 s 0 035 0 035 0 077 0 077 0 113 0 113 Refe...

Page 44: ...60204 1 2006 Sicherheit von Maschinen Elektrische Ausr stungen von Maschinen Teil 1 Allgemeine Anforderungen LST EN 60335 1 2012 Sicherheit elektrischer Ger te f r den Hausgebrauch und hnliche Zwecke...

Page 45: ...n den Hersteller zu wenden und den Grund anzugeben sowie die Vorrichtung ins Werk auf eigene Rechnung zuzustellen Der Hersteller kann diesen technischen Ausweis zu jeder Zeit ndern wenn Tippfehler ode...

Page 46: ...46 SMARTY XV v2019 06...

Page 47: ...47 SMARTY XV v2019 06...

Page 48: ...TABELLE DES PRODUKTES Produktname gu lu Nummer Installation Intervall Datum Ventilator Reinigung Einmal im Jahr Heat exchanger cleaning Einmal im Jahr Filterwechsel Alle 3 4 Monate Sehen Sie in der Pr...